Prices track the daily copper rate. Coil and bulk pricing on request.
Specifications
Conductor resistance per IEC 60228 class 2. Current rating for reference per BS 7671, installation reference method C (clipped direct), 30°C ambient, PVC insulation. Earth/protective conductor size is normally matched to the line conductor of the circuit it protects (BS 7671 Table 54.7), not chosen from an independent load rating. Verify sizing with a licensed electrician for your installation.
Property
Value
Conductor
Plain annealed copper, class 2 stranded, single core
Nominal area
10 mm²
Strand construction
7 / 1.35 mm
Max conductor resistance at 20°C
1.83 Ω/km
Current rating, reference (2 loaded conductors)
63 A
Voltage rating
450/750 V
Insulation / sheath
PVC, green/yellow, 70°C conductor rating
Conductor copper weight
≈ 88.9 kg/km
Typical use
Grounding and bonding conductor, 5–10 kW solar installations
The current rating above is a reference value for the conductor's size and construction. Earth conductors are sized to match the phase conductor of the circuit they protect, not by independent load current. Have a licensed electrician confirm the correct earth conductor size for your installation — or start with the cable size calculator.
Which circuits 10 mm² earth suits
When the earth conductor is the same metal as the line conductor, BS 7671 Table 54.7 sizes it from the line conductor: up to 16 mm² the earth matches the line; from 16 to 35 mm² it is 16 mm²; above 35 mm² it is half the line size. So 10 mm² earth pairs with a 10 mm² line conductor.
Resistance of 10 mm² earth cable at 20 °C, from 1.83 Ω/km.
Run length
Conductor resistance
10 m
0.018 Ω
25 m
0.046 Ω
50 m
0.092 Ω
These figures feed the earth fault loop check your electrician does: the lower the resistance, the faster a breaker trips on a fault. Every 100 m holds 8.9 kg of copper.
Next size up or down
Earth cable sizes either side of 10 mm², same reference conditions as the specification table.
Reference current rating, 2 loaded conductors, BS 7671 reference method C, 30°C ambient. Same class 2 copper construction in every size.
Frequently asked
What is the price of 10mm earth cable in Pakistan?
The price moves with the daily copper rate, so we quote it the day you order. We sell factory-direct from Lahore, with no dealer margin on top. Message us on WhatsApp for today's price per meter.
What is 10mm earth cable used for?
Grounding and bonding conductor for 5–10 kW solar installations and general earthing circuits. Earth conductor size is normally matched to the line conductor of the circuit it protects, per BS 7671 Table 54.7 — see our solar earthing cable guide, and have a licensed electrician confirm the right size for your installation.
Can I get 10mm earth cable delivered?
Yes. We dispatch from Lahore — courier for single coils, transport for bulk. Punjab arrives in 1–2 days, the rest of Pakistan in 2–4 days. See delivery details.
Send us the length and your city