An AC point takes 2.5 mm² copper at 1 ton, 4 mm² at 1.5 and 2 ton, 6 mm² at 3 ton and 10 mm² at 4 ton, three-core with the earth the same size as the live, each on its own type C MCB — 16, 20, 25 and 32 A in that order. Those sizes assume a 220 V single-phase supply and cable clipped direct at 30°C; in conduit, bunched with other circuits, or on a long run from the board, take the next size up.
The circuit is the same shape at every tonnage: one cable from the distribution board, one breaker of its own, a double-pole isolator at the outdoor unit. What changes is the current — watts ÷ 220 V gives the running current, the breaker is picked above that, and the cable has to stay above the breaker after it is derated for conduit and summer heat.
Read the rating plate on the outdoor unit before you read this chart. It gives the maximum current for your exact model, and no chart beats it. Where the plate is gone or unreadable, these are the working figures for a 220 V single-phase house supply. The arithmetic is one division: 2000 W ÷ 220 V = 9.1 A for a 2 ton unit, 3600 W ÷ 220 V = 16.4 A for a 3 ton. The chart rounds those to the nearest amp.
| Tonnage | Power, typical | Current at 220 V | MCB | Live and neutral | Earth | Trade code |
|---|---|---|---|---|---|---|
| 1 ton | 1000–1200 W | 4.5–5.5 A | 16 A type C | 2.5 mm² | 2.5 mm² | 7/.029 |
| 1.5 ton | 1500–1800 W | 6.8–8.2 A | 20 A type C | 4 mm² | 4 mm² | 7/.036 |
| 2 ton | 2000–2400 W | 9–11 A | 25 A type C | 4 mm² to 25 m, then 6 | same as live | 7/.036 |
| 3 ton | 3000–3600 W | 14–16 A | 25 A type C | 6 mm² | 6 mm² | 7/.044 |
| 4 ton | 4000–4800 W | 18–22 A | 32 A type C | 10 mm² | 10 mm² | 7/.052 |
Two things in that chart are worth saying out loud. The earth is the same size as the live, which is what the third core is for — not a thinner strand tucked in beside it. And the breaker is a type C in every row, because a type B will nuisance-trip on the compressor inrush and the householder will blame the cable. 1.5 ton AC wiring is the point most Pakistani houses actually build, and its 4 mm² row is the one this chart gets argued about.
Four steps, in this order. Skip the first and the rest is guesswork.
The outdoor unit carries a rating plate with its maximum current and its LRA, the locked-rotor figure the start surge reaches. Those two numbers beat any tonnage chart, including this one.
Watts ÷ 220 V. A 1.5 ton unit at 1800 W is 8.2 A. Pakistan is 220 V nominal, so charts worked at 230 or 240 V read low here — and when the supply sags in peak hours the same watts pull more amps, not fewer.
The MCB sits above the running current with room for the surge: 16 A, 20 A, 25 A or 32 A from the chart, type C, on a way of its own in the board.
Not above the running current — above the breaker, after derating. Cable in conduit in a Lahore summer carries less than its table figure, and that reduced number is what has to clear the MCB.
Step four is the one the charts skip, and it is where most disagreements about AC wire size actually come from. Two shops quoting different sizes are usually assuming different installations, not different units. The derating arithmetic is worked in full on 1.5 ton AC wire size, where the margin decides between 2.5 and 4 mm².
Every size in the chart is read off this ladder. The trade code column is what you will actually be quoted at the counter: AC wires are sold in Pakistan by imperial strand code, standards work in mm², and the two do not land on each other exactly.
| Size | 2 loaded cores | 3 loaded cores | Voltage drop | Class 2 strands | Trade code | On an AC circuit |
|---|---|---|---|---|---|---|
| 1.5 mm² | 19.5 A | 17.5 A | 29 mV/A/m | 7/0.53 | 3/.029 | Lights and fans only |
| 2.5 mm² | 27 A | 24 A | 18 mV/A/m | 7/0.67 | 7/.029 | 1 ton |
| 4 mm² | 36 A | 32 A | 11 mV/A/m | 7/0.85 | 7/.036 | 1.5 and 2 ton |
| 6 mm² | 46 A | 41 A | 7.3 mV/A/m | 7/1.04 | 7/.044 | 3 ton, long 2 ton runs |
| 10 mm² | 63 A | 57 A | 4.4 mV/A/m | 7/1.35 | 7/.052 | 4 ton |
| 16 mm² | 85 A | 76 A | 2.8 mV/A/m | 7/1.70 | 7/.064 | Submain feeding several points |
1.5 mm² is on the ladder to be ruled out. At 19.5 A it sits below even a 20 A breaker before any derating, so on an AC circuit the cable would fail before the protection did. When two or three AC points go in at once, it is the last row that matters: the submain and the main switch become the limit long before the individual point cables do, so total the load before adding the way.
Heat decides the size on short runs; length decides it on long ones. Voltage drop is the cable's own loss — millivolts per amp per metre, times the current, times the one-way run — and it is the reason the same tonnage takes a different size at the far corner of a plot than it does next to the board.
| Tonnage | 2.5 mm² | 4 mm² | 6 mm² | 10 mm² |
|---|---|---|---|---|
| 1 ton, 5.5 A | 33 m | 55 m | 82 m | 136 m |
| 1.5 ton, 8.2 A | — | 37 m | 55 m | 91 m |
| 2 ton, 11 A | — | 27 m | 41 m | 68 m |
| 3 ton, 16 A | — | — | 28 m | 47 m |
| 4 ton, 22 A | — | — | — | 34 m |
Work one row yourself: a 2 ton unit at 11 A on 4 mm² drops 11 × 11 × 27 ÷ 1000 = 3.27 V over 27 m, which is the budget spent. That is why the 2 ton guide rounds the practical limit to 25 m and goes to 6 mm² beyond it. On a 4 ton, 6 mm² is a special case rather than a flat no — clipped in open air on a short run it can hold, and the 3 and 4 ton guide sets out when. For your own length and current, the voltage drop calculator does the sum.
Size is half the question. The other half is which cable, and anyone asking for the best cable for an AC point is really asking three things at once.
For the sizes in the chart that means 2.5mm 3 core flexible cable at 1 ton, 4mm 3 core standard cable at 1.5 and 2 ton, 6mm 3 core standard cable at 3 ton and 10mm 3 core standard cable at 4 ton. A split unit needs a second cable on top of that, between the indoor and outdoor halves, and its size comes from the unit manual rather than from any chart — that run has its own rules on the split AC interconnecting cable page.
Tonnage par depend karta hai. 1 ton ke liye 2.5 mm² (trade code 7/.029) 16 A MCB par; 1.5 ton ke liye 4 mm² (7/.036) 20 A par; 2 ton ke liye bhi 4 mm², magar 25 meter se lamba run ho to 6 mm²; 3 ton ke liye 6 mm² (7/.044); 4 ton ke liye 10 mm² (7/.052). Har point ka apna alag MCB aur apni alag cable board se aani chahiye.
3-core lein, taake earth bhi live ke barabar ho. Aur pehle outdoor unit ki plate parhein — us par likha maximum current har chart se ziyada sahi hai.
2.5mm on a 16A MCB, and the run length that forces 4mm.
The 2.5-or-4 argument, settled with the derating sum.
Where 4mm runs out of margin and 6mm takes over.
6mm at 3 ton, 10mm at 4 ton, and the isolator.
The second cable, indoor unit to outdoor unit.
Softer start, same conductor. Why it does not shrink.
Send the tonnage, the metres from the board to the outdoor unit and your city. We draw the copper in Lahore and quote the day's rate — Punjab in 1–2 days, rest of Pakistan in 2–4.