PILONE · 25MM² · 3 CORE · 450/750 V · CU CLASS 2

25mm 3 Core Standard Cable

4.8/5 · 127 buyer ratings

PILONE CABLES TECHNICAL TEAM

Three 25 mm² class 2 copper conductors, 7 strands of 2.14 mm per core, PVC insulated and sheathed to 450/750 V. 96 A with three loaded conductors on reference method C, 0.727 Ω/km, 1.75 mV/A/m — about 66 kVA on a 400 V three-phase supply. This is the three-phase feeder that carries no neutral: starter panel to tubewell motor, compressor or lift machine room. About 60 kg of copper in a 90 m coil. Drawn on the Pilone line in Lahore.

Factory-direct price
Contact for quote
In stock
Message us for today’s rate
WhatsApp for today's rate

Prices track the daily copper rate. Bulk and coil pricing on request.

Check the coil before you pay for it

Every coil leaves our factory with a QR code printed on the packaging. Scan it and the factory record for that batch opens: brand, cable size, batch number, year of manufacture and conductor. Compare the batch number on screen with the one printed on your coil — if the two do not match, it did not come from us.

Specifications

Resistance per IEC 60228. Current capacity and voltage drop per BS 7671, installation method C (clipped direct), 30°C ambient, 3 loaded conductors. Verify sizing with a licensed electrician for your installation.
PropertyValue
ConductorPlain annealed copper, class 2 stranded
Nominal area25 mm² × 3 cores
Strand construction7 / 2.14 mm per core (typical)
Max conductor resistance at 20°C0.727 Ω/km
Current capacity (method C, 3 loaded)96 A
Voltage drop1.75 mV/A/m
Voltage rating450/750 V
Insulation / sheathPVC / PVC, 70°C conductor rating
Conductor copper weight≈ 666.9 kg/km (3 × 222 kg/km)
Reference standardsIEC 60228 (conductors), IEC 60227 (PVC cables)

Where this cable belongs

Tubewell and pump starters

Starter panel to a three-phase tubewell or booster motor. The motor takes three phases and an earth at the frame — no neutral goes down the run.

Machine and compressor feeders

Fixed supply to a workshop lathe, an air compressor or a textile machine drawing up to the 96 A this cable carries.

Balanced three-phase submains

Panel to panel where every circuit downstream is three-phase, so the neutral has nothing to return and can be left out.

The buyer for this build is almost always doing one job: getting three phases to a motor. A tubewell contractor, a factory maintenance electrician, a lift installer. Three core at 25 mm² carries the three phases and nothing else — the earth goes to the frame separately, which is normal practice on motor work and is why the 4-core version would just be a spare conductor sitting in the sheath. Where the load downstream is a mix of single-phase circuits, the neutral has to be there and the right cable is 25mm 4 core cable. For a single-phase incomer, 25mm 2 core standard cable at 112 A. One step down in the same three-core build is 16mm 3 core cable at 76 A, and the sizing question in general is worked through on the three-phase cable size page.

Worked example — a 70 A motor 45 m from the starter.

Voltage drop is current × length × the tabulated 1.75 mV/A/m, divided by 1000. So 70 × 45 × 1.75 ÷ 1000 = 5.5 V, which is 1.4% of 400 V — well inside the 5% BS 7671 allows on a power circuit, 20 V here. Load the same cable to its full 96 A and the 20 V budget is spent at 20 ÷ (96 × 1.75 ÷ 1000) = 119 m. Beyond that the run length picks the size, not the motor — check yours with the voltage drop calculator.

Current capacity depends on how the cable is installed. Derate for conduit, grouping, and high ambient temperature. Have a licensed electrician confirm the size for your load and run length — or start with the cable size calculator.

What buyers say

5/5

“Excellent quality copper cables. Fast delivery across Pakistan. Highly recommended for electrical projects.”

AHMAD HASSAN

5/5

“Best cable manufacturer in Lahore. 99.9% pure copper as promised. Very satisfied with the product quality.”

MUHAMMAD ALI

5/5

“Good quality cables at competitive prices. Delivery was quick to Karachi. Will order again.”

IMRAN KHAN

Frequently asked

What is the price of 25mm 3 core cable in Pakistan?
The price changes with the daily copper rate. We sell factory-direct from Lahore, below dealer rates. Message us on WhatsApp for today's price per meter.
What is 25mm 3 core cable used for?
3-phase power without a neutral: motor feeders, submains to distribution boards, and industrial machine supply. Rated around 96 A clipped direct.
Do I need 4 core instead?
Use 3-core when the supply is 3-phase without a neutral, such as most motor and machine feeders. Choose 4-core when the circuit needs a neutral conductor as well.
How many amps does 25mm 3 core cable carry?
96 A with three loaded conductors, clipped direct at 30°C ambient, per BS 7671 reference method C. On a 400 V three-phase supply that is about 66 kVA (1.732 × 400 × 96 ÷ 1000). Pulled through conduit, bunched with other circuits, or run in summer heat it carries less — the tabulated figure is multiplied by the correction factor for your installation.
Is 25mm the same as 2.5mm?
No, and the mix-up is a safety problem. 25 mm² is a three-phase feeder conductor at 96 A. 2.5 mm² is appliance and lighting size, 27 A on two loaded conductors, with a tenth of the copper. Say the decimal out loud when you order — the two names sound alike across a counter. If you want the small one with an earth core, see 2.5mm 3 core flexible cable.