Single-core for anything pulled through conduit. Multi-core wherever the cable runs on its own — the submain, three-phase feeders, motor runs and appliance tails.
Single-core is one conductor with one layer of insulation, sold by the coil — usually 90 m, but ask — and drawn loose down a pipe. Multi-core is two, three or four insulated cores under a common outer sheath, so one pull gives you the whole circuit including the earth. Neither carries more current for the same copper. What changes is how many loaded conductors end up sitting together, and that is what sets the current rating — 36 A at 4 mm² with two, 32 A with three.
Clear one thing up first, because it costs people money at the counter: single-core does not mean solid. Single-core describes how many conductors are in the cable — one. Solid describes whether that conductor is one wire or many strands twisted together. A 4 mm² single-core building wire is stranded, 7/0.85 to IEC 60228 class 2, and it is still single-core. If the question you are really asking is solid against stranded, that is the flexible vs solid cable guide, not this one.
In Pakistani house wiring, single-core copper in conduit is the normal build for lighting, socket and appliance points, while multi-core sheathed cable carries the submain from the meter to the distribution board, the three-phase feeders, the motor runs and the appliance tails that leave the conduit. The engineering difference is not the sheath. It is the number of loaded conductors bunched together: at 4 mm², two loaded conductors are rated 36 A and three are rated 32 A on BS 7671 reference method C at 30°C, and single cores bunched in one pipe are grouped and derated by the same physics under a different heading.
| Single-core | Multi-core | |
|---|---|---|
| Conductors in the cable | 1 | 2, 3 or 4 |
| Outer sheath | None — insulation only | Yes, over all cores |
| Mechanical protection | The conduit or trunking provides it | The sheath provides it |
| How the trade sells it | By the coil, usually 90 m | Coil or cut length |
| Earth conductor | Pulled separately, sized separately | Included as the third or fourth core |
| Read the rating from | The grouping factor for the pipe | The loaded-core column of the table |
| Where it belongs | Lighting, socket and appliance points in conduit | Submains, feeders, motors, tails outside conduit |
| Pilone range | General wiring single-core coils | Standard and flexible cable |
A conductor's rating is a heat limit. Put two current-carrying conductors side by side under one sheath and each has one neighbour warming it; put three, and each has two. So the same copper is allowed less current in a three-core cable than in a two-core, and the standard prints two columns for exactly that reason. The earth core does not count — it carries no current in normal service — so a 3-core cable feeding a single-phase point is still read on the two-loaded-conductor column.
| Size | 2 loaded conductors | 3 loaded conductors | Loss | Class 2 strands |
|---|---|---|---|---|
| 1.5 mm² | 19.5 A | 17.5 A | 10.3% | 7/0.53 |
| 2.5 mm² | 27 A | 24 A | 11.1% | 7/0.67 |
| 4 mm² | 36 A | 32 A | 11.1% | 7/0.85 |
| 6 mm² | 46 A | 41 A | 10.9% | 7/1.04 |
| 10 mm² | 63 A | 57 A | 9.5% | 7/1.35 |
| 16 mm² | 85 A | 76 A | 10.6% | 7/1.70 |
| 25 mm² | 112 A | 96 A | 14.3% | 7/2.14 |
Worked through: take a three-phase submain drawing 60 A. Read the three-loaded-conductor column, because all three phases carry current. 10 mm² gives 57 A and is short before any derating at all; 16 mm² gives 76 A and holds. Read the wrong column and 10 mm² looks like a 63 A cable and passes the check. That one column is the most common sizing error made on four-core cable, and it is why the three-phase cable size guide works off the three-conductor figures throughout.
Single cores dodge the sheath but not the physics. Six loaded cores pulled down one 25 mm conduit heat each other exactly as six cores under one sheath would, and BS 7671 handles it with a grouping factor instead of a second column. The factor is set by how many circuits share the pipe, so a lighting circuit and a socket circuit sharing one conduit count as two circuits, not as the five separate conductors in the pipe. Ask your electrician for the factor that applies to your conduit before you commit to a size.
A 3-core sheathed cable hands you the earth at the same size as the live and neutral, in the same sheath, terminated at the same time. Nothing to remember and nothing to skimp. With single cores the earth is a separate purchase, a separate pull and a separate decision — and on site it is the one that gets shaved, because a thinner earth is cheaper and nobody sees it after the plaster goes on.
On a 4 mm² appliance point that means the earth should also be 4 mm², whether it arrives as the third core of a 4mm 3 core standard cable or as a separate 4 mm² single core in the same conduit. If the earth is the only thing you take from this page, take that.
| Job | Build | Usual size |
|---|---|---|
| Lighting and fan points in conduit | Single-core | 1.5 mm² (3/.029) |
| Socket and kitchen circuits in conduit | Single-core | 2.5 mm² (7/.029) |
| AC and geyser points in conduit | Single-core | 4 mm² (7/.036) |
| Meter to distribution board | Multi-core, 2 core | 16mm 2 core cable |
| Three-phase submain or motor feeder | Multi-core, 4 core | 25mm 4 core cable |
| Appliance tail outside the conduit | Multi-core flexible | 4mm 3 core flexible cable |
| Solar string, panel to inverter | Single-core DC | 6 mm² solar DC |
One rule covers most of it: if the conduit protects the cable, buy single cores and pull them; if nothing protects the cable, buy the sheath. Send the size, the core count and the metres and we quote at the day's copper rate — Punjab in 1–2 days, the rest of Pakistan in 2–4.
Send the size, the core count and the metres with your city. We draw the copper in Lahore and quote at the day's rate — Punjab in 1–2 days, the rest of Pakistan in 2–4.