Skip to content
Factory-direct from Lahore · Nationwide delivery in 2–4 days +92 319 4262451 WhatsApp

3-phase cable size in Pakistan: kW → amps → mm²

PILONE CABLES TECHNICAL TEAM

Divide the load in watts by 611 to get the current at 415 V, then read the size off the chart. A 30 kW three-phase load draws 49 A and lands on 16 mm² four-core copper once the run is derated for a hot, grouped installation.

The 611 is √3 × 415 × 0.85 — three-phase volts and a power factor of 0.85. 10 mm² carries 57 A on the 30°C clipped-direct table, which looks like enough until plant ambient and tray grouping take a fifth of it away. Past about 60 m on that load it is the voltage drop, not the current, that picks the size.

kW to cable size: the one sum that does it

On a 415 V three-phase supply at a power factor of 0.85, the design current in amps is the load in watts divided by 611 — that is √3 × 415 × 0.85 = 611. A 30 kW load therefore draws 49 A, a 50 kW load 82 A, and a 100 kW load 164 A. Those currents are then read against a cable's tabulated capacity for the way it is actually installed: every figure on this page is BS 7671 reference method C, clipped direct, 30°C ambient, PVC-insulated copper, and each one must be reduced by the correction factors for a hotter ambient or a grouped tray before it is compared with the load.

Two things follow. First, a 415 V cable size is not a 400 V one — the higher the volts, the lower the current for the same kW, so a chart built for 400 V reads about 4% high. Second, the power factor matters as much as the kW. At 0.85 a 30 kW load is 49 A; correct the same plant to unity and it is 42 A. Use the figure from your own plate or bill, not ours, if you know it.

3 phase cable size chart, Pakistan. Design current = load in watts ÷ 611 (√3 × 415 V × PF 0.85). Base size is the smallest copper conductor whose tabulated capacity covers that current with three or four loaded conductors: BS 7671 reference method C (clipped direct), 30°C ambient, PVC; conductor data per IEC 60228. The derated column is an illustration — it assumes your ambient and grouping factors multiply to 0.80, so the cable must be tabulated for current ÷ 0.80. Take the real factors for your installation from BS 7671. Verify sizing with a licensed electrician.
Load at 415 VDesign currentBase size, 30°CNeeded if factors = 0.80Size after derating
5 kW8.2 A1.5 mm²10.2 A1.5 mm²
7.5 kW12.3 A1.5 mm²15.4 A1.5 mm²
10 kW16.4 A1.5 mm²20.5 A2.5 mm²
15 kW24.6 A4 mm²30.7 A4 mm²
20 kW32.7 A6 mm²40.9 A6 mm²
25 kW40.9 A6 mm²51.2 A10 mm²
30 kW49.1 A10 mm²61.4 A16 mm²
40 kW65.5 A16 mm²81.9 A25 mm²
50 kW81.8 A25 mm²102.3 A35 mm²
60 kW98.2 A35 mm²122.8 A50 mm²
75 kW122.8 A50 mm²153.5 A70 mm²
100 kW163.7 A70 mm²204.6 A95 mm²
125 kW204.6 A95 mm²255.8 A120 mm²
150 kW245.5 A120 mm²306.9 AAbove 120 mm²
200 kW327.3 AAbove 120 mm²409.1 AAbove 120 mm²

Two readings of the same chart. The small end gives the electrical minimum and nothing more — 1.5 mm² satisfies a 10 kW three-phase load on paper, and no plant runs a feeder that thin, because terminations, mechanical strength and the next machine on the board all argue for heavier copper. The top end runs out: past 120 mm² the answer is parallel runs or a larger conductor than the range on this page, and that is a conversation, not a chart lookup.

What the 30°C column is worth on a plant floor at 45°C

Every ampacity figure published here is a 30°C, clipped-direct, single-cable number. A shed roof in Multan in June is not 30°C, and a feeder in a loaded tray is not on its own. Both pull the same lever: the tabulated capacity is multiplied by correction factors before it is compared with the load current.

1. Design current

Load in watts ÷ 611 at 415 V and PF 0.85. On a single machine use the full-load current from the nameplate instead — the plate beats every chart.

2. Divide by the factors

Required tabulated capacity = design current ÷ (ambient factor × grouping factor). Factors multiply; they do not add.

3. Read the size, then check the drop

Pick the smallest size whose 30°C figure clears that number, then run the voltage drop sum. On long runs the drop wins.

We do not publish a correction-factor table, and that is deliberate: the correct factor depends on your insulation, your installation method, your ambient and how many circuits share the tray, and a factor pulled off the wrong row is worse than no factor at all. Take them from BS 7671 or IEC 60364-5-52 for your own case. What this page can give you is the shape of the arithmetic, which almost no local sizing page shows: a 30°C rating of 57 A with factors multiplying to 0.80 is a 45.6 A cable, because 57 × 0.80 = 45.6. Write it as base × factor = result every time, so the next person can audit it.

A wrong feeder on a factory board is a much larger failure than a wrong socket circuit. Current capacity depends on installation method, grouping and ambient temperature, and the figures here assume clipped direct at 30°C. Have a licensed electrician confirm the size, the correction factors and the protective device for your load and run length before you order cable.

Current capacity and voltage drop by size

Read the three-or-four-loaded-conductor column for a three-phase feeder. The number of loaded cores sets the rating, not the number of cores in the sheath: a four-core cable feeding a balanced motor with no neutral still has three conductors carrying current.

Copper, PVC insulated, 450/750 V fixed wiring. Current capacity and voltage drop per BS 7671 reference method C (clipped direct), 30°C ambient; conductor resistance and stranding per IEC 60228. The three-phase drop column is the two-core figure × √3÷2 = 0.866, because a three-phase line-to-line drop is √3·I·R·L against 2·I·R·L for a single-phase circuit. Derate all capacities for ambient and grouping. Verify sizing with a licensed electrician for your installation.
Size2 loaded cores3–4 loaded coresDrop, single phaseDrop, three phaseClass 2 strandsResistance
2.5 mm²27 A24 A18 mV/A/m15.6 mV/A/m7/0.677.41 Ω/km
4 mm²36 A32 A11 mV/A/m9.5 mV/A/m7/0.854.61 Ω/km
6 mm²46 A41 A7.3 mV/A/m6.3 mV/A/m7/1.043.08 Ω/km
10 mm²63 A57 A4.4 mV/A/m3.8 mV/A/m7/1.351.83 Ω/km
16 mm²85 A76 A2.8 mV/A/m2.4 mV/A/m7/1.701.15 Ω/km
25 mm²112 A96 A1.75 mV/A/m1.5 mV/A/m7/2.140.727 Ω/km
35 mm²138 A119 A1.25 mV/A/m1.1 mV/A/m19/1.530.524 Ω/km
50 mm²168 A144 A0.93 mV/A/m0.81 mV/A/m19/1.780.387 Ω/km
70 mm²213 A184 A0.63 mV/A/m0.55 mV/A/m19/2.140.268 Ω/km
95 mm²258 A223 A0.46 mV/A/m0.40 mV/A/m37/1.780.193 Ω/km
120 mm²299 A259 A0.36 mV/A/m0.31 mV/A/m37/2.030.153 Ω/km

Worked example: 30 kW plant load, 60 m, hot and grouped

A workshop board carrying a mixed 30 kW three-phase load, 60 m from the main panel, run on a tray with other loaded feeders in a shed that gets well past 30°C in summer.

Current. 30,000 ÷ 611 = 49.1 A.

Capacity. 10 mm² is rated 57 A with three loaded conductors. Take the ambient and grouping factors as multiplying to 0.80 for this shed — your own factors come out of BS 7671 — and 57 × 0.80 = 45.6 A, which is below 49.1 A. 10 mm² fails. 16 mm² is 76 A, and 76 × 0.80 = 60.8 A, which clears 49.1 A with 11.7 A to spare.

Voltage drop. On 16 mm² three-phase: 2.4 × 49.1 × 60 ÷ 1000 = 7.07 V. Against a 2.5% feeder budget of 10.4 V that passes. Had 10 mm² survived the derating it would have dropped 3.8 × 49.1 × 60 ÷ 1000 = 11.19 V and failed anyway.

Answer: 16 mm², four core. Both checks land on the same size, which is the comfortable case. When they disagree, the larger size wins — that is the next example.

Worked example: a 200 m feeder at 80 A, where the drop decides

Long feeder runs are ordinary in Pakistani plants — transformer yard to a shed at the back of the compound, 150 to 300 m. On those runs the current stops being the constraint.

Take 80 A over 200 m. On capacity alone, 25 mm² at 96 A looks right; apply 0.80 and it is 76.8 A, just under the load, so 35 mm² at 119 × 0.80 = 95.2 A is the first size that passes on current. Now the drop, on a 2.5% budget of 10.4 V:

Volts lost on a 200 m three-phase run at 80 A. Figure = three-phase mV/A/m × 80 A × 200 m ÷ 1000. Budgets: 2.5% of 415 V = 10.4 V, 5% = 20.8 V. Voltage drop per BS 7671 reference method C, 30°C, copper, PVC. Verify sizing with a licensed electrician for your installation.
SizeDrop at 80 A over 200 mInside 2.5% (10.4 V)?
25 mm²24.0 VNo
35 mm²17.6 VNo
50 mm²12.96 VNo
70 mm²8.8 VYes
95 mm²6.4 VYes

Answer: 70 mm² — two sizes above what the current alone allowed, and the money is in the copper, not the calculation. If the load is motors and the budget is the looser 5% (20.8 V), 35 mm² passes and the bill halves; that choice of budget is the single biggest lever on a long feeder, so make it deliberately and write it on the drawing.

The general shape: on a 415 V feeder the drop starts binding somewhere near 100 m, whatever the size. This is how far each size reaches at its own full 30°C rating before it eats a 2.5% budget.

Longest one-way run within a 10.4 V budget (2.5% of 415 V) when the cable is loaded to its full three-or-four-core 30°C rating. Length = 10.4 ÷ (three-phase mV/A/m × rated amps ÷ 1000), to the nearest metre. Loaded lighter, the same cable reaches proportionally further. Capacity and drop per BS 7671 reference method C, 30°C, copper, PVC. Verify sizing with a licensed electrician.
SizeRated currentReach at full load
4 mm²32 A34 m
6 mm²41 A40 m
10 mm²57 A48 m
16 mm²76 A57 m
25 mm²96 A72 m
35 mm²119 A79 m
50 mm²144 A89 m
70 mm²184 A103 m
95 mm²223 A117 m
120 mm²259 A130 m

Check your own run in the voltage drop calculator, or start from the load in the cable size calculator.

415V par 3 phase cable ka size kaise nikalte hain?

Load ko watt mein le kar 611 se taqseem kar dein — yeh √3 × 415 × 0.85 hai. 30 kW ka matlab 49 amp. Ab chart se woh size lein jiska rating 30°C wala figure hai, aur us par garmi aur grouping ke factor laga kar dekhein ke woh current se ooper rehta hai ya nahi. Factor zarb hote hain, jama nahi.

Aur ek baat jo aksar chhoot jati hai: 100 meter se lambi run par size voltage drop se tay hota hai, current se nahi. Machine ki plate par likha full-load current har chart se behtar hai — jahan plate mil jaye, wahan chart chhor dein.

7/.052, 7/.064: what the trade codes mean at feeder sizes

Panel drawings are in mm²; the shop still quotes strand codes. The codes are imperial and do not land exactly on the IEC 60228 nominal areas, which is why one cable has two names and why a purchase order and a delivery note can disagree without anybody lying.

Trade code is the imperial strand-diameter code Pakistani shops sell by; the area it computes to does not coincide exactly with the IEC 60228 nominal area the cable is sold as. Capacity is read against the nominal size with three or four loaded conductors, BS 7671 reference method C, 30°C, copper, PVC. Verify sizing with a licensed electrician for your installation.
Trade codeActual areaSold as3–4 core capacity
7/.0293.0 mm²2.5–3 mm²24 A
7/.0364.6 mm²4 mm²32 A
7/.0446.9 mm²6–7 mm²41 A
7/.0529.6 mm²10 mm²57 A
7/.06414.5 mm²16 mm²76 A

Where this page stops and another one starts

The cable for a three-phase feeder

Fixed three-phase feeders are class 2 stranded copper, PVC insulated and sheathed, 450/750 V — the standard cable range, made in 4-core for a line-neutral-earth feeder and 3-core where a balanced load needs no neutral. These are the sizes that leave the Lahore line most often for panel and motor work.

96 A · 3–4 CORE

25mm 4 core cable

The 50 kW feeder size, and the one most often asked for by name. Also as 25mm 3 core cable for a three-phase motor feeder.

76 A · 4 CORE

16mm 4 core cable

Where the 30 kW worked example landed once the shed ambient and the tray were counted.

57 A · 4 CORE

10mm 4 core cable

Sub-distribution and small three-phase machines, on short cool runs where nothing derates it away.

Cable is priced off the day's copper rate, so we quote per metre and per coil on WhatsApp rather than publish a number that goes stale. Send the sizes and total metres — a bill of quantities is fine as a photo — with your city: Punjab in 1–2 days, rest of Pakistan in 2–4.

Frequently asked

What is the 3 phase cable size for 30kW at 415 V?
16 mm² four-core copper on a hot, grouped run. 30,000 W divided by 611 is 49 A. The 30°C clipped-direct rating of 10 mm² is 57 A, but correction factors multiplying to 0.80 for ambient and grouping cut that to 45.6 A, under the load. 16 mm² is 76 A, or 60.8 A derated, and it also keeps a 60 m run inside a 2.5 percent voltage drop budget.
415V par 3 phase cable ka size kaise nikalte hain?
Load ko watt mein le kar 611 se taqseem karein. Yeh 1.732 × 415 × 0.85 hai, yaani three-phase volts aur power factor 0.85. 30 kW ka matlab 49 amp. Phir chart se woh size lein jiska rating garmi aur grouping ke factor lagane ke baad bhi current se ooper rahe. 100 meter se lambi run par size voltage drop tay karta hai, current nahi.
Do I have to derate the cable for 45°C when the chart says 30°C?
Yes. Every figure on this page is a 30°C clipped-direct rating. A hotter ambient and a shared tray each cut it, and the two factors multiply together. Work it as base × factor = result, so 57 A × 0.80 = 45.6 A. Take the exact factors for your ambient, insulation and grouping from BS 7671. We do not publish a factor table, because the right one depends on your installation.
How much voltage drop is allowed on a 200 metre factory feeder?
Pick the budget first. 5 percent of 415 V is 20.8 V, and a main feeder is commonly held tighter, to 2.5 percent or 10.4 V. At 80 A over 200 m a 35 mm² cable drops 1.1 × 80 × 200 ÷ 1000 = 17.6 V, while 70 mm² drops 8.8 V. On a 2.5 percent budget that feeder is 70 mm², two sizes above what the current alone would have allowed.
Is 4 core cable always needed for a three-phase run?
Four cores where you need three lines and a neutral, or three lines and an earth. On a balanced three-phase load with no neutral, which covers most motors, a three-core cable with a separate earth conductor is normal practice. Either way read the three-loaded-conductor column: it is the number of current-carrying cores that sets the rating, not the number of cores in the sheath.
Copper or aluminium for a factory submain?
Copper on short, heavily loaded runs and anywhere the terminations are tight. Aluminium where the run is long and the cost per metre decides the job. An aluminium conductor carries less current than copper of the same cross-section, so the aluminium size steps up for the same load, and the per-size figures are on the aluminium cable page. Terminate aluminium only with lugs rated for it.

Send the load, get the size and the rate

Tell us the connected load in kW, the run length, and how the cable is installed — tray, conduit, buried. We match it to a size and quote the day's factory rate. A bill of quantities gets a line-item answer.

WhatsApp about 3-phase cable