Skip to content
Factory-direct from Lahore · Nationwide delivery in 2–4 days +92 319 4262451 WhatsApp

What cable size for a 20kW solar system in Pakistan?

PILONE CABLES TECHNICAL TEAM

6 mm² per DC string, 10 mm² where two strings share a home run, 10 mm² four-core on the AC side to a 40 A MCB per phase, 10 mm² for the array earth.

A 20 kW inverter on a 400 V three-phase connection puts out 20000 ÷ (1.732 × 400) = 28.9 A per phase, which is a 40 A MCB. On the roof, forty panels usually run as four strings of ten, each at about 17.5 A of design current, and 6 mm² holds a 3% voltage drop out to an 86 m route on a 370 V string. The 25 mm² figure often quoted for a system this size is not the string size — it is what a single home run carrying all four strings at once needs, and most 20 kW roofs never build one.

Where a 20kW array stops behaving like a big house system

Twenty kilowatts is the size at which the AC side gets easy and the DC side gets fiddly. On three phases the inverter output splits three ways and the cable to the board is modest. On the roof, forty panels are four strings, and the whole cable decision turns on how many of those four are asked to share a pair of conductors on the way down.

A 20 kW rooftop array in Pakistan needs 6 mm² single-core DC per string, 10 mm² where two strings are combined into one home run, 16 mm² or 25 mm² where all four are combined into a single pair, 10 mm² four-core copper on a 40 A MCB from a three-phase inverter to the AC board, and 10 mm² for bonding the array frames and the inverter body. Those sizes hold for forty panels wired as four series strings of ten, 17.5 A of design current per string, a 400 V three-phase supply, DC routes of 86 m or less per string, and cable clipped direct at 30°C ambient. Change the string layout and the DC answer changes with it; the AC answer does not.

The runs in a 20 kW rooftop array, four strings of ten panels, 400 V three-phase supply. Current capacity per BS 7671, installation reference method C (clipped direct), 30°C ambient; conductor data per IEC 60228. DC rows are the two-conductor values, the three-phase AC row the three-loaded-conductor value. Derate for conduit, bunching and roof heat. Verify sizing with a licensed electrician or your solar installer.
RunCurrentCableCapacityProtection
Each panel string, DC17.5 A design6 mm² single core46 ADC isolator
Two strings combined, DC35 A design6 mm² to a 43 m route, else 10 mm²46 A / 63 ADC isolator, string fuses
All four strings combined, DC70 A design16 mm² to a 56 m route, else 25 mm²85 A / 112 ADC isolator, string fuses
Inverter to AC board, 3-phase 400 V28.9 A/phase10 mm² 4 core57 A40 A MCB
Inverter to AC board, 1-phase 220 V90.9 A35 mm² 2 core138 A125 A
Array frames and inverter earth10 mm²

Working the DC size out, step by step

Two numbers off the back of your own panels drive all of it: the short-circuit current, Isc, and the voltage at maximum power, Vmp. This worked example uses a plate reading Isc 14 A and Vmp 37 V, forty panels in four series strings of ten, and a 30 m route from the roof edge down to the inverter room. Put your own plate figures in the same places.

The millivolt figure already covers the trip out and the trip back, so the 30 m in those sums is the route, measured one way, and the cable you buy is twice it per pair. Forty panels is the count at 500 W each; thirty-four 585 W panels come to roughly the same 20 kW. What moves the cable is the string layout and the plate figures, not the panel count.

How long a run each size covers

Read the left column for a string on its own MPPT input, the middle for the usual two-strings-per-input arrangement, and the right for a single combined home run carrying the whole array.

Longest one-way route at 3% voltage drop on a 370 V string (10 × 37 V), at 17.5 A for one string, 35 A for two combined and 70 A for all four. Buy twice these lengths per pair — the positive and the negative both travel the route. Voltage drop and current capacity per BS 7671, method C, 30°C, PVC, two loaded conductors; conductor data per IEC 60228. Recalculate for your own string current and voltage. Verify with a licensed electrician.
SizeCapacityVoltage dropOne string (17.5 A)Two combined (35 A)All four (70 A)
4 mm²36 A11 mV/A/m57 m28 m, on a 1 A marginnot enough capacity
6 mm²46 A7.3 mV/A/m86 m43 mnot enough capacity
10 mm²63 A4.4 mV/A/m144 m72 mnot enough capacity
16 mm²85 A2.8 mV/A/m226 m113 m56 m
25 mm²112 A1.75 mV/A/m362 m181 m90 m
35 mm²138 A1.25 mV/A/m507 m253 m126 m

Three cells in the right-hand column say "not enough capacity" instead of a distance, and that is the whole argument about 25 mm² on a 20 kW system. Combine all four strings into one pair and heat, not length, settles the size: 70 A needs 16 mm² at minimum, and 25 mm² once that pair runs past 56 m. Split the array across two MPPT inputs instead — which is how most 20 kW inverters are built — and the same roof is wired in 10 mm², for a fraction of the copper. The 4 mm² row carries 35 A by a single amp before any derating at all, which is not a margin; treat that cell as a number, not a recommendation. Full spec and today's rate sit on the 6mm DC solar cable, 10mm DC cable, 16mm DC cable and 25mm DC cable pages.

The AC side, and why three phases make it cheap

A 20 kW inverter in Pakistan is normally a three-phase machine on a 400 V connection. Three phases split the output: 20000 ÷ (1.732 × 400) = 28.9 A per phase, times the 1.25 continuous-duty margin is 36.1 A, so a 40 A MCB. 10 mm² four-core carries 57 A with three conductors loaded, seventeen amps clear of that breaker, and a correction factor of 0.75 for conduit and a hot plant room still leaves 42.8 A — above the breaker. That margin is the reason the AC side of a 20 kW system is less trouble than the AC side of a 10 kW single-phase one.

The single-phase alternative is the row nobody prices before ordering: 20000 ÷ 220 = 90.9 A, which after the same margin is 113.6 A, a 125 A main and 35 mm² cable. Same inverter rating, three sizes of copper apart, decided by one line on the nameplate and by what your connection actually is. Check both before ordering anything on the AC side. Voltage drop on this run is rarely the constraint: 12 m of 10 mm² four-core at 28.9 A drops 4.4 × 28.9 × 12 ÷ 1000 = 1.53 V, well under 1% of 400 V. Breaker margin is. The four cores are three phases and neutral, with the earth as a separate conductor, off the standard cable range. If the system is going on net metering, the run on from that board to the utility meter is sized from your sanctioned load rather than from the inverter — the net metering cable size guide has that table.

A 370 V panel string is live in daylight whether the inverter is switched on or not, and four strings on one roof means four pairs that are all live independently. A DC arc does not self-extinguish the way an AC one does, so never break a DC connection under load — open the isolator first. Size the cable, the DC isolators and the string fusing together as one design, and have a licensed electrician or your solar installer confirm it before anything is energised.

How many metres of cable a 20kW roof takes

Sizes are easy to look up; metres are what the quote is made of. On a 20 kW roof the number that surprises people is the home run: two pairs down the same 30 m route is 120 m of cable before a single panel is connected. Here is the count for one stated layout, to adjust against your own roof.

Cable count for one stated layout: forty panels in four rows of ten, each row wired as one series string, strings paired onto two MPPT inputs at the roof edge and run down 30 m to a three-phase inverter with the AC board beside it. DC rows need twice the route length per pair, because the positive and the negative each make the trip. Figures are the bare doubled route — add about 15% for slack, bends and re-terminations. Measure your own routes before ordering.
RunRouteCable to buySize
String 1 to roof edge, DC8 m16 m (8 red, 8 black)6 mm²
String 2 to roof edge, DC6 m12 m6 mm²
String 3 to roof edge, DC6 m12 m6 mm²
String 4 to roof edge, DC8 m16 m6 mm²
Roof edge to inverter, DC, two pairs30 m120 m10 mm²
Inverter to AC board, 3-phase12 m12 m of 4 core10 mm²
Frames, inverter, earth pit45 m45 m single core10 mm²

Totals for that layout: 56 m of 6 mm² and 120 m of 10 mm² on the DC side, both split evenly red and black, plus 12 m of 10 mm² four-core and 45 m of 10 mm² for the earth — 233 m of cable in all. With 15% for slack, order 32 m of each DC colour in 6 mm² and 69 m of each in 10 mm². One warning before you compare quotes on a job this size: coil lengths in this market are not standard, and price lists routinely print a coil price where a per-metre price belongs. Ask for the metres, ask which unit the number is in, and check both quotes against the same run.

The cable for this system

Single-core solar DC cable in red and black jackets, cut back to show the stranded copper conductor, with a coil of red cable behind
10MM² · 1 CORE · DC SOLAR · 80/0.40 CLASS 5

10mm DC Solar Cable

The paired home runs on a 20 kW roof, and the bulk of its metres. Single-core stranded copper drawn on the Pilone line in Lahore — plain annealed class 5, 80 strands of 0.40 mm, not tinned. A 100 m length holds about 8.89 kg of conductor at 88.9 kg/km, which is the fastest check on whether you were sold full copper: put the coil on a scale.

Factory-direct price
Contact for quote
Message us for today’s rate
WhatsApp for today's rate

Prices track the daily copper rate. Send the metres and your city on WhatsApp for the exact figure.

The strings themselves take 6mm solar cable, a single combined home run takes 16mm DC cable or 25mm DC cable, the AC run takes 10mm four-core off the standard cable range, and the earth takes 10mm earth cable. All DC and solar cable sizes. Installers buying several sizes at once should start at the solar installer supply page.

Current capacities on this page assume the cable is clipped direct in open air at 30°C. A run pulled through conduit, bunched with other circuits, on a roof slab in June carries less than the table says. Have a licensed electrician or your solar installer confirm the size for your layout — or start with the cable size calculator.

Frequently asked

20kW solar system ke liye kitna cable chahiye?
For the layout on this page it comes to 233 m: 56 m of 6 mm² on the strings, 120 m of 10 mm² on the two home runs, 12 m of 10 mm² four-core on the AC side and 45 m for the earth. The 30 m route from roof edge to inverter alone eats 120 m, because two pairs travel it. Measure your routes, double them per pair, add about 15%.
Is 25mm DC cable needed for a 20kW solar system?
Only for one arrangement: all four strings combined into a single pair of conductors, 70 A, on a route past 56 m. Split across two MPPT inputs, which is how most 20 kW inverters are built, the same array runs on 10 mm² and the strings themselves on 6 mm². Count your inputs before buying 25 mm².
What MCB size for a 20kW inverter?
40 A per phase on a 400 V three-phase connection. 20000 ÷ (1.732 × 400) = 28.9 A, times the 1.25 continuous-duty margin is 36.1 A, and the next standard rating up is 40 A on 10 mm² four-core. On single phase the same inverter draws 90.9 A, which is a 125 A main and 35 mm².
How many panels in a 20kW solar system?
Forty at 500 W, thirty-four at 585 W, forty-four at 450 W — all roughly the same 20 kW. The count does not set the cable. What sets it is the Isc and Vmp printed on the panel you actually bought, how many go in one series string, and how many strings share a home run.
Can a 20kW solar system run on a single-phase connection?
Electrically the cable can be built for it: 90.9 A, a 125 A main and 35 mm² two-core. Whether your connection allows a 20 kW inverter on single phase is a question for your distribution company and your installer, not for a cable maker. Check the inverter nameplate and your connection before ordering either way.
What size earth for a 20kW solar array?
10 mm² for bonding the array frames and the inverter body back to the house earth electrode, matching the 10 mm² conductors it runs alongside. The earth core inside the AC cable follows its own phase conductor, so on a 10 mm² four-core run it is 10 mm² too. The solar earthing cable guide has the full table.

Cable for the 20kW array, at the factory rate

We draw the copper in Lahore and sell it at the day's rate — no dealer margin. Send the string layout, the roof-to-inverter route and whether your connection is single or three-phase: Punjab in 1–2 days, rest of Pakistan in 2–4.

WhatsApp for a quote