PILONE CABLES TECHNICAL TEAM

WAPDA cable is a trade name, not a utility specification.

In the market it means the aluminium service cable from the meter to your distribution board, in one of two strand codes — 7/.052, sold as 10 mm², and 7/.064, sold as 16 mm². Which one you need follows the sanctioned load on your connection papers, not the name: 10 mm² aluminium carries 48 A clipped direct at 30°C, 16 mm² carries 66 A, and a 10 kW single-phase connection draws 45.5 A — clear on the 30°C figure, short of the 41.8 A that 10 mm² is worth once corrected for a 40°C wall, so 7 kW and under takes 7/.052 and 10 kW takes 7/.064. The distribution company's wire ends at the meter; this run is yours to buy.

What the name actually means

WAPDA cable is the Pakistani trade name for the aluminium meter cable that runs between an electricity meter and a distribution board, and the same product is sold as silver cable — after the grey-white colour of the aluminium conductor, not because there is any silver in it — or simply as meter wire. It is stocked mainly in two strand codes: 7/.052, which computes to 9.6 mm² and is sold as 10 mm², and 7/.064, which computes to 14.5 mm² and is sold as 16 mm². Neither name is a specification, an approval or a standard — it is shop vocabulary for a size and a construction, and reading it as an endorsement is where buyers go wrong.

Two core is a single-phase 220 V connection, live and neutral; four core is three-phase 400 V, three phases and a neutral. Your connection paperwork states which you hold and the sanctioned load in kW that this page turns on. The copper version of the same run is on the main meter cable page; the circuits leaving the board are sized on the single-phase and three-phase pages.

7/.052 kitne mm ka hota hai? Trade code to true size

Strand codes are imperial: 7/.052 is seven strands of 0.052 inch. Work the geometry and the areas do not land on the metric sizes the cable is sold as — what you buy as 16 mm² is 14.5 mm² of aluminium. That is arithmetic, not an accusation, and it is why capacity rather than label is the thing to size against.

Computed area is the geometric area of the strands in the code; sold-as is the nearest IEC 60228 nominal size the trade prices it at. The last two rows are the sizes sold as WAPDA cable or silver cable. Conductor data per IEC 60228.
Strand codeStrands × inchComputed areaSold asUsual conductor
3/.0293 × 0.0291.29 mm²1.5 mm²Copper
7/.0297 × 0.0293.0 mm²2.5–3 mm²Copper
7/.0367 × 0.0364.6 mm²4 mm²Copper
7/.0447 × 0.0446.9 mm²6–7 mm²Copper
7/.0527 × 0.0529.6 mm²10 mm²Aluminium on this run
7/.0647 × 0.06414.5 mm²16 mm²Aluminium on this run

Sanctioned load to size, single-phase 220 V

Current is load divided by voltage. The cable is then chosen so its capacity after correction clears that current — the table figure is a 30°C number, and a service cable on an outside wall in Pakistan is not at 30°C.

Single-phase 220 V; current = load ÷ 220. Aluminium current capacity per BS 7671 reference method C (clipped direct), PVC, 30°C ambient, two loaded conductors; the 40°C column applies the BS 7671 ambient correction for 70°C PVC, Ca = 0.87. Conductor data per IEC 60228. This is a general engineering reference, not a stated DISCO standard — your distribution company may set its own minimum for the service connection. Verify with your DISCO and a licensed electrician before you order.
Sanctioned loadCurrent at 220 VAluminium 2 coreCapacity at 30°CCapacity at 40°CCopper alternative
5 kW22.7 A10 mm² (7/.052)48 A41.8 A6 mm²
7 kW31.8 A10 mm² (7/.052)48 A41.8 A6 mm²
10 kW45.5 A16 mm² (7/.064)66 A57.4 A10 mm²
15 kW68.2 A25 mm²87 A75.7 A16 mm²
20 kW90.9 A35 mm²107 A93.1 A25 mm²

The copper alternative in stock: 16mm 2 core cable · 25mm 2 core cable

Where the market default fails: 10 kW on 7/.052

A 10 kW single-phase connection draws 10000 ÷ 220 = 45.5 A. The size the shop hands over for that job is 10 mm² aluminium — the cable everyone calls WAPDA cable — and at 30°C it is rated 48 A, so on paper it clears by about 5%.

Now put the run where it actually goes: up an outside wall in a Lahore June. The BS 7671 ambient correction for 70°C PVC at 40°C is 0.87, so 48 × 0.87 = 41.8 A — below the 45.5 A the connection draws. The default size has become the weakest part of the connection. 7/.064, the 16 mm², is rated 66 A, corrects to 57.4 A and still clears the load with about 12 A in hand.

Voltage drop says the same thing. Over a 15 m run, at the IEC 60228 conductor resistance of 3.08 Ω/km, 10 mm² aluminium drops 2 × 45.5 × 3.08 × 15 ÷ 1000 = 4.20 V — most of a 6.6 V budget (3% of 220 V) spent before a single house circuit is fed. 16 mm² at 1.91 Ω/km drops 2.61 V.

0.87 is the 40°C figure for 70°C PVC; take the exact correction for your own ambient and installation method from BS 7671, and derate again for a buried or ducted run. This cable feeds the whole house, so an undersized answer is a fire risk rather than an inconvenience. Have a licensed electrician confirm the size and terminate the connection.

Three-phase 400 V connections

On three phases the current spreads across them: 25 kW draws 25000 ÷ (1.732 × 400 × 0.9) = 40.1 A per phase at 0.9 power factor. 16 mm² 4 core clears that after correction; 10 mm² does not. Read the corrected column, not the 30°C one.

Three-phase 400 V; current = load ÷ (1.732 × 400 × 0.9), taking 0.9 power factor. Aluminium capacity with three loaded conductors per BS 7671 reference method C (clipped direct), PVC, 30°C; the 40°C column applies Ca = 0.87 for 70°C PVC. Check the power factor of your own load. Verify with a licensed electrician before you order.
Sanctioned loadCurrent per phaseAluminium 4 coreCapacity at 30°CCapacity at 40°C
10 kW16.0 A10 mm² (7/.052)43 A37.4 A
15 kW24.1 A10 mm² (7/.052)43 A37.4 A
25 kW40.1 A16 mm² (7/.064)59 A51.3 A
40 kW64.2 A25 mm²76 A66.1 A
50 kW80.2 A35 mm²94 A81.8 A

Metres, not coils

Measure the route the cable takes, not the straight line: down from the meter board, along the wall or trench, into the house and up to the board, plus a metre of slack at each end. Most houses land between 8 and 15 metres. Service cable is sold by the coil and coil lengths differ between makers, so ask for the coil length with the rate — a quoted silver cable price in Pakistan is usually a coil price, and a 12 m run does not need a coil. A cut length costs less.

Sizes and rates: 10mm aluminium cable price · 16mm aluminium cable price · 25mm aluminium cable price

If the run goes underground

A buried stretch between the meter pillar and the house wants armour — a steel-wire layer that takes soil pressure, spades and rodents. It also wants a second derating step, because earth around a cable does not shed heat the way open air does. Size it for the buried section, not the wall section.

Cable for an underground run · Armoured cable, 4mm² to 95mm²

Frequently asked

WAPDA cable kya hota hai?
Bazaar mein iska matlab meter se distribution board tak jane wala aluminium service cable hai — 7/.052 (10 mm² ke naam se) ya 7/.064 (16 mm² ke naam se), single phase par 2 core aur three phase par 4 core. Yeh WAPDA ka standard ya approval nahi, sirf dukaan ki zubaan hai. Size sanctioned load par depend karta hai, naam par nahi.
Is it copper or aluminium, and why do people call it silver cable?
Aluminium. Silver cable is the same product under another shop name, taken from the grey-white colour of the conductor — there is no silver in it. Listings that call a silver cable copper have mixed the names up. Aluminium is light in the hand and dull grey at the cut end; copper is orange-brown and heavy.
7/.052 kitne mm ka hota hai?
Seven strands of 0.052 inch computes to 9.6 mm², and the trade sells it as 10 mm². 7/.064 computes to 14.5 mm² and is sold as 16 mm². The codes are imperial and the sale sizes are the nearest IEC 60228 nominal, so they never line up exactly. Size against capacity, not the label.
10mm WAPDA cable kitne ampere le sakta hai?
48 A clipped direct at 30°C on BS 7671 method C. Apply the 40°C correction for 70°C PVC, Ca = 0.87, and it becomes 41.8 A. That covers a 7 kW connection at 31.8 A but not a 10 kW one at 45.5 A. For 10 kW take 7/.064, the 16 mm²: 66 A on the table, 57.4 A corrected.
Does WAPDA or LESCO give you the cable, or do you buy it yourself?
The distribution company's line runs up to the meter. The cable from the meter to your distribution board is normally the customer's to supply, which is why it sits in every hardware market. Confirm any minimum your DISCO sets for the service connection with your local office before you buy the length.

7/.052 and 7/.064, at the factory rate

Ask for the WAPDA cable price on the day and that is what you get: we draw aluminium and copper in Lahore and sell at the day's rate, no dealer margin. Send your sanctioned load, core count, metres and city: Punjab in 1–2 days, rest of Pakistan in 2–4.