Pick the size you plan to run, the load on it and the length of the run. You get the drop in volts, the drop as a percentage of the supply, and a pass or fail against the 2.5% design target — 5.75 V at 230 V, 10.00 V at 400 V. If the size does not hold it, the calculator names the size that does.
Enter the load. The drop in volts, the drop as a percentage, the voltage left at the load and the longest run this size can take all appear here.
2.10%
Within the 2.5% target
4mm²
Contact for quote Contact for quote Contact for quote Contact for quote Contact for quote Contact for quote Contact for quote Contact for quote Contact for quote Contact for quote Contact for quote Contact for quote Contact for quote
Message us for today’s rate · prices track the daily copper rate
Sizing guidance, not a design. Have a licensed electrician confirm the size, the breaker and the earthing for your installation.
A design current of — over — needs more than 120 mm² copper to stay inside the target. We make copper armoured cable to 95 mm² and aluminium to 120 mm².
One way from the board to the load, along the path the cable actually takes — up the wall, across the ceiling, down again. Not the straight line across the room.
A larger conductor, or a shorter route. The readout gives the longest run this size can take at your load, so you can see which one costs less.
Motors, pumps and compressors draw several times their running current at start. Enter the running current here; have the start condition checked by a licensed electrician.
Volt drop is the conductor’s own resistance eating the supply on its way to the load: the current, the length and the size decide it. The calculator multiplies the size’s mV/A/m figure by the design current and the run length, then compares the result with 2.5% of the supply voltage. It also checks the load against the size’s current capacity, because a run that passes on volt drop can still be over the conductor.
| Assumption | Value used |
|---|---|
| Supply voltage | 230 V single-phase · 400 V three-phase |
| Power factor | 1.0 when the load is entered in watts |
| Volt drop figures | mV/A/m from the spec table — the single-phase 2-core column |
| Three-phase drop | single-phase figure × 0.866 (√3 / 2) |
| Volt drop target | 2.5% — 5.75 V at 230 V, 10.00 V at 400 V |
| Current capacity | BS 7671 method C (clipped direct), 30°C ambient, no derating applied |
| Loaded conductors | 2 single-phase · 3 three-phase |
| Conductor temperature | 70°C PVC — no allowance for a conductor running below its rating |
| Range covered | 0.75 – 120 mm² copper |
| Not covered | aluminium conductors · correction factors for grouping, ambient and thermal insulation · DC strings and battery runs — for a solar DC run see the panel to inverter cable guide |
The same table the calculator reads. Multiply the figure by the current in amps and the run in metres, then divide by 1000, to get the drop in volts.
| Size | Drop, single-phase | Drop, three-phase | Capacity, single-phase | Capacity, three-phase |
|---|---|---|---|---|
| 0.75 mm² | 62 mV/A/m | 53.7 mV/A/m | 6 A | 6 A |
| 1 mm² | 44 mV/A/m | 38.1 mV/A/m | 10 A | 10 A |
| 1.5 mm² | 29 mV/A/m | 25.1 mV/A/m | 19.5 A | 17.5 A |
| 2.5 mm² | 18 mV/A/m | 15.6 mV/A/m | 27 A | 24 A |
| 4 mm² | 11 mV/A/m | 9.53 mV/A/m | 36 A | 32 A |
| 6 mm² | 7.3 mV/A/m | 6.32 mV/A/m | 46 A | 41 A |
| 10 mm² | 4.4 mV/A/m | 3.81 mV/A/m | 63 A | 57 A |
| 16 mm² | 2.8 mV/A/m | 2.42 mV/A/m | 85 A | 76 A |
| 25 mm² | 1.75 mV/A/m | 1.52 mV/A/m | 112 A | 96 A |
| 35 mm² | 1.25 mV/A/m | 1.08 mV/A/m | 138 A | 119 A |
| 50 mm² | 0.93 mV/A/m | 0.81 mV/A/m | 168 A | 144 A |
| 70 mm² | 0.63 mV/A/m | 0.55 mV/A/m | 213 A | 184 A |
| 95 mm² | 0.46 mV/A/m | 0.40 mV/A/m | 258 A | 223 A |
| 120 mm² | 0.36 mV/A/m | 0.31 mV/A/m | 299 A | 259 A |
Send the size, the length in metres and your city. We quote the factory rate for that day and dispatch — Punjab in 1–2 days, rest of Pakistan in 2–4.