Class 5 flexible copper cable for lighting circuits and small appliance runs. Thirty 0.25 mm strands per conductor, PVC insulated and sheathed, made on the Pilone line in Lahore.
Prices track the daily copper rate. Coil and bulk pricing on request.
| Property | Value |
|---|---|
| Conductor | Plain annealed copper, class 5 flexible stranded |
| Nominal area | 1.5 mm² |
| Strand construction | 30 / 0.25 mm |
| Max conductor resistance at 20°C | 13.3 Ω/km |
| Current capacity, 2 loaded conductors | 19.5 A |
| Current capacity, 3 loaded conductors | 17.5 A |
| Voltage drop | 29 mV/A/m |
| Voltage rating | 450/750 V |
| Insulation / sheath | PVC / PVC, 70°C conductor rating |
| Conductor copper weight | ≈ 13.3 kg/km per core |
| Typical use | LED lighting circuits, ceiling and exhaust fans |
Line and neutral only. Lighting drops and appliance runs that take their earth separately.
Line, neutral, and earth. The usual single-phase choice for socket circuits and appliances.
Three phases and neutral. Three loaded conductors bring the rating down to 17.5 A.
Current capacity with two loaded conductors, BS 7671 reference method C, 30°C ambient. Same class 5 copper construction in every size.
We quote 1.5mm flexible at the day's copper rate and dispatch from the Lahore line. Tell us the core count and how many meters you need.