Divide the load in watts by 611 to get the current at 415 V, then read the size off the chart. A 30 kW three-phase load draws 49 A and lands on 16 mm² four-core copper once the run is derated for a hot, grouped installation.
The 611 is √3 × 415 × 0.85 — three-phase volts and a power factor of 0.85. 10 mm² carries 57 A on the 30°C clipped-direct table, which looks like enough until plant ambient and tray grouping take a fifth of it away. Past about 60 m on that load it is the voltage drop, not the current, that picks the size.
On a 415 V three-phase supply at a power factor of 0.85, the design current in amps is the load in watts divided by 611 — that is √3 × 415 × 0.85 = 611. A 30 kW load therefore draws 49 A, a 50 kW load 82 A, and a 100 kW load 164 A. Those currents are then read against a cable's tabulated capacity for the way it is actually installed: every figure on this page is BS 7671 reference method C, clipped direct, 30°C ambient, PVC-insulated copper, and each one must be reduced by the correction factors for a hotter ambient or a grouped tray before it is compared with the load.
Two things follow. First, a 415 V cable size is not a 400 V one — the higher the volts, the lower the current for the same kW, so a chart built for 400 V reads about 4% high. Second, the power factor matters as much as the kW. At 0.85 a 30 kW load is 49 A; correct the same plant to unity and it is 42 A. Use the figure from your own plate or bill, not ours, if you know it.
| Load at 415 V | Design current | Base size, 30°C | Needed if factors = 0.80 | Size after derating |
|---|---|---|---|---|
| 5 kW | 8.2 A | 1.5 mm² | 10.2 A | 1.5 mm² |
| 7.5 kW | 12.3 A | 1.5 mm² | 15.4 A | 1.5 mm² |
| 10 kW | 16.4 A | 1.5 mm² | 20.5 A | 2.5 mm² |
| 15 kW | 24.6 A | 4 mm² | 30.7 A | 4 mm² |
| 20 kW | 32.7 A | 6 mm² | 40.9 A | 6 mm² |
| 25 kW | 40.9 A | 6 mm² | 51.2 A | 10 mm² |
| 30 kW | 49.1 A | 10 mm² | 61.4 A | 16 mm² |
| 40 kW | 65.5 A | 16 mm² | 81.9 A | 25 mm² |
| 50 kW | 81.8 A | 25 mm² | 102.3 A | 35 mm² |
| 60 kW | 98.2 A | 35 mm² | 122.8 A | 50 mm² |
| 75 kW | 122.8 A | 50 mm² | 153.5 A | 70 mm² |
| 100 kW | 163.7 A | 70 mm² | 204.6 A | 95 mm² |
| 125 kW | 204.6 A | 95 mm² | 255.8 A | 120 mm² |
| 150 kW | 245.5 A | 120 mm² | 306.9 A | Above 120 mm² |
| 200 kW | 327.3 A | Above 120 mm² | 409.1 A | Above 120 mm² |
Two readings of the same chart. The small end gives the electrical minimum and nothing more — 1.5 mm² satisfies a 10 kW three-phase load on paper, and no plant runs a feeder that thin, because terminations, mechanical strength and the next machine on the board all argue for heavier copper. The top end runs out: past 120 mm² the answer is parallel runs or a larger conductor than the range on this page, and that is a conversation, not a chart lookup.
Every ampacity figure published here is a 30°C, clipped-direct, single-cable number. A shed roof in Multan in June is not 30°C, and a feeder in a loaded tray is not on its own. Both pull the same lever: the tabulated capacity is multiplied by correction factors before it is compared with the load current.
Load in watts ÷ 611 at 415 V and PF 0.85. On a single machine use the full-load current from the nameplate instead — the plate beats every chart.
Required tabulated capacity = design current ÷ (ambient factor × grouping factor). Factors multiply; they do not add.
Pick the smallest size whose 30°C figure clears that number, then run the voltage drop sum. On long runs the drop wins.
We do not publish a correction-factor table, and that is deliberate: the correct factor depends on your insulation, your installation method, your ambient and how many circuits share the tray, and a factor pulled off the wrong row is worse than no factor at all. Take them from BS 7671 or IEC 60364-5-52 for your own case. What this page can give you is the shape of the arithmetic, which almost no local sizing page shows: a 30°C rating of 57 A with factors multiplying to 0.80 is a 45.6 A cable, because 57 × 0.80 = 45.6. Write it as base × factor = result every time, so the next person can audit it.
Read the three-or-four-loaded-conductor column for a three-phase feeder. The number of loaded cores sets the rating, not the number of cores in the sheath: a four-core cable feeding a balanced motor with no neutral still has three conductors carrying current.
| Size | 2 loaded cores | 3–4 loaded cores | Drop, single phase | Drop, three phase | Class 2 strands | Resistance |
|---|---|---|---|---|---|---|
| 2.5 mm² | 27 A | 24 A | 18 mV/A/m | 15.6 mV/A/m | 7/0.67 | 7.41 Ω/km |
| 4 mm² | 36 A | 32 A | 11 mV/A/m | 9.5 mV/A/m | 7/0.85 | 4.61 Ω/km |
| 6 mm² | 46 A | 41 A | 7.3 mV/A/m | 6.3 mV/A/m | 7/1.04 | 3.08 Ω/km |
| 10 mm² | 63 A | 57 A | 4.4 mV/A/m | 3.8 mV/A/m | 7/1.35 | 1.83 Ω/km |
| 16 mm² | 85 A | 76 A | 2.8 mV/A/m | 2.4 mV/A/m | 7/1.70 | 1.15 Ω/km |
| 25 mm² | 112 A | 96 A | 1.75 mV/A/m | 1.5 mV/A/m | 7/2.14 | 0.727 Ω/km |
| 35 mm² | 138 A | 119 A | 1.25 mV/A/m | 1.1 mV/A/m | 19/1.53 | 0.524 Ω/km |
| 50 mm² | 168 A | 144 A | 0.93 mV/A/m | 0.81 mV/A/m | 19/1.78 | 0.387 Ω/km |
| 70 mm² | 213 A | 184 A | 0.63 mV/A/m | 0.55 mV/A/m | 19/2.14 | 0.268 Ω/km |
| 95 mm² | 258 A | 223 A | 0.46 mV/A/m | 0.40 mV/A/m | 37/1.78 | 0.193 Ω/km |
| 120 mm² | 299 A | 259 A | 0.36 mV/A/m | 0.31 mV/A/m | 37/2.03 | 0.153 Ω/km |
A workshop board carrying a mixed 30 kW three-phase load, 60 m from the main panel, run on a tray with other loaded feeders in a shed that gets well past 30°C in summer.
Current. 30,000 ÷ 611 = 49.1 A.
Capacity. 10 mm² is rated 57 A with three loaded conductors. Take the ambient and grouping factors as multiplying to 0.80 for this shed — your own factors come out of BS 7671 — and 57 × 0.80 = 45.6 A, which is below 49.1 A. 10 mm² fails. 16 mm² is 76 A, and 76 × 0.80 = 60.8 A, which clears 49.1 A with 11.7 A to spare.
Voltage drop. On 16 mm² three-phase: 2.4 × 49.1 × 60 ÷ 1000 = 7.07 V. Against a 2.5% feeder budget of 10.4 V that passes. Had 10 mm² survived the derating it would have dropped 3.8 × 49.1 × 60 ÷ 1000 = 11.19 V and failed anyway.
Answer: 16 mm², four core. Both checks land on the same size, which is the comfortable case. When they disagree, the larger size wins — that is the next example.
Long feeder runs are ordinary in Pakistani plants — transformer yard to a shed at the back of the compound, 150 to 300 m. On those runs the current stops being the constraint.
Take 80 A over 200 m. On capacity alone, 25 mm² at 96 A looks right; apply 0.80 and it is 76.8 A, just under the load, so 35 mm² at 119 × 0.80 = 95.2 A is the first size that passes on current. Now the drop, on a 2.5% budget of 10.4 V:
| Size | Drop at 80 A over 200 m | Inside 2.5% (10.4 V)? |
|---|---|---|
| 25 mm² | 24.0 V | No |
| 35 mm² | 17.6 V | No |
| 50 mm² | 12.96 V | No |
| 70 mm² | 8.8 V | Yes |
| 95 mm² | 6.4 V | Yes |
Answer: 70 mm² — two sizes above what the current alone allowed, and the money is in the copper, not the calculation. If the load is motors and the budget is the looser 5% (20.8 V), 35 mm² passes and the bill halves; that choice of budget is the single biggest lever on a long feeder, so make it deliberately and write it on the drawing.
The general shape: on a 415 V feeder the drop starts binding somewhere near 100 m, whatever the size. This is how far each size reaches at its own full 30°C rating before it eats a 2.5% budget.
| Size | Rated current | Reach at full load |
|---|---|---|
| 4 mm² | 32 A | 34 m |
| 6 mm² | 41 A | 40 m |
| 10 mm² | 57 A | 48 m |
| 16 mm² | 76 A | 57 m |
| 25 mm² | 96 A | 72 m |
| 35 mm² | 119 A | 79 m |
| 50 mm² | 144 A | 89 m |
| 70 mm² | 184 A | 103 m |
| 95 mm² | 223 A | 117 m |
| 120 mm² | 259 A | 130 m |
Check your own run in the voltage drop calculator, or start from the load in the cable size calculator.
Load ko watt mein le kar 611 se taqseem kar dein — yeh √3 × 415 × 0.85 hai. 30 kW ka matlab 49 amp. Ab chart se woh size lein jiska rating 30°C wala figure hai, aur us par garmi aur grouping ke factor laga kar dekhein ke woh current se ooper rehta hai ya nahi. Factor zarb hote hain, jama nahi.
Aur ek baat jo aksar chhoot jati hai: 100 meter se lambi run par size voltage drop se tay hota hai, current se nahi. Machine ki plate par likha full-load current har chart se behtar hai — jahan plate mil jaye, wahan chart chhor dein.
Panel drawings are in mm²; the shop still quotes strand codes. The codes are imperial and do not land exactly on the IEC 60228 nominal areas, which is why one cable has two names and why a purchase order and a delivery note can disagree without anybody lying.
| Trade code | Actual area | Sold as | 3–4 core capacity |
|---|---|---|---|
| 7/.029 | 3.0 mm² | 2.5–3 mm² | 24 A |
| 7/.036 | 4.6 mm² | 4 mm² | 32 A |
| 7/.044 | 6.9 mm² | 6–7 mm² | 41 A |
| 7/.052 | 9.6 mm² | 10 mm² | 57 A |
| 7/.064 | 14.5 mm² | 16 mm² | 76 A |
Fixed three-phase feeders are class 2 stranded copper, PVC insulated and sheathed, 450/750 V — the standard cable range, made in 4-core for a line-neutral-earth feeder and 3-core where a balanced load needs no neutral. These are the sizes that leave the Lahore line most often for panel and motor work.
The 50 kW feeder size, and the one most often asked for by name. Also as 25mm 3 core cable for a three-phase motor feeder.
Where the 30 kW worked example landed once the shed ambient and the tray were counted.
Sub-distribution and small three-phase machines, on short cool runs where nothing derates it away.
Cable is priced off the day's copper rate, so we quote per metre and per coil on WhatsApp rather than publish a number that goes stale. Send the sizes and total metres — a bill of quantities is fine as a photo — with your city: Punjab in 1–2 days, rest of Pakistan in 2–4.
Tell us the connected load in kW, the run length, and how the cable is installed — tray, conduit, buried. We match it to a size and quote the day's factory rate. A bill of quantities gets a line-item answer.