Copper tails, two core, one size below the aluminium equivalent: 6 mm² at 5 kW, 10 mm² at 10 kW, 25 mm² at 20 kW.
A 10 kW single-phase connection draws 45.5 A. 10 mm² copper carries 63 A clipped direct at 30°C and 54.8 A after the 40°C ambient correction, so it holds this load where 10 mm² aluminium (48 A, 41.8 A corrected) does not. The service line stops at the meter — the run from there to your board is yours to supply.
The main meter cable is the feeder between the electricity meter and the main distribution board, and it carries the entire sanctioned load of the connection rather than one circuit. In copper, on a single-phase 220 V supply, with BS 7671 method C capacities corrected for a 40°C ambient, that means 6 mm² up to about 5 kW, 10 mm² to 10 kW, 16 mm² to 15 kW, 25 mm² to 20 kW and 35 mm² to 25 kW. Aluminium does the same job one size larger, and it is the default on this run because it costs less per amp.
Size against the sanctioned figure on your connection paperwork, not against the appliances in the house today: the board can be filled later, and the feeder cannot be changed without digging. The aluminium trade-name sizes, 7/.052 and 7/.064, are on the WAPDA cable page; circuits leaving the board are sized on the single-phase and three-phase pages.
Current is load divided by voltage, and the size is chosen so the capacity after correction clears it. The table figure is a 30°C number, and a run leaving the meter board on an outside wall is not at 30°C in a Pakistani summer.
| Sanctioned load | Current at 220 V | Copper 2 core | Capacity at 30°C | Capacity at 40°C | Class 2 strands |
|---|---|---|---|---|---|
| 5 kW | 22.7 A | 6 mm² | 46 A | 40.0 A | 7/1.04 |
| 10 kW | 45.5 A | 10 mm² | 63 A | 54.8 A | 7/1.35 |
| 15 kW | 68.2 A | 16 mm² | 85 A | 74.0 A | 7/1.70 |
| 20 kW | 90.9 A | 25 mm² | 112 A | 97.4 A | 7/2.14 |
| 25 kW | 113.6 A | 35 mm² | 138 A | 120.1 A | 19/1.53 |
Heat settles the size on a short run; length settles it on a long one. Hold the whole installation to 3% of 220 V — 6.6 V — and this feeder should not spend much more than half of it, because every final circuit is fed off the far end.
| Load and size | Current | 10 m | 15 m | 20 m |
|---|---|---|---|---|
| 5 kW · 6 mm² | 22.7 A | 1.66 V | 2.49 V | 3.31 V |
| 10 kW · 10 mm² | 45.5 A | 2.00 V | 3.00 V | 4.00 V |
| 15 kW · 16 mm² | 68.2 A | 1.91 V | 2.86 V | 3.82 V |
| 20 kW · 25 mm² | 90.9 A | 1.59 V | 2.39 V | 3.18 V |
| 25 kW · 35 mm² | 113.6 A | 1.42 V | 2.13 V | 2.84 V |
Read the 10 kW row across. At 10 m the feeder spends 2.00 V of the 6.6 V and the house has room; at 20 m it spends 4.00 V, over half the budget before the first light switch. Go one size up and 16 mm² at 2.8 mV/A/m drops 2.8 × 45.5 × 20 ÷ 1000 = 2.55 V on the same run. Length, not capacity, is what buys the bigger size here — check your own figure in the voltage drop calculator.
Aluminium is the market default here because it is cheaper per amp and lighter to pull. Copper's case is the termination: it takes a lug and holds it, while an aluminium conductor creeps under clamping pressure and wants the joint checked. It also carries more per mm² — 63 A against 48 A at 10 mm². Check what your board's terminals are made to take before choosing.
Copper feeders in stock: 16mm 2 core cable for meter tails · 25mm 2 core cable · copper vs aluminium compared
We draw the copper in Lahore and sell it at the day's rate — no dealer margin. Send your sanctioned load, run length and city: Punjab in 1–2 days, rest of Pakistan in 2–4.