Single core stranded copper building wire, PVC insulated, coiled
PILONE · 3/.029 · 1 CORE · 450/750 V · CU

3/.029 Copper Cable (3/29 Wire)

4.8/5 · 127 buyer ratings

PILONE CABLES TECHNICAL TEAM

Single core stranded copper building wire, code 3/.029 — three strands of 0.029 inch wire, which computes to 1.28 mm². The trade sells that build as 1.5 mm², but 1.28 mm² is less copper than a 1.5 mm² conductor, so the 1.5 mm² reference figures cannot simply be assumed for it. Confirm the declared nominal size and maximum conductor resistance on the quotation. PVC insulated, 450/750 V. This is the lighting-circuit wire that gets pulled through conduit on a house job. Drawn on the Pilone line in Lahore.

Factory-direct price
Contact for quote
In stock
Message us for today’s rate
WhatsApp for today's rate

Prices track the daily copper rate. Bulk and coil pricing on request.

Check the coil before you pay for it

Every coil leaves our factory with a QR code printed on the packaging. Scan it and the factory record for that batch opens: brand, cable size, batch number, year of manufacture and conductor. Compare the batch number on screen with the one printed on your coil — if the two do not match, it did not come from us.

Specifications

3/.029 is an inch strand code (3 strands × 0.029 in), not an IEC 60228 size. Values marked “calculated” are arithmetic from the strand diameter, not test results. Confirm the declared nominal size and maximum resistance with the quotation, and have a licensed electrician size the circuit.
PropertyValue
ConductorPlain annealed copper, stranded (3/.029 in)
Calculated area1.28 mm² (3 × 0.426 mm²)
Trade nameSold as 1.5 mm²
Calculated resistance at 20°C≈ 13.5 Ω/km (plain copper, 1.28 mm²; the IEC 60228 limit for 1.5 mm² class 2 is 12.1 Ω/km)
Current capacityNot tabulated for this construction; size the circuit on the declared nominal size once its resistance is confirmed
Voltage drop (calculated)≈ 32 mV/A/m single-phase at 70°C (1.5 mm² table value: 29)
Voltage rating450/750 V
InsulationPVC, 70°C conductor rating
Standards referred toIEC 60228 resistance limits, for comparison only; no compliance with a standard is claimed on this page

Where this cable belongs

Lighting circuits

Board to ceiling rose to switch, looped in conduit. The size almost every lighting circuit in a Pakistani house is wired in.

Switch drops and fan points

Two-way switching, fan regulators and light points, where the load is a few amps and the run is short.

Conduit pulls on new builds

Bought by the coil during first fix. Three strands pull round a conduit bend more easily than a solid conductor of the same size.

The buyer here is a house wireman at first fix, ordering coils by the colour for a 5 or 10 marla build. 3/.029 is the lighting size and it should stay on lighting: socket circuits normally step up to the next code, 7/.029, which the trade sells as 2.5 mm² — see 7/.029 copper cable. For an AC point, a geyser or a stove the jump is bigger again, to 4mm (7/.036) single core copper cable. The honesty on the code cuts both ways: 3/.029 computes to 1.28 mm² and is sold as 1.5 mm², and Pilone labels by the same market convention every other maker uses, which is why both numbers are printed here. If you want a true metric 1.5 mm² conductor, ask for it by the mm² name — 1.5mm single core solid cable.

Worked example — a 5 A lighting circuit 30 m from the board.

Voltage drop is current × length × mV/A/m, divided by 1000. Using about 32 mV/A/m, worked from the calculated 1.28 mm² at a 70°C conductor temperature: 5 × 30 × 32 ÷ 1000 = 4.8 V, which is 2.2% of 220 V — inside the 3% (6.6 V) that BS 7671 Appendix 4 gives for lighting circuits fed from the public supply. At 10 A the same 6.6 V is spent at 6.6 ÷ (10 × 32 ÷ 1000) ≈ 20 m. That is short, and it is the reason long runs on a big plot move up a size even when the load has not changed — check yours with the voltage drop calculator.

Current capacity depends on how the cable is installed. Derate for conduit, grouping, and high ambient temperature. Have a licensed electrician confirm the size for your circuit — or start with the cable size calculator.

What buyers say

5/5

“Excellent quality copper cables. Fast delivery across Pakistan. Highly recommended for electrical projects.”

AHMAD HASSAN

5/5

“Best cable manufacturer in Lahore. 99.9% pure copper as promised. Very satisfied with the product quality.”

MUHAMMAD ALI

5/5

“Good quality cables at competitive prices. Delivery was quick to Karachi. Will order again.”

IMRAN KHAN

Frequently asked

What is the price of 3/.029 copper cable in Pakistan?
The price changes with the daily copper rate. We sell factory-direct from Lahore, below dealer rates. Message us on WhatsApp for today's price per meter.
What is 3/.029 copper cable used for?
A single core stranded building wire for lighting circuits: conduit and trunking runs, lighting circuit looping, and switch drops and fan points. It is sold as 1.5 mm², but its calculated area is 1.28 mm², so confirm the declared nominal size and resistance before relying on 1.5 mm² ratings.
Should I use solid single core cable instead?
Both are used for fixed house wiring. Stranded wire like this one bends more easily through conduit bends; solid single core wire is stiffer but slightly cheaper. Either is normal for lighting and socket circuits at this size. See 1.5mm single core solid cable.
What is 3/.029 in mm?
3/.029 means three strands of 0.029 inch wire. One strand is 0.029 × 25.4 = 0.737 mm across, so its area is 0.7854 × 0.737² = 0.426 mm², and three of them come to 1.28 mm². The trade sells that build as 1.5 mm². The imperial codes do not land exactly on the metric names — some sit above, some below — so both numbers are published here.
How many amps does 3/.029 copper wire carry?
No current rating is tabulated for the 3/.029 construction. The 19.5 A often quoted is the BS 7671 method C figure for a 1.5 mm² conductor, and a conductor built exactly to 3 × 0.029 in has about 1.28 mm² of copper, which is less. Keep it on lighting circuits, confirm the declared nominal size and maximum resistance on the quotation, and have an electrician size the circuit, allowing for conduit, grouping and heat.