Earth Cable

Earth cable connects an electrical system to the ground. When a fault sends current where it should not go, the earth cable carries it safely into the earth and lets the breaker trip.

Drawn on the Pilone line in Lahore, 6 to 35 mm². Every house, solar system, and industrial panel needs correct earthing.

Pick a size

Each size has its own page with the specification and the current factory rate.

How to size an earth cable

A common rule: the earth conductor should match the phase conductor up to 16 mm². Above that, it can be smaller — a 16 mm² earth is typically enough for a 25 or 35 mm² phase conductor. For solar systems, see the solar earthing guide.

This is a simplified rule of thumb. The correct earth size depends on the fault current and disconnection time for your installation. Always have a licensed electrician verify the earthing design.

The sizes side by side

Conductor resistance and strand construction per IEC 60228 class 2. Current rating is the conductor's general BS 7671 reference method C rating, 30°C ambient, PVC insulation — shown for reference; as a protective earth conductor it is not intended to carry continuous load. Verify the earthing design with a licensed electrician.
Size (mm²) Strands R at 20°C (Ω/km) Typical use
67/1.043.08Earths phase conductors up to 6 mm²
107/1.351.83Earths phase conductors up to 10 mm²
167/1.701.15Earths phase conductors up to 16 mm²
257/2.140.727Full-size earth for larger sub-mains
3519/1.530.524Main incomer and heavy sub-main earthing

Get today's rate on any earth cable size

Cable prices track the daily copper rate, so we quote the factory price on the day. Send the size, length, and your city.