Skip to content
Factory-direct from Lahore · Nationwide delivery in 2–4 days +92 319 4262451 WhatsApp

Karachi meter connection cable: same run, hotter wall

PILONE CABLES TECHNICAL TEAM

Same cable as any other Pakistani connection: 10 mm² aluminium (7/.052) on loads to about 7 kW, 16 mm² (7/.064) from 10 kW.

A K-Electric connection is sized the same way as one in a WAPDA-area city: current from the sanctioned load, cable from the current. What Karachi changes is the ambient the cable works in, and that is the step most sizing charts skip — 10 mm² aluminium reads 48 A on the table and 41.8 A once corrected for 40°C. K-Electric's service line ends at the meter; the run from there to your distribution board is yours to supply.

Same cable, different supply company

A meter connection cable in Karachi is the same product as on a WAPDA-area connection anywhere else in Pakistan: 2 core for single-phase 220 V, 4 core for three-phase 400 V, sized so the cable's corrected capacity clears the current the sanctioned load draws. The market sells it in both cities as WAPDA cable or silver cable — aluminium, 7/.052 sold as 10 mm² and 7/.064 sold as 16 mm². No K-Electric approval attaches to those names; they are shop vocabulary for a size.

The full size ladder, the strand-code arithmetic and the three-phase table are on the WAPDA cable page, and they apply to a Karachi connection unchanged. This page covers the K-Electric side of it: what the utility hands over, what you buy, how the rating reads on an exposed Karachi wall, and how the cable reaches you.

What the ambient does to the rating

Published capacities assume 30°C air around the cable. A service run clipped to an outside wall in Karachi does not get that for much of the year, and the correction is a straight multiplier on the rating.

Two loaded conductors, current capacity per BS 7671 reference method C (clipped direct), PVC, 30°C ambient; the 40°C columns apply the BS 7671 ambient correction for 70°C PVC, Ca = 0.87. Take the exact factor for your own ambient and installation method from the standard, and derate again for a ducted or buried run. Conductor data per IEC 60228. This is a general engineering reference, not a stated K-Electric standard; the utility may set its own minimum for the service connection. Verify with a licensed electrician before you order.
SizeAluminium at 30°CAluminium at 40°CCopper at 30°CCopper at 40°C
10 mm² (7/.052)48 A41.8 A63 A54.8 A
16 mm² (7/.064)66 A57.4 A85 A74.0 A
25 mm²87 A75.7 A112 A97.4 A
35 mm²107 A93.1 A138 A120.1 A

Work one job through it. A 10 kW single-phase connection draws 45.5 A: the 30°C column says 10 mm² aluminium is fine, the 40°C column says 41.8 A and it is not. On an exposed wall read the second column — 16 mm² at 57.4 A corrected, or 10 mm² in copper at 54.8 A.

Copper for the same run: 10mm 2 core cable · 16mm 2 core cable

This run feeds the whole premises, so an undersized answer is a fire risk rather than an inconvenience. Confirm your exact sanctioned load and any K-Electric requirement for the service connection, and have a licensed electrician size and terminate it.

Getting it to Karachi

We manufacture in Lahore and dispatch nationwide — Punjab in 1–2 days, the rest of Pakistan including Karachi in 2–4 working days, courier for single coils and transport for bulk. Send the size, core count, total metres and your area on WhatsApp and you get the day's factory rate.

Aluminium cable in Karachi · All cable types in Karachi · Delivery across Pakistan

Frequently asked

Karachi mein K-Electric connection ke liye same cable hai?
Haan. Cable connection ke load se decide hota hai, supply company ke naam se nahi. Single phase par 2 core, three phase par 4 core — wohi bazaar wala WAPDA cable ya silver cable, yani 7/.052 (10 mm²) aur 7/.064 (16 mm²). Farq sirf garmi ka hai: deewar par lagay cable ko 40°C wali rating par parhein.
Does K-Electric supply the meter-to-DB cable?
K-Electric's service line runs up to the meter. The cable from the meter to your distribution board is normally the customer's to supply, which is why it sits in every hardware market. Confirm any minimum for the service connection with your local office before you buy the length.
Does the Karachi climate change the cable size?
It can change it by one size. Ratings are published for 30°C air; the BS 7671 correction for 70°C PVC at 40°C is 0.87, so 10 mm² aluminium falls from 48 A to 41.8 A. A 10 kW connection at 45.5 A clears the first figure and not the second, which is what pushes an exposed run up to 16 mm².

Meter cable to Karachi, at the factory rate

Drawn in Lahore, sold at the day's rate with no dealer margin, dispatched to Karachi in 2–4 working days. Send your sanctioned load, core count and metres.

WhatsApp for advice