Solar DC cable in Pakistan is priced off the day's copper rate, so any printed list goes stale — the prices below fill from our live factory sheet, and one WhatsApp message confirms the same rate against your quantity.
For most residential strings the size question ends at 4 mm² (36 A) or 6 mm² (46 A) single-core DC cable, bought as a red and black pair, per metre or per 90 m coil. Every solar SKU we make is in the table below with its conductor, insulation and current rating beside the price; the full catalog with datasheets lives at solar DC cable.
Thirteen sizes and constructions, smallest to largest. The small sizes up to 6 mm² do panel strings and controller wiring; 10 mm² and up are DC feeders on bigger arrays. The two most-bought sizes also have their own spec pages — 4mm² solar DC and 6mm² solar DC — and each product name links to its own datasheet page — conductor build, resistance, and a WhatsApp line already loaded with that size.
| Product | Conductor | Insulation | Current capacity | Today's price |
|---|---|---|---|---|
| 1-core 0.75mm DC cable | 0.75 mm² · 24/0.20 | PVC / PVC | 6 A | Contact for quote |
| 1-core 1mm DC cable | 1 mm² · 32/0.20 | PVC / PVC | 10 A | Contact for quote |
| 1-core 1.5mm DC cable | 1.5 mm² · 30/0.25 | PVC / PVC | 19.5 A | Contact for quote |
| 1-core 2.5mm DC cable | 2.5 mm² · 50/0.25 | PVC / PVC | 27 A | Contact for quote |
| 1-core 4mm DC cable | 4 mm² · 56/0.30 | PVC / PVC | 36 A | Contact for quote |
| 4mm XLPE/PVC solar wire | 4 mm² · 56/0.30 | XLPE / PVC, 90 °C | 36 A | Contact for quote |
| 1-core 6mm DC cable | 6 mm² · 84/0.30 | PVC / PVC | 46 A | Contact for quote |
| 6mm XLPE/PVC solar wire | 6 mm² · 84/0.30 | XLPE / PVC, 90 °C | 46 A | Contact for quote |
| 6mm double-PVC solar DC wire | 6 mm² · 84/0.30 | PVC / PVC, two layers | 46 A | Contact for quote |
| 10mm² solar DC | 10 mm² · 80/0.40 | PVC / PVC | 63 A | Contact for quote |
| 16mm² solar DC | 16 mm² · 126/0.40 | PVC / PVC | 85 A | Contact for quote |
| 25mm² solar DC | 25 mm² · 196/0.40 | PVC / PVC | 112 A | Contact for quote |
| 35mm² solar DC | 35 mm² · 276/0.40 | PVC / PVC | 138 A | Contact for quote |
A solar cable price in Pakistan is the daily copper rate wearing insulation, so it moves with the metal and no printed figure stays correct for long. As of August 2026, the two sizes that carry most residential solar strings are 4 mm² and 6 mm² single-core DC cable: 4 mm² is rated 36 A and 6 mm² is rated 46 A on the BS 7671 method C reference, and both are sold as a red and black pair, per metre or per 90 m coil. A 6 mm² conductor holds half as much copper again as a 4 mm² conductor — 53.3 kg per kilometre against 35.6 kg — so it always costs more per metre, and the honest way to buy either is a dated factory quote against a named size, insulation type and length. Pilone Cables quotes today's factory rate for every solar DC size on WhatsApp at +92 319 4262451.
Why the numbers move at all — and why a week-old screenshot of this page is not a quote — is the whole subject of how cable is priced in Pakistan and the daily copper rate.
On the DC side the current is modest — a typical string of modern panels works at roughly 12–14 A, and the exact figure is the Imp line on the panel datasheet — so ampacity is rarely what forces the size up. Length is. Every metre of cable eats volts, and volts lost on the string side are watts the inverter never sees.
| Size | mV/A/m | 10 m run | 20 m run | 30 m run | 40 m run |
|---|---|---|---|---|---|
| 4 mm² | 11 | 1.4 V | 2.9 V | 4.3 V | 5.7 V |
| 6 mm² | 7.3 | 0.9 V | 1.9 V | 2.8 V | 3.8 V |
| 10 mm² | 4.4 | 0.6 V | 1.1 V | 1.7 V | 2.3 V |
| 16 mm² | 2.8 | 0.4 V | 0.7 V | 1.1 V | 1.5 V |
Worked at 30 m, which is a common roof-to-inverter run in a two-storey Pakistani house: with the string at 13 A, 4 mm² loses 13 × 30 × 11 ÷ 1000 = 4.29 V, and 6 mm² loses 13 × 30 × 7.3 ÷ 1000 = 2.85 V. In power terms that is 13 × 4.29 = 56 W wasted against 13 × 2.85 = 37 W — a 19 W difference burning in the cable, all day, every sunny day, for twenty-five years of panel life. That arithmetic is why installers put 4 mm² on short strings, step to 6 mm² somewhere past a 20 m run, and go to 10 mm² or 16 mm² for long feeders and combined runs.
System-by-system versions of this sum, with the panel counts and breaker sizes, are in the solar guides: 3 kW, 5 kW, 7 kW, 10 kW, 15 kW and 20 kW, plus the run-by-run map on panel to inverter cable. The battery side is its own problem — low voltage, high current — covered in inverter battery cable.
Same copper, different coat, and the coat is what the roof attacks. PVC left in direct sunlight hardens and cracks over a season or two; the XLPE and double-PVC constructions exist for exactly that duty. This is the honest version of the choice, without selling you the dearer wire where the cheaper one does the job.
| Construction | Conductor rating | Built for | Where it earns its price |
|---|---|---|---|
| PVC / PVC (standard DC) | 70 °C | Indoor and protected DC runs — in conduit, trunking, inside the roof space | The cheapest of the three; right where sun never touches the cable |
| XLPE / PVC solar wire | 90 °C | Exposed rooftop runs in continuous sun and heat | Holds its insulation through summers that harden plain PVC |
| Double-PVC solar DC wire | 70 °C | Exposed runs, as the second sheath takes the weathering | Sits between the two: tougher than single PVC, priced under XLPE |
The practical split most installers land on: XLPE/PVC or double-PVC from the panels to wherever the run enters the building, standard PVC DC cable from there to the inverter if the indoor run is long. The chemistry behind the two compounds is on PVC vs XLPE insulation.
Red is positive, black is negative, and unlike an AC circuit the polarity never alternates — it is fixed the moment the connectors are crimped. Colouring the two conductors differently along their whole length means a polarity mistake at the inverter or a connector is visible before it is expensive. That is why the cable is sold as single cores in a red and black pair rather than as one two-core cable: each leg routes separately, and each is identifiable anywhere you cut it.
The double insulation is about where the cable lives and what it carries. A string sits on an open roof — UV, heat, abrasion against tray and clamp — and it is live whenever the sun is up, at up to the 1000 V DC printed on the sheath. DC current does not pass through zero the way AC does, so a DC fault arc has no natural extinguishing point; the second insulation layer means one nick or one hardened patch does not put a live conductor against the roof. The full comparison with ordinary house wire is on DC cable vs AC cable — and no, single-insulated building wire is not a substitute on the panel side.
Because the cable is mostly copper, and copper is a world commodity quoted daily in dollars. A 90 m coil of 6 mm² holds 53.3 × 0.090 = 4.8 kg of conductor before a gram of insulation, so when the metal or the rupee moves, the coil moves with it. That is why this page carries markers filled from the day's sheet instead of printed figures that would be stale by Thursday.
It is also why the way to buy is a dated quote on the whole list at once. Send the sizes, the metres or coils per size, the insulation type, and your city; the reply is one factory rate for everything, set against the same day's copper. Punjab delivers in 1–2 days, the rest of Pakistan in 2–4. Installers buying every month should look at cables for solar installers; the rate structure across the full catalog, AC sizes included, is on the cable price list.
Every size with its full datasheet: conductor build, resistance, voltage rating, and a WhatsApp line per size.
The whole DC route, run by run — string, combiner, feeder — with a size against each leg.
The AC side of a net-metered system: inverter to distribution board to meter, and the sizes that side needs.
Send the sizes, the metres or coils per size, the insulation type — PVC, double-PVC or XLPE — and your city. One factory rate on the whole solar list, set against today's copper, with the coil length stated. Punjab in 1–2 days, rest of Pakistan in 2–4.