Skip to content
Factory-direct from Lahore · Nationwide delivery in 2–4 days +92 319 4262451 WhatsApp

Cable overheating: find the cause, then fix the size

PILONE CABLES TECHNICAL TEAM

A wire gets hot for one of two reasons: it is carrying more current than its size allows, or a joint in it has gone high-resistance.

The first is fixed by a larger conductor or a smaller load; the second by remaking one connection, and a new coil will not help it. Tell them apart by touching the run a metre away from the fitting — warm along the whole length means the size, cold there and hot only at the fitting means the joint. PVC cable is built around a 70 °C conductor, and nobody can read that temperature through the sheath by hand, so discoloured insulation, a smell of hot plastic, or a cable you cannot hold means switch the circuit off at the board now.

Which of these is your cable?

A copper PVC cable overheats when the current in it exceeds what its conductor area can shed as heat, or when a terminal develops enough resistance to burn power at that one point. On BS 7671 reference method C — clipped direct, 30 °C ambient — 1.5 mm² carries 19.5 A, 2.5 mm² carries 27 A and 4 mm² carries 36 A with two loaded conductors; pulled through conduit, bundled with other circuits, or sitting in a Lahore roof space in June, every one of those figures comes down. A cable running hot at a current below its tabulated rating is almost always a connection fault, not a conductor fault.

Symptom to cause. Every check here is done with the circuit isolated at the board, by a licensed electrician — this is what to look for, not permission to work live. Capacity figures per BS 7671 (IEC 60364-5-52), reference method C, 30 °C, copper, PVC; conductor data per IEC 60228.
What you seeMost likely causeWhat to checkWhat fixes it
Whole run warm along its length under normal loadCurrent above the cable's derated capacityTotal the appliances on the circuit; read the MCB ratingA larger conductor, or take load off the circuit
Only the socket, switch or joint is hot; cable cold a metre awayHigh-resistance connectionScrew tightness, discoloured brass, strands left outside the clampRemake the termination; replace the accessory if the metal is burnt
Insulation discoloured, tacky, or smelling of hot plasticThe cable has run above its temperature rating for a long timeThe whole length, for more discoloured stretchesReplace the run — cooked PVC does not recover
MCB trips after several minutes under loadOverload: real current above the breaker ratingWhat was added to that circuit since it last heldSplit the load onto a second circuit, or step up cable and breaker together
Wire burned but the MCB never trippedCurrent above the cable's capacity, below the breaker'sBreaker rating against the cable's derated capacityCorrect the pair — the MCB never above what the cable can carry
Aluminium replaced copper at the same sizeAluminium carries less at equal sectionThe size stamped on the new cable against the oldStep up the size; check the terminations as well
Hot only when the UPS or generator is feeding the houseOne changeover output carrying what the grid split across several waysWhich circuits sit behind the changeover, and the totalSize the backup feed to the whole backup load

How hot is too hot for a PVC cable?

The number that exists is the conductor rating: 70 °C for ordinary PVC building and power cable, and typically 90 °C for the XLPE and XLPO insulation used on solar DC cable. That is the temperature the copper inside is allowed to reach, not the temperature of the sheath you can touch. How much cooler the sheath runs depends on the insulation thickness, whether the cable is in conduit, and the air around it — so a hand on the outside does not measure it, and we will not tell anyone their cable is safe by feel.

What that leaves is a practical rule. A cable at its full rated current is warm by design, and warm on its own is not a fault. Four things are: heat you cannot keep your hand on, the smell of hot plastic, insulation that has gone brown or soft or tacky, and heat somewhere that was cool last year. Any of those, switch the circuit off and get it looked at before it is used again.

Wire kitna garam ho to normal hai? Thora garam hona normal hai. Boo aaye, rang badle, ya haath na tik sake — to circuit turant band karein aur licensed electrician ko dikhaein.

3/29, 7/29, 7/36 — what each one actually carries

Half of the trouble here is that the shop and the standard speak different languages. You ask for a size in mm² and you are quoted a strand code — seven strands of 0.029 inch is 7/.029 — and the imperial codes do not land exactly on the metric nominal sizes. Charts circulating in Pakistan quote current ratings for these codes with no installation method behind them, usually higher than any standard supports. These are the BS 7671 figures with the method stated, so you can check them against any other chart you are shown.

Trade strand code to nominal size and current capacity. Actual area = strands × π/4 × strand diameter²; the metric column is the size the code is sold as, not an exact equivalent. Capacity read against the nominal size per BS 7671 (IEC 60364-5-52), reference method C (clipped direct), 30 °C ambient, copper, PVC. Derate for conduit, bundling and higher ambient. Verify sizing with a licensed electrician for your installation.
Trade codeActual areaSold as2 loaded cores3 loaded cores
3/.0291.29 mm²1.5 mm²19.5 A17.5 A
7/.0293.0 mm²2.5–3 mm²27 A24 A
7/.0364.6 mm²4 mm²36 A32 A
7/.0446.9 mm²6–7 mm²46 A41 A
7/.0529.6 mm²10 mm²63 A57 A
7/.06414.5 mm²16 mm²85 A76 A

Read the two-core column for an ordinary single-phase circuit, where live and neutral are the only loaded conductors, and the three-core column for a three-phase run. Both are before derating. Which size to buy for a given appliance is a different question from why the existing one is hot — the AC circuit is worked through on cable for a 1.5 ton AC, and the cable size calculator sizes any load and run.

The breaker is not protecting the cable

Take a pairing that turns up constantly: a 32 A MCB on 2.5 mm². The cable carries 27 A clipped direct at 30 °C. Pull 30 A through it and the cable is 3 A over its rating and heating, while the breaker sees 30 A on a 32 A device and holds all evening. Put the same cable in conduit alongside two other loaded circuits in a hot roof space and the 27 A comes down further, so the gap widens — and nothing in the panel knows.

The rule is one line: the MCB rating must never exceed the cable's capacity after derating. Before derating that gives 16 A on 1.5 mm², 25 A on 2.5 mm², 32 A on 4 mm², 40 A on 6 mm² and 63 A on 10 mm², and a step lower again where the run is buried, bundled or hot. So no, a bigger MCB is not the fix for repeated tripping. A breaker that trips under load is reporting the load; a larger one deletes the report and leaves the load exactly where it was. Where the cable is genuinely undersized, the choice between rewiring and shrinking the circuit is set out on wire size too small.

Aluminium at the same number is not the same cable

25 mm² aluminium carries 87 A with two loaded conductors on method C. 25 mm² copper carries 112 A on the same basis. Same number on the drum, 25 A less capacity — 25 ÷ 112 = 22% down. Swap one for the other size for size on a feeder that was already near its limit and the new cable runs hot at a load the old one carried without complaint. Aluminium earns its place on service drops and long feeders, and we draw it from 10 to 120 mm²; it just has to be sized as aluminium, not as the copper it replaced. The ratio at every size is on copper vs aluminium cable.

Aluminium also behaves differently at a screw terminal. It creeps under clamping pressure and moves more with heat than copper does, so a joint that was tight on installation day can loosen over years of warming and cooling — and a loose joint is a heater. This is why an aluminium run is more likely to give you a hot termination than a hot cable, and why those terminations want the right connector and a re-check rather than being made once and forgotten.

A short circuit is a different failure

A short circuit is a direct low-resistance path between live and neutral, or live and earth. The current jumps far above anything the cable is rated for and the MCB's magnetic element clears it in milliseconds. That is not what is happening to a cable that gets slowly hot. Overheating is the failure the breaker does not see: a current the breaker is content with, and the cable is not.

The timing separates them. A trip the instant you switch something on is a short or a motor inrush. A trip after minutes under load is an overload. Keeping shorts out of an installation is a different job with different answers — mechanical protection, sound terminations, an RCD — and it is set out on how to prevent a short circuit.

Is the coil really the size written on it?

Under-section coils and copper-clad aluminium are a real cause of hot cable here, and they are invisible once the wire is in the wall. The check that costs nothing is weight. Copper conductor weighs 8.89 kg per km for every mm² of section, so a 90 m coil of 2.5 mm² single core holds 22.2 × 0.09 = 2.00 kg of conductor copper. A coil actually drawn to the full 7/.029 section — 3.0 mm² — holds 3.0 × 8.89 × 0.09 = 2.40 kg.

Conductor copper only, in a 90 m coil of single-core wire. Excludes insulation, sheath and drum, so any real coil weighs more than the figure shown — what the check catches is a coil lighter than the bare conductor should be. Weight = nominal area × 8.89 kg/km per mm²; sizes per IEC 60228. A sanity check, not a laboratory result.
Sold asTrade codeConductor copperPer 90 m coil
1.5 mm²3/.02913.3 kg/km1.20 kg
2.5 mm²7/.02922.2 kg/km2.00 kg
4 mm²7/.03635.6 kg/km3.20 kg
6 mm²7/.04453.3 kg/km4.80 kg
10 mm²7/.05288.9 kg/km8.00 kg

Do not reach for a magnet. Copper-clad aluminium has an aluminium core and aluminium is not magnetic either, so the magnet test that circulates online cannot tell the two apart. What does tell them apart is stripping 30 mm and looking at a cut strand end — CCA shows a pale core inside a copper skin — and weight, which no coating can fake. Where the section itself is in doubt, we will check conductor size and resistance on a sample; that is a supplier's verification, not a certified independent test report, and we say so on that page. Our own position on the metal is on 100% copper wire.

Hot only on the UPS or the generator

This one catches people out because the same house on the same appliances behaves differently on backup. Two things change. The changeover output is a single cable carrying every circuit that was backed up, where the grid fed those circuits through separate ways in the board — so the current through that one run is the sum, not the largest. And loads that hold their power output — an inverter AC, a switch-mode charger, a motor driving a fixed load — draw more current as the voltage sags on a tired battery bank, so the amps rise exactly when the supply weakens.

Add a generator or inverter parked in a hot store or on a roof, and the ambient is above the 30 °C the tables assume, which lowers the capacity again. The arithmetic for sizing that feed is on load shedding backup wiring.

What actually fixes it

1. Switch off, then look

Isolate the circuit at the board before anything else. A cable that is discoloured or smells has already lost insulation life and is not going back into service as it is.

2. Separate the joint from the conductor

Heat that stops within a metre of a fitting is a termination fault. Heat spread along the whole run is a sizing fault. The two have different repairs and only one of them needs new cable.

3. Size the run again from the real numbers

Current from the appliance rating plates, length measured along the route the cable takes, and the installation method it will sit in. Then check the length as well as the load — on long runs voltage drop sets the size before heat does.

4. Buy the size the arithmetic gives

Not the size that was there, and not the size the last shop had in stock. Where the answer comes out at 4 mm² on a socket or AC circuit, that is 4mm 3 core standard cable with the earth at full size.

A hot cable, socket, or breaker is a safety matter. Switch the circuit off and have a licensed electrician inspect the wiring, the connections and the cable size before it is used again — this page is not a substitute for that inspection, and we do not inspect or diagnose installations remotely. Current capacities here assume reference method C at 30 °C; derate for conduit, bundling and higher ambient, and take the correction factors for your own installation from BS 7671.

The cable for the replacement run

Standard cable cut back to show three insulated stranded copper conductors inside a black PVC sheath
4MM² · 3 CORE · 450/750 V · CU CLASS 2

4mm 3 Core Standard Cable

The usual answer where a 2.5 mm² circuit has outgrown itself. Class 2 stranded copper, 7/0.85, PVC insulated and sheathed to 450/750 V, rated 36 A clipped direct at 30 °C with two loaded conductors, drawn on the Pilone line in Lahore.

Factory-direct price
Contact for quote
Message us for today’s rate
Send the load and the run length

Cable is priced off the day's copper rate, so we quote per metre and per coil on WhatsApp rather than publish a figure that goes stale. Send the size, the metres and your city.

Other sizes in the same family: 6mm 3 core cable where the load has grown past 32 A, 10mm 2 core cable for a submain from the meter, and 4mm 3 core flexible cable where the tail has to bend.

Frequently asked

Wire kitna garam ho to normal hai?
Thora garam hona normal hai — cable apni poori rated current par garam hota hi hai. PVC cable 70 °C conductor ke hisab se bana hai, magar woh temperature insulation ke andar hai, aur sheath ke bahar haath laga kar aap usay naap nahi sakte. Jo normal nahi hai: itna garam ke haath na tik sake, garam plastic ki boo, insulation ka rang badalna ya naram ho jana. Aisi soorat mein circuit board se band karein.
Why is my electrical wire getting hot when the AC runs?
Either the circuit is carrying more current than the cable's derated capacity, or the connection at the point has gone high-resistance. Feel the run a metre away from the socket or isolator. Cold there and hot only at the fitting means the joint. Warm along the whole length means the size. A 1.5 ton unit on 2.5 mm² buried in conduit is the common version of the second case.
7/29 pe kitna load chal sakta hai?
7/.029 computes to about 3.0 mm² and is sold as 2.5 mm². Read against the 2.5 mm² row it carries 27 A with two loaded conductors and 24 A with three, clipped direct at 30 °C in PVC. In conduit, bundled with other circuits, or in summer heat it carries less. Treat it as a 20 A breaker's cable, not a 32 A one.
My breaker trips again and again — is it the breaker or the wire?
Time it. A trip within a second of switching something on is a short circuit or a motor inrush against too sharp a breaker curve. A trip after several minutes under load is an overload: the real current is above the breaker rating, and the cable is being asked for the same current. A breaker that starts tripping at a load it used to hold is usually reporting new load.
Can I just fit a bigger MCB to stop the tripping?
No. The breaker protects the cable, so its rating must sit under the cable's capacity after derating — 16 A on 1.5 mm², 25 A on 2.5 mm², 32 A on 4 mm², 40 A on 6 mm². Fit a 32 A device on 2.5 mm² and the cable reaches its 27 A limit while the breaker is still content. The trip is the report; a bigger breaker deletes the report and leaves the load.
Why did the wire burn but the breaker never tripped?
Because the current never reached the breaker's threshold. A 32 A MCB holds happily at 30 A while 2.5 mm², rated 27 A and less in conduit, cooks. A loose terminal does the same at normal current: suppose one screw develops 0.1 Ω, then at 20 A it burns 20 × 20 × 0.1 = 40 W in a space the size of a thumbnail. An MCB is not built to see either case.
Is my coil actually the size written on it, or is it CCA?
Weigh it. Copper conductor runs 8.89 kg per km per mm², so a 90 m coil of 2.5 mm² holds about 2.00 kg of conductor copper and 4 mm² about 3.20 kg. Any real coil weighs more than that, because of insulation and the drum. What the check catches is a coil lighter than the bare conductor should be. Do not use a magnet — copper-clad aluminium is non-magnetic too.
The socket is hot but the cable is cold — what does that mean?
That is a connection fault, not a cable fault, and a new coil will not fix it. Heat that stops within a metre of the fitting means the resistance is at the terminal: a screw that was never tight, strands left outside the clamp, or a brass contact already burnt. Switch the circuit off and have the termination remade, and the accessory replaced if the metal is discoloured.

The right size, at the factory rate

We draw the copper in Lahore and sell it at the day's rate — no dealer margin, and the line that made the coil answers the message. Send the load, the run length and your city: Punjab in 1–2 days, rest of Pakistan in 2–4.

WhatsApp for a quote