Pilone Cables is not an accredited test laboratory and issues no test report. What we do, on request, is measure conductor size, strand count and resistance on a coil drawn on our Lahore line.
The reading is compared with the IEC 60228 limit for that size and class — 4.61 Ω/km for 4 mm² class 2, 7.41 for 2.5 mm², 1.15 for 16 mm². That is a factory verification, and it is worth exactly what an honest measurement is worth: it tells you the conductor is the size on the label. Anything that has to carry a stamp — type tests, insulation and voltage withstand, flame tests — belongs to an accredited laboratory, not to the manufacturer of the cable.
Count the strands and measure one: 7/0.85 is a 4 mm² class 2 conductor, 56/0.30 is the class 5 flexible build of the same size.
Measured on a known length and converted to ohms per kilometre, then read against the IEC 60228 limit in the table below.
| Size | Class 2 strands | Class 2 max Ω/km | Max Ω on a 10 m sample | Class 5 max Ω/km |
|---|---|---|---|---|
| 1.5 mm² | 7/0.53 | 12.1 | 0.121 | 13.3 |
| 2.5 mm² | 7/0.67 | 7.41 | 0.0741 | 7.98 |
| 4 mm² | 7/0.85 | 4.61 | 0.0461 | 4.95 |
| 6 mm² | 7/1.04 | 3.08 | 0.0308 | 3.30 |
| 10 mm² | 7/1.35 | 1.83 | 0.0183 | 1.91 |
| 16 mm² | 7/1.70 | 1.15 | 0.0115 | 1.21 |
| 25 mm² | 7/2.14 | 0.727 | 0.00727 | 0.78 |
Resistance is the only conductor property a standard defines as a hard number, which is why it is the one worth measuring. A purity percentage cannot be read off a meter; ohms can. Measure a known length of the conductor, divide by that length in kilometres, and compare.
Worked example. A 10 m sample of what was sold as 4 mm² class 2 measures 0.052 Ω. Convert: 0.052 ÷ 0.010 km = 5.2 Ω/km. The IEC 60228 limit for that conductor is 4.61 Ω/km, so the sample is 13% above the limit and the conductor is not a 4 mm² class 2 conductor, whatever the sheath says. Had it measured 0.045 Ω — 4.5 Ω/km — it would sit inside the limit.
Two cautions on the reading. The limits are set at 20°C and copper resistance climbs with temperature, so a sample measured in a hot workshop reads high and needs correcting before anyone calls a pass or a fail. And a cheap multimeter is near its floor at these values — 0.0115 Ω for a 10 m sample of 16 mm² is smaller than the resistance of most test leads, so the lead resistance has to be measured and subtracted, or a four-wire measurement used.
Stated plainly, because the alternative is a page of implied credentials. Pilone Cables holds no third-party test report and publishes none. We do not run type tests, insulation thickness or insulation resistance tests, high-voltage withstand tests, or any flame or smoke test. We issue no certificate, and a measurement we hand you is our word, not an accredited result.
If a tender or an inspector needs a report, an accredited testing laboratory is the right route and a manufacturer checking its own cable is not a substitute for one. What we can honestly offer is the spec for every size we draw, and a measurement on a coil that came off our line.
Size, core count and voltage rating are printed along the sheath. Fixed wiring cable in PVC is a 450/750 V cable; light flexible cord is 300/500 V. If the print and the invoice disagree, stop there.
Seven thick strands is a class 2 fixed-wiring conductor; dozens of fine strands is class 5 flexible. 7/0.85 and 56/0.30 are both 4 mm², but they are not interchangeable in a terminal.
Cut a known length — 10 m is enough, and the table above gives the limit for that length. Anything shorter and lead resistance swamps the reading. Once you have it, bring the coil or a 10 m offcut to the Lahore factory and we take the resistance reading with you.
Checking whether the metal is really copper rather than copper-clad aluminium is a different measurement again — it is a mass check, not a resistance check, and the method is on how to check the conductor yourself. The wider list of questions worth putting to any supplier is on choosing a cable company in Pakistan.
Send the size and the invoice on WhatsApp, then bring the coil or a 10 m offcut to the Lahore factory and we take the conductor and resistance reading with you. Mon–Sat, 09:00–18:00.