Cable size calculator

Enter the load, the supply and the run length. You get the smallest copper size that carries the current, keeps volt drop inside 2.5%, and takes a standard breaker — with the numbers behind it. Sized for Pakistan supply: 230 V single-phase, 400 V three-phase.

Add up everything on this circuit. If you know the running current — motors, inverters, anything with a low power factor — enter amps instead.

Supply

One way, from the distribution board to the load. Long runs are decided by volt drop, not by current.

Pick how the cable will run. Inside conduit, bunched, or in a hot roof space the cable runs hotter, so the calculator allows for it.

Result

Enter a load. The size, the capacity it needs where you are installing it, the volt drop over your run, and the breaker it takes all appear here.

Getting the inputs right

Add up the circuit

Every appliance fed by this cable, not just the biggest one. A 1.5 ton AC at 1500 W plus 200 W of lights is a 1700 W circuit.

Measure the run

Distance from the distribution board to the appliance, one way, following the route the cable takes — not the straight line across the room.

Leave room to grow

The result is the minimum for the load you entered. If more load will land on the same circuit later, take the next size up now.

How the size is worked out

The calculator holds three conditions at once and returns the smallest size that passes all three: it carries the current where it is installed, the volt drop stays inside the target, and a standard breaker fits between the load and the cable.

The calculator reads the copper rows of our published spec tables: current capacity and volt drop per BS 7671 (IEC 60364-5-52), reference method C. Verify sizing with a licensed electrician for your installation.
AssumptionValue used
Supply voltage230 V single-phase · 400 V three-phase
Power factor1.0 when the load is entered in watts
Current capacityBS 7671 method C (clipped direct), 30°C ambient, PVC insulated copper
Loaded conductors2 single-phase · 3 three-phase
Installation allowance1.00 clipped · 0.80 conduit or bunched · 0.70 hot roof or buried
Correction factorsThe table figures are for clipped direct; the other two apply a flat first-pass allowance of 0.80 and 0.70, not the exact correction factors for your grouping and ambient.
Volt drop target2.5% — 5.75 V at 230 V, 10.00 V at 400 V
Volt drop figuresmV/A/m from the table; three-phase = 2-core figure × 0.866
Breaker checkstandard ratings 6–125 A, sized so Ib ≤ In ≤ Iz
Smallest size returned1.5 mm² (fixed wiring floor)
Range covered1.5 – 35 mm² copper
Not coveredaluminium conductors · DC strings and battery runs — for a solar DC run see the panel to inverter cable guide
The installation allowance is a first-pass margin, not a substitute for the correction factors that apply to your exact grouping, ambient temperature and thermal insulation. A cable that is correct on paper can still overheat in the wrong route. Have a licensed electrician confirm the size, the breaker and the earthing before you buy.

Cable size reference

The same table the calculator reads. Current capacity is what the conductor carries clipped direct at 30°C — derate it for conduit, bunching and heat.

Copper conductors, PVC insulated, 70°C rating. Current capacity and volt drop per BS 7671 reference method C (clipped direct), 30°C ambient. Volt drop is the single-phase 2-core figure; for three-phase multiply by 0.866. Verify sizing with a licensed electrician for your installation.
SizeSingle-phaseThree-phaseVolt dropTypical use
1.5 mm²19.5 A17.5 A29 mV/A/mLights, fans, small appliance sockets
2.5 mm²27 A24 A18 mV/A/m1 ton AC, kitchen and utility sockets
4 mm²36 A32 A11 mV/A/m1.5–2 ton AC, geyser
6 mm²46 A41 A7.3 mV/A/m2 ton AC, AC side of a 3–5 kW inverter
10 mm²63 A57 A4.4 mV/A/mMain connection, AC side of a 5–10 kW inverter
16 mm²85 A76 A2.8 mV/A/mCommercial supply, AC side of a 10–15 kW inverter
25 mm²112 A96 A1.75 mV/A/mSubmains and 3-phase feeders
35 mm²138 A119 A1.25 mV/A/mLarge industrial feeders