4 mm² copper, on its own 20 A type C MCB. Run it as 3-core so the earth is 4 mm² too.
A 1.5 ton air conditioner draws 1500–1800 W, which is 6.8–8.2 A on Pakistan's 220 V supply, and the compressor start puts a brief surge on top of that — as a rule of thumb two to three times the running current, with the plate's LRA as the figure to trust. 4 mm² is rated 36 A clipped direct at 30°C, so it still clears the 20 A breaker after the cable is derated for conduit, grouping and summer heat. 2.5 mm² only survives that arithmetic on a short, cool, surface run — the rule and the working are below.
Start at the rating plate on the outdoor unit: it gives the maximum current for your exact model, and no chart beats it. Where the plate is unreadable, these are the working figures. The arithmetic: 1500 W ÷ 220 V = 6.8 A, 1800 W ÷ 220 V = 8.2 A, so the running current sits in the 6.8–8.2 A band. On top of it comes the compressor start surge, which the breaker curve has to ride out — as a rule of thumb two to three times the running current, though the number to size against is the LRA printed on the plate.
| Parameter | Value |
|---|---|
| Appliance | 1.5 ton split or window air conditioner |
| Power, typical | 1500–1800 W |
| Running current at 220 V | 6.8–8.2 A |
| Start surge | LRA on the plate — rule of thumb, 2–3× running |
| Breaker rating | 20 A MCB |
| Breaker curve | Type C |
| Live and neutral | 4 mm² copper |
| Earth (CPC) | 4 mm² — the third core |
| Cable make-up | 3 core, 450/750 V PVC |
| Termination at the unit | Double-pole isolator |
| Circuit | Dedicated from the DB |
That is the sheet an electrician wants before he opens the wall. The rest of this page is the working behind those rows.
For a 1.5 ton air conditioner in Pakistan, 4 mm² copper on a dedicated 20 A type C MCB is the size that holds in every normal installation: the unit draws 6.8–8.2 A at 220 V, 4 mm² is rated 36 A clipped direct at 30°C, and it keeps a working margin over the breaker once it is derated for conduit, grouping and summer ambient. 2.5 mm², rated 27 A on the same basis, is acceptable only where all four of these are true at once: the run is under 20 metres, the cable is clipped or in surface trunking rather than buried conduit, it is not bundled with other loaded circuits, and the breaker is 16 A rather than 20 A.
The 1.5 ton AC cable size in mm, then, is 4 mm² live, 4 mm² neutral, 4 mm² earth. This is the ladder that decision is read off.
Ask three shops and you get three answers, because each one is quietly assuming a different installation — the conditions above are what the disagreement is really about.
| Size | 2 loaded cores | 3 loaded cores | Voltage drop | Class 2 strands | Class 5 strands | Margin on 20 A |
|---|---|---|---|---|---|---|
| 1.5 mm² | 19.5 A | 17.5 A | 29 mV/A/m | 7/0.53 | 30/0.25 | −0.5 A |
| 2.5 mm² | 27 A | 24 A | 18 mV/A/m | 7/0.67 | 50/0.25 | +7 A |
| 4 mm² | 36 A | 32 A | 11 mV/A/m | 7/0.85 | 56/0.30 | +16 A |
| 6 mm² | 46 A | 41 A | 7.3 mV/A/m | 7/1.04 | 84/0.30 | +26 A |
Every figure above is a 30°C, clipped-direct number, and nobody installs like that. Take a real job: master bedroom in Lahore, 18 m from the distribution board, cable in conduit chased into the wall, fixed-speed 1.5 ton.
Running current is 1800 ÷ 220 = 8.2 A, and both sizes carry that on paper. The question is what they carry after correction. Conduit in a wall runs hotter than open air, and a Lahore roof space in June is nowhere near 30°C, so both figures come down. Suppose the correction factors for your method and ambient multiply out to 0.75: 2.5 mm² becomes 27 × 0.75 = 20.3 A against a 20 A breaker — the margin is gone. 4 mm² becomes 36 × 0.75 = 27 A, still 7 A clear.
Take the exact correction factors for your method and ambient from BS 7671, or have your electrician do it. The point is not the 0.75 — it is that the derated number, never the table number, is what the breaker has to sit under. Most sizing charts skip that step, and it is the whole argument.
Heat decides the size on short runs, length decides it on long ones. Voltage drop is the cable's own loss: millivolts per amp per metre, times the current, times the one-way run.
| Run | 2.5 mm² | 4 mm² | 6 mm² |
|---|---|---|---|
| 10 m | 1.48 V | 0.90 V | 0.60 V |
| 15 m | 2.21 V | 1.35 V | 0.90 V |
| 20 m | 2.95 V | 1.80 V | 1.20 V |
| 25 m | 3.69 V | 2.26 V | 1.50 V |
| 30 m | 4.43 V | 2.71 V | 1.80 V |
| 40 m | 5.90 V | 3.61 V | 2.39 V |
Hold the installation to 3% of 220 V — 6.6 V — and give the AC final circuit half of it, 3.3 V, because the submain from the meter to the board has already spent the rest. On that budget 2.5 mm² runs 3.3 ÷ 0.148 = 22 m, 4 mm² runs 3.3 ÷ 0.090 = 37 m, 6 mm² runs 55 m. So 2.5 mm² is out of budget at about the length an ordinary house run reaches, while 4 mm² still has room at the far corner of a double-storey plot. Check your own length in the voltage drop calculator; on a 2 ton unit the same sum bites far earlier, as the 2 ton AC wire size guide shows.
4 mm² copper wire, apne alag 20 A MCB par. Trade mein isko 7/.036 kehte hain. AC 220 volt par takreeban 8 amp kheenchta hai, magar compressor start hote waqt current aam qaida ke tor par do se teen guna ho jata hai — asal figure plate par likha LRA hai, aur isi liye wire running current se bara liya jata hai. 3-core lein, taake earth bhi 4 mm² ho.
Dukaan par aksar 7/.029 (jo 2.5–3 mm² ke naam se bikta hai) diya jata hai. Woh sirf tab chalta hai jab run 20 meter se kam ho, wire deewar ke andar conduit mein na ho, aur breaker 16 A ho. Warna garmi aur conduit ke baad uska margin khatam ho jata hai.
Same unit, same 18 m run, peak hours, supply sagging. The watts do not change, so the current rises: 1800 ÷ 190 = 9.5 A instead of 8.2 A. The cable's own drop then stacks on top of the sag at the unit's terminals — 18 × 9.5 × 18 ÷ 1000 = 3.08 V on 2.5 mm², and 11 × 9.5 × 18 ÷ 1000 = 1.88 V on 4 mm². The compressor sees about 187 V one way, 188 V the other.
Read those two numbers honestly: going up a size buys 1.2 V. Cable size is not the defence against a sagging supply — a stabilizer is. Take 4 mm² for the derating margin and the run length, not because thicker copper will fix the voltage on your street.
Half the confusion here is that the shop and the standard speak different languages. Ask for a size in mm² and you get quoted a strand code: seven strands of 0.036 inch is 7/.036. The codes are imperial and do not land exactly on the IEC nominal areas, which is why one wire has two names.
| Trade code (nominal) | Actual area | Sold as | Current capacity |
|---|---|---|---|
| 3/.029 | 1.29 mm² | 1.5 mm² | 19.5 A |
| 7/.029 | 3.0 mm² | 2.5–3 mm² | 27 A |
| 7/.036 | 4.6 mm² | 4 mm² | 36 A |
| 7/.044 | 6.9 mm² | 6–7 mm² | 46 A |
| 7/.052 | 9.6 mm² | 10 mm² | 63 A |
| 7/.064 | 14.5 mm² | 16 mm² | 85 A |
Ask for 7/.036 and you get what this guide calls 4 mm². Ask for 7/.029 and you get the 2.5–3 mm² wire most shops reach for when a customer says "AC ka wire" — the one that runs out of margin first on a 20 A breaker in conduit. 4mm wire for an AC point is the size we draw most of, made as 4mm 3 core standard cable and 4mm 3 core flexible cable.
A split install is two cable purchases, and most sizing guides price only one. Measure both before you ask for a rate.
| Run | What it carries | Cable |
|---|---|---|
| Distribution board to the isolator | The full load, 8.2 A | 4 mm² 3 core |
| Isolator to the outdoor unit | The full load, short tail | 4 mm² 3 core |
| Indoor unit to outdoor unit | Supply and control cores | Per the unit manual |
Cable is sold by the coil in Pakistan and coil lengths differ between makers, so ask for the coil length with the rate — it decides whether one AC point costs you part of a coil or all of it. Total your runs, add a metre at each end, and send that figure with your city; we quote against your metres, not a guess. The interconnecting run has its own rules, set out in the split AC interconnecting cable guide.
Class 2 stranded copper, 7/0.85, PVC insulated and sheathed, 450/750 V, drawn on the Pilone line in Lahore. Rated 36 A clipped direct at 30°C.
This is the price of the wire, not the air conditioner. Cable tracks the daily copper rate, so we quote per metre and per coil on WhatsApp — send the length and your city for the exact figure.
For an AC point take the 3 core version, so the earth is 4 mm² too: 4mm 3 core standard cable for a fixed run in conduit, or 4mm 3 core flexible cable where the tail bends around the condenser. The 2 core sizes — 4mm 2 core cable price, 4mm 2 core flexible cable — suit circuits with the earth run separately.
We draw the copper in Lahore and sell it at the day's rate — no dealer margin, and the same line that made the coil answers the message. Tell us the metres and your city: Punjab in 1–2 days, rest of Pakistan in 2–4.