Skip to content
Factory-direct from Lahore · Nationwide delivery in 2–4 days +92 319 4262451 WhatsApp

What size wire for a 1.5 ton AC in Pakistan — 2.5mm or 4mm?

PILONE CABLES TECHNICAL TEAM

4 mm² copper, on its own 20 A type C MCB. Run it as 3-core so the earth is 4 mm² too.

A 1.5 ton air conditioner draws 1500–1800 W, which is 6.8–8.2 A on Pakistan's 220 V supply, and the compressor start puts a brief surge on top of that — as a rule of thumb two to three times the running current, with the plate's LRA as the figure to trust. 4 mm² is rated 36 A clipped direct at 30°C, so it still clears the 20 A breaker after the cable is derated for conduit, grouping and summer heat. 2.5 mm² only survives that arithmetic on a short, cool, surface run — the rule and the working are below.

The whole circuit sheet, not just the wire

Start at the rating plate on the outdoor unit: it gives the maximum current for your exact model, and no chart beats it. Where the plate is unreadable, these are the working figures. The arithmetic: 1500 W ÷ 220 V = 6.8 A, 1800 W ÷ 220 V = 8.2 A, so the running current sits in the 6.8–8.2 A band. On top of it comes the compressor start surge, which the breaker curve has to ride out — as a rule of thumb two to three times the running current, though the number to size against is the LRA printed on the plate.

Circuit sheet for one 1.5 ton unit on a 220 V single-phase supply. Copper, PVC, BS 7671 reference method C (clipped direct), 30°C ambient; conductor data per IEC 60228. Check your own rating plate first. Verify sizing with a licensed electrician for your installation.
ParameterValue
Appliance1.5 ton split or window air conditioner
Power, typical1500–1800 W
Running current at 220 V6.8–8.2 A
Start surgeLRA on the plate — rule of thumb, 2–3× running
Breaker rating20 A MCB
Breaker curveType C
Live and neutral4 mm² copper
Earth (CPC)4 mm² — the third core
Cable make-up3 core, 450/750 V PVC
Termination at the unitDouble-pole isolator
CircuitDedicated from the DB

That is the sheet an electrician wants before he opens the wall. The rest of this page is the working behind those rows.

The best wire for 1.5 ton AC points — and the one exception

For a 1.5 ton air conditioner in Pakistan, 4 mm² copper on a dedicated 20 A type C MCB is the size that holds in every normal installation: the unit draws 6.8–8.2 A at 220 V, 4 mm² is rated 36 A clipped direct at 30°C, and it keeps a working margin over the breaker once it is derated for conduit, grouping and summer ambient. 2.5 mm², rated 27 A on the same basis, is acceptable only where all four of these are true at once: the run is under 20 metres, the cable is clipped or in surface trunking rather than buried conduit, it is not bundled with other loaded circuits, and the breaker is 16 A rather than 20 A.

The 1.5 ton AC cable size in mm, then, is 4 mm² live, 4 mm² neutral, 4 mm² earth. This is the ladder that decision is read off.

Ask three shops and you get three answers, because each one is quietly assuming a different installation — the conditions above are what the disagreement is really about.

Margin is the two-core capacity less the 20 A MCB rating, before derating. Read the two-core column for a single-phase AC point even on a 3 core cable, because live and neutral are the only loaded conductors; the three-core column is for three-phase. Copper, PVC. Current capacity and voltage drop per BS 7671, reference method C (clipped direct), 30°C ambient; conductor and stranding data per IEC 60228. Verify sizing with a licensed electrician for your installation.
Size2 loaded cores3 loaded coresVoltage dropClass 2 strandsClass 5 strandsMargin on 20 A
1.5 mm²19.5 A17.5 A29 mV/A/m7/0.5330/0.25−0.5 A
2.5 mm²27 A24 A18 mV/A/m7/0.6750/0.25+7 A
4 mm²36 A32 A11 mV/A/m7/0.8556/0.30+16 A
6 mm²46 A41 A7.3 mV/A/m7/1.0484/0.30+26 A

Where the 2.5-vs-4 argument is actually settled

Every figure above is a 30°C, clipped-direct number, and nobody installs like that. Take a real job: master bedroom in Lahore, 18 m from the distribution board, cable in conduit chased into the wall, fixed-speed 1.5 ton.

Running current is 1800 ÷ 220 = 8.2 A, and both sizes carry that on paper. The question is what they carry after correction. Conduit in a wall runs hotter than open air, and a Lahore roof space in June is nowhere near 30°C, so both figures come down. Suppose the correction factors for your method and ambient multiply out to 0.75: 2.5 mm² becomes 27 × 0.75 = 20.3 A against a 20 A breaker — the margin is gone. 4 mm² becomes 36 × 0.75 = 27 A, still 7 A clear.

Take the exact correction factors for your method and ambient from BS 7671, or have your electrician do it. The point is not the 0.75 — it is that the derated number, never the table number, is what the breaker has to sit under. Most sizing charts skip that step, and it is the whole argument.

How far the AC can be from the distribution board

Heat decides the size on short runs, length decides it on long ones. Voltage drop is the cable's own loss: millivolts per amp per metre, times the current, times the one-way run.

Volts lost in the cable at 8.2 A, the top of the running band at 220 V. Figure = mV/A/m × 8.2 A × run ÷ 1000. Run is one way, along the route the cable takes. Voltage drop per BS 7671, reference method C, 30°C, copper, PVC. Verify sizing with a licensed electrician for your installation.
Run2.5 mm²4 mm²6 mm²
10 m1.48 V0.90 V0.60 V
15 m2.21 V1.35 V0.90 V
20 m2.95 V1.80 V1.20 V
25 m3.69 V2.26 V1.50 V
30 m4.43 V2.71 V1.80 V
40 m5.90 V3.61 V2.39 V

Hold the installation to 3% of 220 V — 6.6 V — and give the AC final circuit half of it, 3.3 V, because the submain from the meter to the board has already spent the rest. On that budget 2.5 mm² runs 3.3 ÷ 0.148 = 22 m, 4 mm² runs 3.3 ÷ 0.090 = 37 m, 6 mm² runs 55 m. So 2.5 mm² is out of budget at about the length an ordinary house run reaches, while 4 mm² still has room at the far corner of a double-storey plot. Check your own length in the voltage drop calculator; on a 2 ton unit the same sum bites far earlier, as the 2 ton AC wire size guide shows.

1.5 ton AC ke liye kitne mm ka wire chahiye?

4 mm² copper wire, apne alag 20 A MCB par. Trade mein isko 7/.036 kehte hain. AC 220 volt par takreeban 8 amp kheenchta hai, magar compressor start hote waqt current aam qaida ke tor par do se teen guna ho jata hai — asal figure plate par likha LRA hai, aur isi liye wire running current se bara liya jata hai. 3-core lein, taake earth bhi 4 mm² ho.

Dukaan par aksar 7/.029 (jo 2.5–3 mm² ke naam se bikta hai) diya jata hai. Woh sirf tab chalta hai jab run 20 meter se kam ho, wire deewar ke andar conduit mein na ho, aur breaker 16 A ho. Warna garmi aur conduit ke baad uska margin khatam ho jata hai.

What happens when the supply drops to 190 V

Same unit, same 18 m run, peak hours, supply sagging. The watts do not change, so the current rises: 1800 ÷ 190 = 9.5 A instead of 8.2 A. The cable's own drop then stacks on top of the sag at the unit's terminals — 18 × 9.5 × 18 ÷ 1000 = 3.08 V on 2.5 mm², and 11 × 9.5 × 18 ÷ 1000 = 1.88 V on 4 mm². The compressor sees about 187 V one way, 188 V the other.

Read those two numbers honestly: going up a size buys 1.2 V. Cable size is not the defence against a sagging supply — a stabilizer is. Take 4 mm² for the derating margin and the run length, not because thicker copper will fix the voltage on your street.

Wiring the AC point

Current capacity depends on how the cable is installed. Derate for conduit, grouping, and ambient temperature above 30°C, and read the correction factors for your own method out of BS 7671. Have a licensed electrician confirm the size for your load and run length — or start with the cable size calculator.

7/29, 7/36: what the trade codes mean in mm²

Half the confusion here is that the shop and the standard speak different languages. Ask for a size in mm² and you get quoted a strand code: seven strands of 0.036 inch is 7/.036. The codes are imperial and do not land exactly on the IEC nominal areas, which is why one wire has two names.

Trade code (nominal) is the imperial strand-diameter code Pakistani shops sell by; the area it computes to does not coincide exactly with the IEC 60228 nominal area the cable is sold as. Capacity is read against the nominal size, two loaded conductors, BS 7671 reference method C, 30°C, copper, PVC. Verify sizing with a licensed electrician for your installation.
Trade code (nominal)Actual areaSold asCurrent capacity
3/.0291.29 mm²1.5 mm²19.5 A
7/.0293.0 mm²2.5–3 mm²27 A
7/.0364.6 mm²4 mm²36 A
7/.0446.9 mm²6–7 mm²46 A
7/.0529.6 mm²10 mm²63 A
7/.06414.5 mm²16 mm²85 A

Ask for 7/.036 and you get what this guide calls 4 mm². Ask for 7/.029 and you get the 2.5–3 mm² wire most shops reach for when a customer says "AC ka wire" — the one that runs out of margin first on a 20 A breaker in conduit. 4mm wire for an AC point is the size we draw most of, made as 4mm 3 core standard cable and 4mm 3 core flexible cable.

How many metres of wire for one AC point

A split install is two cable purchases, and most sizing guides price only one. Measure both before you ask for a rate.

What to measure for a single-phase 1.5 ton install. The interconnecting cable between the indoor and outdoor unit is specified by the unit manufacturer — take that size from the unit manual or the plate, not from a chart.
RunWhat it carriesCable
Distribution board to the isolatorThe full load, 8.2 A4 mm² 3 core
Isolator to the outdoor unitThe full load, short tail4 mm² 3 core
Indoor unit to outdoor unitSupply and control coresPer the unit manual

Cable is sold by the coil in Pakistan and coil lengths differ between makers, so ask for the coil length with the rate — it decides whether one AC point costs you part of a coil or all of it. Total your runs, add a metre at each end, and send that figure with your city; we quote against your metres, not a guess. The interconnecting run has its own rules, set out in the split AC interconnecting cable guide.

The cable for this job

Two-core standard cable with black outer sheath, cut back to show red and black insulated stranded copper conductors
4MM² · 2 CORE · 450/750 V · CU CLASS 2

4mm 2 Core Standard Cable

Class 2 stranded copper, 7/0.85, PVC insulated and sheathed, 450/750 V, drawn on the Pilone line in Lahore. Rated 36 A clipped direct at 30°C.

Factory-direct price
Contact for quote
Message us for today’s rate
WhatsApp for today's rate

This is the price of the wire, not the air conditioner. Cable tracks the daily copper rate, so we quote per metre and per coil on WhatsApp — send the length and your city for the exact figure.

For an AC point take the 3 core version, so the earth is 4 mm² too: 4mm 3 core standard cable for a fixed run in conduit, or 4mm 3 core flexible cable where the tail bends around the condenser. The 2 core sizes — 4mm 2 core cable price, 4mm 2 core flexible cable — suit circuits with the earth run separately.

Frequently asked

1.5 ton AC ke liye kaun sa wire use karen?
4 mm² copper — trade code 7/.036 — apne alag 20 A MCB par, aur 3-core lein taake earth bhi 4 mm² ho. AC 220 volt par takreeban 8 amp kheenchta hai, magar start hote waqt current aam qaida ke tor par do se teen guna ho jata hai — asal figure plate par likha LRA hai.
Is 2.5mm wire enough for a 1.5 ton AC, or do I need 4mm?
4 mm². Both sizes carry the 8 A running load — 2.5 mm² is rated 27 A, 4 mm² is rated 36 A. The difference shows after derating: in conduit in summer heat, 2.5 mm² loses its margin over the 20 A breaker while 4 mm² keeps about 7 A of it. 2.5 mm² is defensible only on a short, clipped, unbundled run on a 16 A breaker.
Is 7/29 wire OK for a 1.5 ton AC?
7/.029 is the trade code for about 3 mm², sold as 2.5–3 mm². It will run the unit on a short surface run, which is why shops recommend it. On a 20 A breaker in conduit it is the size that runs out of margin first. Ask for 7/.036 — that is the 4 mm².
How many amps does a 1.5 ton AC draw at 220V?
1500 W ÷ 220 V = 6.8 A and 1800 W ÷ 220 V = 8.2 A, so 6.8–8.2 A running. On top of that comes the compressor start surge — as a rule of thumb two to three times the running current, but the figure to size against is the LRA printed on the plate. Read your own rating plate: inverter and fixed-speed models differ.
Which MCB for a 1.5 ton AC, 16A or 20A, and B curve or C curve?
20 A, type C, on a circuit of its own — never shared with room sockets or lights. The 20 A rating sits above the 6.8–8.2 A running current with room for the surge, and 4 mm² at 36 A sits above the breaker. A type C curve rides the compressor inrush; a type B will nuisance-trip at switch-on.
Does an inverter 1.5 ton AC need a thinner wire than a non-inverter?
No. The 1.5 ton inverter AC wire size is the same 4 mm². The compressor ramps instead of slamming on, so the surge is smaller and the running current varies with room load — but the maximum current on the plate is what the cable is sized against, and that does not shrink. See the inverter AC cable guide.
Is the wire different for a split AC and a window AC?
The power cable is the same 4 mm² at this tonnage. What differs is the second cable: a split unit also needs an interconnecting cable between indoor and outdoor unit, sized to the unit manual. A window unit has none, and is more often plugged into a socket than hardwired through an isolator.
What is the 1.5 ton AC wire price in Pakistan, per meter and per coil?
This is the price of the wire, not the air conditioner. Copper cable is priced off the day's copper rate, so we quote per metre and per coil on WhatsApp rather than publish a figure that goes stale. Send the size, total metres and your city: Punjab in 1–2 days, rest of Pakistan in 2–4.
What is the 1.5 ton AC wire required for a house point?
4 mm² three-core copper, live, neutral and earth all 4 mm², on its own 20 A type C MCB, terminated at a double-pole isolator beside the outdoor unit. For the metres, measure the route from the distribution board to the isolator and add a metre at each end. A split unit needs a second cable as well, between indoor and outdoor unit, sized to the unit manual.

4mm wire for the AC point, at the factory rate

We draw the copper in Lahore and sell it at the day's rate — no dealer margin, and the same line that made the coil answers the message. Tell us the metres and your city: Punjab in 1–2 days, rest of Pakistan in 2–4.

WhatsApp for a quote