Skip to content
Factory-direct from Lahore · Nationwide delivery in 2–4 days +92 319 4262451 WhatsApp

How much wire is required for house wiring?

PILONE CABLES TECHNICAL TEAM

Points × average run × conductors per run, plus 15% for wastage, divided by 90 = coils. A compact single-storey house of 37 points needs about 1,378 m of single-core copper: 16 coils across the three wiring sizes, plus a 23 m cut length of 6 mm² for the main earth.

There is no figure that follows from plot size alone, because the three inputs above are what the plot does not tell you: how many points you are wiring, how far each one sits from the board, and how many conductors each run carries. Count those three off your own layout and the arithmetic below turns them into a coil list you can hand to a supplier. The full bill for a given plot — point schedule, storey delta, cost scope — sits on that plot's own guide.

The wire calculation for a house, in four inputs

This is the derivation almost nobody publishes. Every quantity on a typical house wiring list is asserted with no point count, no run length and no conductor count behind it, which is why two lists for the same house can differ several times over and neither can be adjusted to yours.

1. Points (P)

Every light, fan, socket, AC, geyser and pump position on the approved layout. Count switches as part of the point they control. This is the input that moves the total most, so count it, do not estimate it.

2. Average run (L)

The one-way route from the distribution board to a typical point, in metres, following the conduit and not the straight line. Take it as the floor's diagonal less about 15%: a 950 sq ft floor is roughly 25 × 38 ft, whose diagonal is 45.5 ft or 13.9 m, giving about 12 m.

3. Conductors per run (C)

2.5 on lighting and fan circuits, where switch legs share a neutral. 3 on socket and appliance circuits, which each carry live, neutral and earth. Use 1 for the single main earthing conductor.

4. Margin (w)

10–20% on top for cutting waste, failed pulls and the drops you did not draw. 15% is the working figure below. Add it before you convert to coils, not after.

Multiplied out: conductor metres = P × L × C, then × 1.15, then ÷ 90 for coils. Do it once per cable size, not once for the house, because you cannot buy a part-coil of one size with the leftover of another.

The circuit worksheet, worked all the way through

Take a single-storey house of about 900 sq ft covered area, wired to 37 points on 9 circuits, distribution board central, all runs in conduit. Fill your own numbers into the same rows.

Worked circuit sheet. Conductor metres = points × average run × conductors per run, before margin. Average runs are measured along the conduit route from the distribution board, one way. Replace every figure with your own; the arithmetic does not change.
CircuitPointsAverage runConductorsSizeConductor metres
Lighting and fans, front810 m2.51.5 mm²200 m
Lighting and fans, rear812 m2.51.5 mm²240 m
Room sockets, front611 m32.5 mm²198 m
Room sockets, rear613 m32.5 mm²234 m
Kitchen59 m32.5 mm²135 m
Water pump115 m32.5 mm²45 m
AC point 1114 m34 mm²42 m
AC point 2116 m34 mm²48 m
Geyser point112 m34 mm²36 m
Main earthing conductor20 m16 mm²20 m
Total, before margin371,198 m

Now the margin and the conversion, size by size. 1.5 mm²: 200 + 240 = 440 m, × 1.15 = 506 m, ÷ 90 = 5.6, so 6 coils. 2.5 mm²: 198 + 234 + 135 + 45 = 612 m, × 1.15 = 704 m, so 8 coils. 4 mm²: 42 + 48 + 36 = 126 m, × 1.15 = 145 m, so 2 coils. The 6 mm² earth is 20 m × 1.15 = 23 m, bought as a cut length rather than a coil. So the need is 1,378 m of conductor in total, and the order is sixteen coils plus that 23 m cut length — and every one of those numbers moves if your point count does.

Notice what the rounding costs. The three coil sizes need 506 + 704 + 145 = 1,355 m between them, and rounded per size they come as 6 + 8 + 2 = 16 coils, which is 1,440 m: 1,440 − 1,355 = 85 m of spare. The 6 mm² earth sits outside that sum entirely, because a 23 m cut length is not part of any coil. That 85 m is not waste; it is the reason a second coil of 4 mm² goes on the order rather than a short delivery stopping the job. Round up per size every time.

One coil kitne meter ka hota hai?

A standard coil of single-core house wire in Pakistan is 90 m, near enough 100 yards. That is the unit the trade buys in and the unit an electrician will quote back at you, while every technical source publishes metres. One conversion sits between them: metres ÷ 90, rounded up per size.

Coil length is also the number that quietly varies between suppliers, so confirm it in writing before you order — from us or from anyone else. Two checks settle it on delivery. A tape walked against a marked 10 m span is definitive. A faster screen is resistance: IEC 60228 caps 1.5 mm² class 2 copper at 12.1 Ω/km at 20 °C, so a full 90 m coil should read no more than 12.1 × 0.090 = 1.09 Ω end to end. Read that honestly: the standard sets a maximum, real copper reads under it, and a low reading can mean good copper or a short coil. Resistance flags a problem; the tape proves it. We quote per metre, so a coil count is a convenience conversion on our side rather than the unit of sale.

The cross-check that catches a bad estimate

Counting points gives one answer. There is a second, independent route, and any estimate worth ordering against has to survive both. The trade rule is 1.5–2 ft of conduit run per square foot of plot; at 2–3 conductors pulled through each run, that converts to a band of conductor metres. If your counted figure falls outside the band for your plot, one of your three inputs is wrong.

Planning band from the area rule only, single storey. Plot area = marla × 225 sq ft. Runs = plot × 1.5 to 2 ft, converted at 3.281 ft/m. Conductor metres = runs × 2 to 3. Coils at 90 m, rounded up. These bands are deliberately wide — that is what a rule of thumb is worth. Counting points is what narrows them.
PlotPlot areaConduit runsConductor metresCoilsCounted list
3 marla675 sq ft309–412 m617–1,234 m7–143 marla cable list
5 marla1,125 sq ft514–686 m1,029–2,057 m12–235 marla cable list
7 marla1,575 sq ft720–960 m1,440–2,880 m16–327 marla cable list
10 marla2,250 sq ft1,029–1,372 m2,057–4,114 m23–4610 marla cable list
1 kanal4,500 sq ft2,057–2,743 m4,114–8,229 m46–921 kanal cable list
2 kanal9,000 sq ft4,114–5,486 m8,229–16,457 m92–1832 kanal cable list

One warning about the counted route on large plots. The average run stops growing with the plot once the house gets a second distribution board, because every final circuit then measures back to the nearest board, not to the main one. Keep multiplying by a whole-house diagonal on a kanal and the count will land far above the area band. On anything above about 10 marla, split the sheet per board and add a submain row between them.

Double storey mein kitna extra wire lagega?

Run the sheet twice, once per floor, and change three things on the upper one. The point count drops — there is no porch, no main entrance, no pump upstairs, so plan on about 85% of the ground floor's points. The average run shortens if the upper floor gets its own board. And a riser appears that the ground floor did not need: a submain from the main board to the upper board, sized on the load it feeds rather than on the floor area.

Lay the riser conduit before the plaster goes on. It is the one run that cannot be added later without breaking a wall from top to bottom, and it is the item most often left off a quantity list because it belongs to neither floor. Each plot guide carries its own single-versus-double-storey table.

The cable a coil list always leaves out

The coils wire the house. They do not feed it. The run from the WAPDA or K-Electric meter to the distribution board is a separate multicore cable bought by the running foot, not by the coil, and it is missing from nearly every published wiring list. Size it on the sanctioned load off your meter card: a 7.5 kW single-phase connection is 7500 ÷ 220 = 34.1 A, which puts 10 mm² copper — 63 A, and 4.4 mV/A/m of drop — on a run of about 22 m before the voltage-drop budget is spent. Two-core for single phase, four-core for three phase.

The full rationale, including the aluminium alternative on long service runs, is on WAPDA meter cable size and main meter cable. Add its metres to the order as a cut length: 10mm 2 core cable for a single-phase house, 16mm 4 core aluminium cable where the run is long and the connection is three phase.

These are planning quantities from a stated point count, run length and conductor count — not a certified design. Cable sizes for each circuit are set by load, installation method and run length, not by the quantity sheet. Confirm the point schedule, the circuit count and every size with a licensed electrician against your approved layout — the selection chart is on single-phase cable size, and the cable size calculator settles one circuit at a time.

Before you send the list

Three things decide whether the order arrives right, and none of them is the coil count.

TIMING

Order at conduit stage

Wire is pulled after the conduit is laid and before the plaster. The new-house wiring sequence sets out where it falls.

SPLIT

Sizes, not a total

Send the coil count per size. A single total metre figure cannot be cut, priced or delivered as one thing.

REWIRE

Old house, more wire

A rewire re-uses some conduit and abandons the rest. Rewiring an old house carries the allowance.

Frequently asked

Ghar ki wiring mein kitna wire lagta hai, kaise hisab lagayein?
Teen cheezein ginein: points, har point ka board tak average run, aur har run mein kitne conductor jate hain. Phir points × run × conductors, 15% wastage ka izafa, aur 90 se taqseem — jitne coil chahiyen. Misal ke tor par 37 points, average 12 m run par, takreeban 16 coil banta hai. Har size ka hisab alag lagayein.
Can I make a house wiring wire estimate from plot size alone?
Only as a wide band. The area rule gives 1.5–2 ft of conduit run per square foot of plot and 2–3 conductors per run, which on a 5 marla plot lands anywhere between 12 and 23 coils. That band is useful for catching a wrong estimate, not for placing an order. Counting points is what narrows it.
One coil kitne meter ka hota hai?
Single-core house wire ka standard coil Pakistan mein 90 m ka hota hai, takreeban 100 gaz. Har figure isi se convert hota hai: meters ÷ 90, aur har size ke liye upar round karein. Order se pehle coil ki lambai likhwa lein — hum se ho ya kisi aur se, yehi woh number hai jo supplier se supplier badalta hai.
Kitna extra wire lena chahiye wastage ke liye?
10–20%, aur 15% aam kaam ka figure hai. Yeh cutting waste, nakaam pulls aur woh drops cover karta hai jo layout par nahi bane thay. Margin coil mein convert karne se pehle lagayein, baad mein nahi — aur har size alag round up karein, warna ek size ka bacha hua doosre ke kaam nahi aata.
How many conductors should I count per run?
2.5 on lighting and fan circuits, because switch legs share a neutral back to the point. 3 on socket and appliance circuits, which each carry live, neutral and earth the whole way. The main earthing conductor is a single run of its own. Using 3 everywhere overstates a lighting-heavy house by about 8%.
Does the meter to distribution board cable come out of the coils?
No. That run is a separate multicore cable bought by the running foot and sized on your sanctioned load, not on floor area. A 7.5 kW single-phase connection draws 7500 ÷ 220 = 34.1 A and takes 10 mm² copper, rated 63 A, over about 22 m. Add its length to the order as a cut length.
Can Pilone work the quantity out for me?
Send the point count per circuit, the average run to the board and your city on WhatsApp and we will run the same arithmetic back to you as a coil list per size, with today's factory rate against it. Confirm the final quantity against your electrician's layout before anything is cut.

Send the point count, get the coil list

We draw the copper in Lahore and sell it at the day's rate — no dealer margin. Send your points per circuit and your city: Punjab in 1–2 days, rest of Pakistan in 2–4.

Send the point count and your city