Copper inside the house, aluminium on the service drop and the long heavy feeder. Size for size aluminium carries about 78% of what copper carries — 16 mm² aluminium is 66 A against 85 A for 16 mm² copper — so a swap always means going one or two sizes up.
Aluminium is lighter and cheaper per metre but needs more cross-section, larger terminals and a termination made for it. Copper is smaller for the same current, easier to terminate on the small screw terminals inside a distribution board or an AC isolator, and is what every final circuit in a Pakistani house should be. "Alloy wire" at a Pakistani counter almost always means the aluminium range.
Ask for alloy wire in Pakistan and you will normally be shown aluminium conductor cable, sold as the cheaper alternative to copper for a service drop, a feeder or a submain. The word is loose. It can mean plain aluminium, it can mean an aluminium alloy conductor of the kind used on overhead lines, and it is sometimes used loosely of copper-clad aluminium — a thin copper skin over an aluminium core, which looks like copper at the cut end and behaves like aluminium in the circuit. The three are not the same product and only the first two are what a feeder is designed around.
So do not buy on the word. Ask three questions instead. What is the conductor material? What is the nominal cross-section in mm²? What is the maximum conductor resistance per kilometre? Resistance is the figure IEC 60228 actually defines, it is measurable on a delivered coil, and it settles the argument that a colour or a label cannot. Aluminium at 16 mm² is capped at 1.91 Ω/km; copper at the same size is 1.15. If a seller cannot give you the number, you are being sold a name.
Is alloy wire safe for house wiring? For final circuits — sockets, lights, an AC point — the answer in a Pakistani house is no, not because aluminium is unsafe in principle but because those circuits use small sizes and small terminals, and aluminium at those sizes needs more cross-section than the accessory was built for and a termination method that houses rarely get. Aluminium belongs where the sizes are large and the terminations are made for it: the drop from the pole, the feeder to a board, the run to a tube well.
Aluminium conducts less well than copper, so the same cross-section carries less current. The ratio is close to constant across the range: 66 ÷ 85 = 0.78 at 16 mm², 87 ÷ 112 = 0.78 at 25 mm², 230 ÷ 299 = 0.77 at 120 mm². Whatever the size, expect roughly three-quarters of the copper figure.
| Size | Copper, 2 cores | Aluminium, 2 cores | Copper, 3 cores | Aluminium, 3 cores |
|---|---|---|---|---|
| 10 mm² | 63 A | 48 A | 57 A | 43 A |
| 16 mm² | 85 A | 66 A | 76 A | 59 A |
| 25 mm² | 112 A | 87 A | 96 A | 76 A |
| 35 mm² | 138 A | 107 A | 119 A | 94 A |
| 50 mm² | 168 A | 130 A | 144 A | 113 A |
| 70 mm² | 213 A | 165 A | 184 A | 144 A |
| 95 mm² | 258 A | 199 A | 223 A | 175 A |
| 120 mm² | 299 A | 230 A | 259 A | 202 A |
This is the table nobody publishes for Pakistan, and it is the one that decides whether the swap saves anything. Take the copper size the design calls for, read across, and take the first aluminium size that meets or beats its capacity. At the small end that is one size up; from 25 mm² upwards it is two.
| Copper | Carries | Matching aluminium | Carries | Step |
|---|---|---|---|---|
| 10 mm² | 63 A | 16 mm² | 66 A | 1 size |
| 16 mm² | 85 A | 25 mm² | 87 A | 1 size |
| 25 mm² | 112 A | 50 mm² | 130 A | 2 sizes |
| 35 mm² | 138 A | 70 mm² | 165 A | 2 sizes |
| 50 mm² | 168 A | 95 mm² | 199 A | 2 sizes |
| 70 mm² | 213 A | 120 mm² | 230 A | 2 sizes |
35 mm² aluminium at 107 A looks close enough to 25 mm² copper at 112 A to tempt a one-size swap, and it is 5 A short. Being short before derating means being well short after it, so the table takes the next size instead. This is why "aluminium is one size up" is only half true: it is one size up to 16 mm² copper and two sizes up above it.
Weight is the reason, and it survives the sizing-up. Copper masses 8.89 kg per kilometre for each mm² of conductor; aluminium masses 2.70 — about 30% of the metal for the same cross-section. So even after stepping up to hold the same current, an aluminium conductor is still under half the weight: to carry 85 A you need either 16 mm² copper at 142.2 kg/km or 25 mm² aluminium at 67.5 kg/km, and 67.5 ÷ 142.2 = 0.47.
| Size | Copper mass | Aluminium mass | Same-capacity comparison |
|---|---|---|---|
| 10 mm² | 88.9 kg/km | 27.0 kg/km | 63 A: 10mm² Cu 88.9 vs 16mm² Al 43.2 kg/km |
| 16 mm² | 142.2 kg/km | 43.2 kg/km | 85 A: 16mm² Cu 142.2 vs 25mm² Al 67.5 kg/km |
| 25 mm² | 222.3 kg/km | 67.5 kg/km | 112 A: 25mm² Cu 222.3 vs 50mm² Al 135.0 kg/km |
| 50 mm² | 444.5 kg/km | 135.0 kg/km | 168 A: 50mm² Cu 444.5 vs 95mm² Al 256.5 kg/km |
| 95 mm² | 844.6 kg/km | 256.5 kg/km | 258 A: no aluminium size in our range matches 95mm² Cu |
A span from a pole to a meter board has to hold its own weight between two fixings, and a long feeder has to be carried, pulled and paid for by the kilogram of metal. Both arguments favour aluminium and neither applies inside a house, where the runs are short, the sizes are small, and the cost of the conductor is a minor part of the job. That is the honest reason the service drop is aluminium and the wiring behind the board is copper — not a claim about one metal being better than the other.
Pilone draws both metals in Lahore. Copper runs through the standard cable range for fixed wiring and the flexible cable range where the tail has to bend; aluminium runs from 10 mm² to 120 mm² in the aluminium cable range. The two sizes most feeders land on are 10mm 2 core aluminium cable at 48 A and 16mm 2 core aluminium cable at 66 A; for a three-phase feeder take 16mm 4 core aluminium cable. On the copper side the equivalents are 10mm 2 core cable at 63 A and 16mm 2 core cable price at 85 A.
We draw both in Lahore and sell at the day's rate — no dealer margin. Send the load, the route length and your city, and we will size both metals and quote them together: Punjab in 1–2 days, rest of Pakistan in 2–4.