Skip to content
Factory-direct from Lahore · Nationwide delivery in 2–4 days +92 319 4262451 WhatsApp

Cable current capacity chart for Pakistan — copper and aluminium

BY PILONE CABLES TECHNICAL TEAM

Every size, both metals, with the assumptions printed next to the number.

Copper runs from 19.5 A at 1.5 mm² to 299 A at 120 mm²; aluminium from 48 A at 10 mm² to 230 A at 120 mm². Those are two-loaded-conductor figures, BS 7671 reference method C (clipped direct), 30 °C ambient, PVC insulation. Every chart on this page is a starting point, not a permission: correct it for your ambient temperature and for the circuits bunched beside it before you size the breaker, and the derating tables below give you both factors.

Read the assumptions before you read the amps

An ampacity without a stated installation method is not a number. The same 6 mm² conductor carries a different current clipped to a wall, buried in a conduit, or bunched with five other circuits in a tray, and a chart that does not say which one it means is guessing on your behalf. Every figure here carries the same four assumptions, printed in the caption of each table.

Read across the row, not down the page. A 6 mm² copper cable is rated 46 A with two loaded conductors and 41 A with three, clipped direct at 30 °C ambient under BS 7671 reference method C. That is the tabulated figure. Divide it by the correction factors for your own ambient temperature and for the number of circuits bunched with it, and the derated figure — never the table figure — is what the protective device has to sit under. In a Lahore roof void at 45 °C with two other circuits in the same bunch, that 46 A becomes 46 × 0.79 × 0.70 = 25 A.

The four assumptions behind every current figure on this page. Change any one of them and the number changes. Current capacity per BS 7671 (IEC 60364-5-52); conductor resistance and stranding per IEC 60228.
AssumptionThis chartWhat changes it
Installation methodReference method C — clipped directConduit in a wall is method A or B, with its own lower column
Ambient temperature30 °CRoof voids and surface runs in a Pakistani June sit well past 40 °C
GroupingOne circuit, not bunchedEvery extra loaded circuit in the bunch pulls the factor down
InsulationPVC, 70 °C conductorXLPE runs hotter and rates higher; solar DC cable is typically 90 °C

Where a size is quoted on this site — on a standard cable datasheet, in the cable size calculator, or in a guide — it is read off these same tables, on these same assumptions.

Copper cable current capacity chart

Two loaded conductors is the single-phase case: live and neutral. Three loaded conductors is the three-phase case. The column counts conductors that carry current, not cores in the sheath — a 3 core cable feeding a single-phase load is read off the two-conductor column, because the earth is not loaded.

Copper conductor, PVC insulated. Current capacity and voltage drop per BS 7671 (IEC 60364-5-52), reference method C (clipped direct), 30 °C ambient, 70 °C conductor. Voltage drop is the single-phase, two-loaded-conductor figure in millivolts per amp per metre of run; a three-phase circuit drops less line-to-line, so take that case from the voltage drop calculator. Trade code is the imperial strand code Pakistani shops sell by and does not land exactly on the IEC nominal area. 0.75 and 1 mm² are supplied as class 5 flexible cord (300/500 V); fixed wiring cable at 450/750 V starts at 1.5 mm². Verify sizing with a licensed electrician for your installation.
SizeTrade code2 loaded conductors3 loaded conductorsVoltage drop
0.75 mm²6 A6 A62 mV/A/m
1 mm²10 A10 A44 mV/A/m
1.5 mm²3/.02919.5 A17.5 A29 mV/A/m
2.5 mm²7/.02927 A24 A18 mV/A/m
4 mm²7/.03636 A32 A11 mV/A/m
6 mm²7/.04446 A41 A7.3 mV/A/m
10 mm²7/.05263 A57 A4.4 mV/A/m
16 mm²7/.06485 A76 A2.8 mV/A/m
25 mm²19/.052112 A96 A1.75 mV/A/m
35 mm²138 A119 A1.25 mV/A/m
50 mm²168 A144 A0.93 mV/A/m
70 mm²213 A184 A0.63 mV/A/m
95 mm²258 A223 A0.46 mV/A/m
120 mm²299 A259 A0.36 mV/A/m

The sizes an ordinary Pakistani house lives on are the middle of that ladder: lighting on 1.5 mm², sockets on 2.5 mm², air conditioners on 4 mm², geysers and small motors on 6 mm², the submain from the meter on 10 mm² or 16 mm², and the incoming three-phase main on 25 mm².

Copper conductor data — resistance, stranding, weight

Resistance is the row that settles arguments. It is a measurable property of the conductor, fixed by IEC 60228 for a given size and class, and it is the honest way to check whether a coil is what it was sold as. Class 2 is the stiffer stranded conductor used in standard fixed-wiring cable; class 5 is the fine-strand flexible build.

Maximum conductor resistance at 20 °C per IEC 60228, class 2 (stranded, fixed wiring) and class 5 (flexible). Strand constructions are typical class 2 and class 5 builds. Conductor mass is copper only, computed at 8.89 kg/km per mm² — it excludes insulation, sheath and any filler, so a weighed coil will read higher. 0.75 and 1 mm² are made as flexible cord and carry no class 2 build.
SizeClass 2 strandsClass 2 resistanceClass 5 strandsClass 5 resistanceCopper mass
0.75 mm²24/0.2026.0 Ω/km6.7 kg/km
1 mm²32/0.2019.5 Ω/km8.9 kg/km
1.5 mm²7/0.5312.1 Ω/km30/0.2513.3 Ω/km13.3 kg/km
2.5 mm²7/0.677.41 Ω/km50/0.257.98 Ω/km22.2 kg/km
4 mm²7/0.854.61 Ω/km56/0.304.95 Ω/km35.6 kg/km
6 mm²7/1.043.08 Ω/km84/0.303.30 Ω/km53.3 kg/km
10 mm²7/1.351.83 Ω/km80/0.401.91 Ω/km88.9 kg/km
16 mm²7/1.701.15 Ω/km126/0.401.21 Ω/km142.2 kg/km
25 mm²7/2.140.727 Ω/km196/0.400.78 Ω/km222.3 kg/km
35 mm²19/1.530.524 Ω/km276/0.400.554 Ω/km311.2 kg/km
50 mm²19/1.780.387 Ω/km396/0.400.386 Ω/km444.5 kg/km
70 mm²19/2.140.268 Ω/km360/0.500.272 Ω/km622.3 kg/km
95 mm²37/1.780.193 Ω/km475/0.500.206 Ω/km844.6 kg/km
120 mm²37/2.030.153 Ω/km608/0.500.161 Ω/km1066.8 kg/km

The mass column is a buyer's tool, not a spec-sheet ornament. Copper in a coil = size × number of cores × 8.89 kg/km × length. A 90 m coil of 25 mm² 4 core holds 25 × 4 × 8.89 = 889 kg/km, which is 889 × 0.090 = 80 kg of copper before any insulation or sheath. Weigh your own coil, subtract nothing, and you have a floor to compare against. It is a method, not an accusation — coil lengths and sheath weights differ honestly between makers, so ask for the coil length with the rate.

Aluminium cable current capacity chart

Aluminium is the metal for service drops, long feeders and anything above roughly 25 mm² where the copper price stops making sense. In the market it is often sold as "silver cable", which is a trade nickname for the metal's colour, not a different material. It starts at 10 mm² because below that the terminals and the mechanical handling stop being worth it.

Aluminium conductor, PVC insulated. Current capacity per BS 7671 (IEC 60364-5-52), reference method C (clipped direct), 30 °C ambient, 70 °C conductor. Resistance per IEC 60228 class 2 at 20 °C. Conductor mass computed at 2.70 kg/km per mm², aluminium only. The copper comparison column is the copper size from the chart above whose two-conductor rating is closest, with its own figure in brackets — read the direction, some are above and some below. Copper's steps widen at the top of the ladder, so one copper size can be the closest match for two aluminium sizes. Verify sizing with a licensed electrician for your installation.
Size2 loaded conductors3 loaded conductorsClass 2 resistanceAluminium massClosest copper by amps
10 mm²48 A43 A3.08 Ω/km27.0 kg/km6 mm² (46 A)
16 mm²66 A59 A1.91 Ω/km43.2 kg/km10 mm² (63 A)
25 mm²87 A76 A1.20 Ω/km67.5 kg/km16 mm² (85 A)
35 mm²107 A94 A0.868 Ω/km94.5 kg/km25 mm² (112 A)
50 mm²130 A113 A0.641 Ω/km135.0 kg/km35 mm² (138 A)
70 mm²165 A144 A0.443 Ω/km189.0 kg/km50 mm² (168 A)
95 mm²199 A175 A0.320 Ω/km256.5 kg/km70 mm² (213 A)
120 mm²230 A202 A0.253 Ω/km324.0 kg/km70 mm² (213 A)

Two ratios fall straight out of the two charts and they are worth committing to memory. Aluminium carries about 77% of copper's current at the same nominal size — 48 against 63 at 10 mm², 87 against 112 at 25 mm², 230 against 299 at 120 mm². In practice that is one standard size step, so the same load that takes 25 mm² copper takes 35 mm² aluminium. And aluminium conductor weighs about 30% of copper at the same size — 67.5 against 222.3 kg/km at 25 mm² — which is the whole commercial reason it exists. The trade-off between the two metals, terminal by terminal, is set out in the copper versus aluminium guide; the sizes we draw are on the aluminium cable pages.

Derating: what the chart figure becomes on a real job

This is the step most Pakistani sizing charts skip, and it is the step that decides whether the cable or the breaker fails first. Two of the three corrections are numbers you multiply. The third is not a number at all.

Ambient temperature — the factor Ca

The 30 °C baseline is a European default. A cable clipped along a roof void, run across a flat roof, or chased into a west-facing wall in Lahore or Multan in June is not at 30 °C. BS 7671 Table 4B1 gives the correction for 70 °C thermoplastic cable, and at 45 °C it is 0.79 — a 21% cut, not the 15% that circulates on Pakistani wiring blogs.

Ambient correction factor Ca for 70 °C thermoplastic (PVC) cable, BS 7671 Table 4B1, applied to the method C figures above. The three worked columns are examples only — the factor applies to every row of the chart. For 35 °C and other intermediate ambients, read Table 4B1 directly for your own conditions.
AmbientFactor Ca4 mm² (36 A)10 mm² (63 A)25 mm² (112 A)
30 °C1.0036.0 A63.0 A112.0 A
40 °C0.8731.3 A54.8 A97.4 A
45 °C0.7928.4 A49.8 A88.5 A
50 °C0.7125.6 A44.7 A79.5 A

Grouping and bundling — the factor Cg

Cables bunched together heat each other. The correction depends on how many loaded circuits are in the bunch, and a flat "20% for bundling" is only right when there are exactly two. Six circuits in one conduit takes the figure down by 43%.

Grouping correction factor Cg for circuits bunched and enclosed in one layer, BS 7671 Table 4C1. Count loaded circuits in the bunch, not conductors. Worked column is 10 mm² copper, two loaded conductors, 63 A tabulated. Combine with Ca by multiplying both factors. Verify sizing with a licensed electrician for your installation.
Circuits in the bunchFactor Cg10 mm² (63 A) becomes
11.0063.0 A
20.8050.4 A
30.7044.1 A
40.6541.0 A
50.6037.8 A
60.5735.9 A

Conduit — a different column, not a multiplier

Conduit is where most charts go wrong. Putting a cable in a conduit does not apply a percentage to the method C figure — it moves the cable to a different reference method with its own tabulated values. Method C, clipped direct, is the most generous of the common methods, so every figure on this page is an upper bound for a conduit run. Do not invent a multiplier for it. Take the method A or method B column from BS 7671 for the cable you are actually installing, or size the conduit run in the cable size calculator, which asks for the method.

Buried cable is a fourth case again, with soil thermal resistivity and burial depth of its own; the practical points for a buried run are in the underground cable guide.

Current capacity depends on how the cable is installed. These are first-pass planning factors from published tables, not a substitute for the design. Read the correction factors for your own installation method and ambient out of BS 7671, and have a licensed electrician confirm the size against your load, your run length and your protective device before anything is buried in a wall.

How to use the chart in six steps

1. Get the design current

Watts ÷ volts for a single-phase load at 230 V. For a motor or an appliance, take the full-load current from the rating plate instead — the plate beats every chart. Call it Ib.

2. Pick the column

Single-phase circuit, two loaded conductors. Three-phase circuit, three loaded conductors. The earth core never counts, whatever the cable is called.

3. Find your correction factors

Ca from the ambient table, Cg from the grouping table. If the run is in conduit, change to the method A or B column instead of correcting the method C figure.

4. Divide, then look up

Required tabulated capacity = Ib ÷ (Ca × Cg). Read down the chart column and take the first size whose figure meets or beats it. Dividing up front beats derating each candidate.

5. Check the voltage drop

Volts lost = mV/A/m × Ib × one-way run ÷ 1000. Hold the whole installation inside 2.5% of 230 V, which is 5.75 V, and give a final circuit part of that budget.

6. Fit the breaker between them

The protective device rating sits above Ib and below the cable's derated capacity. If nothing fits between the two, the cable is too small — go up a size, not up a breaker.

Worked example: a 55 A house submain in a 45 °C roof void

A single-phase submain from the meter to the distribution board. Design current 55 A. The route is 22 m through a roof void that reaches 45 °C in June, and the cable is bunched with two other loaded circuits along the way — three circuits in the bunch.

Step 1. Ca at 45 °C is 0.79. Cg for three circuits is 0.70. Multiplied: 0.79 × 0.70 = 0.553.

Step 2. Required tabulated capacity = 55 ÷ 0.553 = 99.5 A. That is the number to look up, not 55 A.

Step 3. Read down the two-loaded-conductor column. 10 mm² is 63 A — short. 16 mm² is 85 A — still short. 25 mm² is 112 A and clears it. Checked the other way round: 112 × 0.79 × 0.70 = 61.9 A, comfortably over the 55 A load.

Step 4. Voltage drop on 25 mm² is 1.75 mV/A/m: 1.75 × 55 × 22 ÷ 1000 = 2.12 V, which is 0.92% of 230 V. Inside the budget with room to spare, so heat decided this size, not length.

Read the same job off the raw chart with no correction and you land on 10 mm², because 63 A looks like it covers 55 A. That is a two-size error, and it is the error that makes a submain warm to the touch in June. Check your own numbers in the cable size calculator and the voltage drop calculator.

Worked example: a 95 A three-phase feeder, copper against aluminium

A 400 V three-phase workshop feeder, design current 95 A, 4 core cable clipped direct in a ventilated riser at 40 °C, running on its own. Ca is 0.87, Cg is 1.00, so the required tabulated capacity is 95 ÷ 0.87 = 109.2 A.

Read the three-loaded-conductor column, because all three lines are loaded. In copper, 25 mm² is 96 A — short of 109.2. 35 mm² is 119 A and takes it. In aluminium, 35 mm² is 94 A — short. 50 mm² is 113 A and takes it. One size step between the metals, exactly as the 77% ratio predicts.

Weigh the two: 35 mm² copper carries 311.2 kg of conductor per kilometre, 50 mm² aluminium carries 135.0 kg — 43% of the mass for the same duty. That is the trade the aluminium buyer is making, before terminals, lugs and the extra diameter are counted. Three-phase sizing end to end, including the neutral and the earth, is worked through on the 3 phase cable size page; the single-phase equivalent is on single phase cable size.

Trade codes: what 7/.029 and 7/.064 are in mm²

Ask for a size in mm² in a Pakistani shop and you get quoted a strand code. Seven strands of 0.036 inch is 7/.036. The codes are imperial, so the area they compute to does not land on the IEC nominal size the cable is sold as — one wire, two names, and the gap between them is where most of the confusion in this market lives. The arithmetic is simple enough to check: strand diameter in inches × 25.4 gives millimetres, area per strand is π/4 × d², multiplied by the strand count.

Trade code to metric area. Computed area is π/4 × d² × strand count, with d converted from inches at 25.4 mm per inch. "Sold as" is the IEC 60228 nominal size the market prices it at, including at Pilone — we label by the same convention and publish both figures. Current capacity is read against the nominal size, two loaded conductors, BS 7671 reference method C, 30 °C, copper, PVC.
Trade codeStrand diameterComputed areaSold asCurrent capacity
3/.0290.737 mm1.28 mm²1.5 mm²19.5 A
7/.0290.737 mm2.98 mm²2.5 mm²27 A
7/.0360.914 mm4.60 mm²4 mm²36 A
7/.0441.118 mm6.87 mm²6 mm²46 A
7/.0521.321 mm9.59 mm²10 mm²63 A
7/.0641.626 mm14.53 mm²16 mm²85 A
19/.0521.321 mm26.03 mm²25 mm²112 A

The codes have their own pages here: 3/.029, 7/.029, 7/.036, 7/.044, and in aluminium 7/.052 at 10 mm² and 7/.064 at 16 mm². One warning worth repeating: 25 mm² and 2.5 mm² are not the same cable. 25 mm² carries 112 A, 2.5 mm² carries 27 A, and a written order that drops the decimal point is a safety problem, not a typing one.

Frequently asked

How many amps can a 6mm cable carry?
46 A with two loaded conductors and 41 A with three, clipped direct at 30 °C ambient under BS 7671 reference method C. Those are the table figures. In conduit, bunched with other circuits, or in a 45 °C roof void the working figure is lower: at 45 °C with three circuits in the bunch the same cable comes down to 46 × 0.79 × 0.70 = 25 A.
25mm cable kitne ampere carry karta hai?
25 mm² copper 112 ampere carry karta hai jab do conductor loaded hon, aur 96 ampere jab teen loaded hon — clipped direct, 30 °C ambient, BS 7671 method C. Yeh table ka figure hai. Garmi mein aur doosre circuits ke saath bandha ho to figure kam ho jata hai: 45 °C par 112 × 0.79 = 88 ampere reh jata hai.
Is a 32 A breaker safe on 2.5 mm cable?
No. 2.5 mm² copper is 27 A with two loaded conductors and 24 A with three, clipped direct at 30 °C — both below 32 A before any correction is applied at all. The protective device has to sit below the cable's derated capacity, not above it. 2.5 mm² belongs on a 16 A or 20 A device, and 20 A only where the run is cool, clipped and not bunched.
How much do I derate a cable for 45 degrees in a Pakistani summer?
BS 7671 Table 4B1 gives 0.79 for 70 °C thermoplastic cable at 45 °C ambient — a 21% cut, not the 15% that gets quoted around. At 40 °C it is 0.87 and at 50 °C it is 0.71. Multiply the table amps by the factor, or divide your design current by it to get the capacity you need to look up.
How many amps does 10mm aluminium cable carry?
48 A with two loaded conductors and 43 A with three, on the same method C, 30 °C basis. That is about 76% of what 10 mm² copper carries. Aluminium runs near 77% of copper's amps at every size on this chart, so the same load usually needs one standard size larger in aluminium.
Does cable in conduit carry fewer amps than clipped cable?
Yes, and it is not a percentage — it is a different column. The figures on this page are reference method C, clipped direct, the most generous of the common methods. A cable in conduit in a wall is method A or method B and has its own lower tabulated value in BS 7671. Do not apply a rule-of-thumb multiplier to a method C figure; read the right column.
7/.029 kitne ampere ka hai?
7 strands of 0.029 inch computes to 2.98 mm², and the trade sells it as 2.5 mm². Read it against the 2.5 mm² row: 27 A with two loaded conductors, 24 A with three, method C at 30 °C. Ask for the code and the mm² together — the code is imperial and does not land exactly on the IEC nominal size.
Do I use the 2 core or 3 core column for a 3 core cable on a single-phase circuit?
The two-conductor column. It counts loaded conductors, not cores in the sheath. On a single-phase circuit only live and neutral carry current, so a 3 core cable feeding a single-phase load is read off the two-loaded-conductor column. The three-conductor column is for a three-phase circuit, where all three lines are loaded.

Got the size — now get the rate

We draw the copper and aluminium in Lahore and sell it at the day's rate, with no dealer margin in between. Send the size, the core count, the total metres and your city: Punjab in 1–2 days, rest of Pakistan in 2–4.

WhatsApp for today's rate