Skip to content
Factory-direct from Lahore · Nationwide delivery in 2–4 days +92 319 4262451 WhatsApp

How much wire does a 7 marla house need?

PILONE CABLES TECHNICAL TEAM

About 29 coils — 14 of 1.5 mm², 12 of 2.5 mm² and 3 of 4 mm² — which is roughly 2,520 m of single-core copper, plus about 82 ft of 16 mm² main cable from the meter to the distribution board.

That is a single-storey 7 marla house wired to 60 points on 14 circuits, pulled through conduit, with 15% cut in for wastage. Double storey takes about 53 coils. A coil is 90 m — the length the trade sells house wire in.

The 7 marla number, in coils and in metres

A single-storey 7 marla house of about 1,300 sq ft covered area, wired to 60 points on 14 circuits, needs roughly 2,520 m of single-core copper conductor: 1,196 m of 1.5 mm² for lights and fans, 1,042 m of 2.5 mm² for socket, kitchen and pump circuits, 259 m of 4 mm² for three AC points and two geysers, and about 25 m of 6 mm² for the main earth. In 90 m coils that is 14 + 12 + 3 = 29 coils. Those figures carry a 15% wastage margin and assume a centrally placed distribution board, conduit routing and one floor.

The technical world quotes house wiring in metres. Every shop in Pakistan sells it in coils. One standard coil of single-core building wire is 90 m, near enough 100 yards, so the conversion at the counter is metres ÷ 90, rounded up per size.

There is no dedicated 7 marla wiring list published anywhere we could find. Search it and you get 5 marla pages and house-plan drawings. The gap between the two plots is not small: a 7 marla house takes about 8 more coils than a 5 marla and needs a heavier cable from the meter.

How the 29 coils are worked out

Three inputs, multiplied. Change any of them for your own house and the answer moves with you.

1. Count the points

60 on a single-storey 7 marla plan: 32 light and fan points, 22 socket points, 3 AC points, 2 geysers, 1 pump. Count yours off the approved layout.

2. Set the average run

13 m per point: its share of the circuit run back to the DB, plus the ceiling rise and the switch drop. A 1,300 sq ft floor is roughly 30 × 43 ft, so the far corner is a long way from a central board.

3. Count conductors per run

2.5 for lighting and fan circuits, where switch legs share neutrals; 3 for socket and appliance circuits, which each carry live, neutral and earth.

Lighting and fans: 32 × 13 × 2.5 = 1,040 m. Sockets and kitchen: 22 × 13 × 3 = 858 m. Pump, on a 16 m run: 1 × 16 × 3 = 48 m, giving 906 m of 2.5 mm². Three ACs and two geysers on 15 m runs: 5 × 15 × 3 = 225 m of 4 mm². Main earth: 22 m. Raw total 2,193 m. Add 15%: 2,193 × 1.15 = 2,522 m. Divide by 90 and round up per size: 29 coils.

Cross-check against the trade rule of 1.5–2 ft of conduit run per sq ft of plot. At 1,575 sq ft that is 720–960 m of runs, and at 2–3 conductors per run, 1,440–2,880 m of conductor. 2,522 m sits inside it. The method itself is on how much cable a house needs.

7 marla house wiring cable list

Planning quantities for a single-storey 7 marla house, 1,300 sq ft covered, 60 points, conduit wiring, 15% wastage included. Coils at 90 m, rounded up per size. A planning band, not a bill — count your own points off the approved layout.
CircuitSize (strand code)Conductor metresCoils
Lighting and fan circuits1.5 mm² (3/.029)1,196 m14
Socket, kitchen and pump circuits2.5 mm² (7/.029)1,042 m12
3 AC points, 2 geyser points4 mm² (7/.036)259 m3
Main earth conductor6 mm² (7/.044)25 mcut length
Meter to DB main cable16 mm² 2 core (7/.064)25 m / 82 ftcut length

Where the 60 points sit

A 7 marla plot is 1,575 sq ft. After setback, stairs and porch you build about 1,300 sq ft per floor — typically three bedrooms, a drawing room, a lounge, a kitchen and two or three bathrooms.

A typical single-storey 7 marla point schedule. The point count drives the coil list, the circuit count and the size of the distribution board.
RoomLight and fanSocketAppliance
Bedroom 1531 AC
Bedroom 2431 AC
Bedroom 3431 AC
Drawing room53
Lounge64
Kitchen34
3 bathrooms32 geysers
Porch, stairs, outside221 pump
Total32226

Turning 60 points into a distribution board

Coils are only half the planning. The other half is how many ways the board needs, and that is a count you can do exactly rather than guess. Points do not map one-to-one to ways — they group into circuits, and each circuit takes one way.

Three grouping rules cover a house: about 10 light and fan points per lighting circuit; about 8 socket points per socket circuit; and one dedicated way each for anything that draws heavily or must not trip the rest of the house.

Circuit schedule for the 60-point 7 marla schedule above, at roughly 10 light points and 8 socket points per circuit. Spare ways at 20% so the board can absorb a future circuit without being replaced.
CircuitServesCableBreakerWays
Lighting and fans32 points1.5 mm²6 A4
General sockets18 points2.5 mm²16 A3
Kitchen4 points2.5 mm²20 A1
AC points3 points, one way each4 mm²20 A3
Geysers2 points, one way each4 mm²25 A2
Water pump1 point2.5 mm²16 A1
Circuits used14
Spare at 20%Future AC, a new bathroom, solar3
Board size17 ways needed, next stocked size up18 way

Boards are stocked in 4, 6, 8, 12, 18, 24 and 36 ways, so 17 rounds up to an 18-way. Do not buy the 12-way because the circuits fit: it fits today, and the first thing you add lands on a shared MCB. The spare ways are the cheapest part of the installation and the only part that cannot be added without opening the wall the board sits in.

Three ACs is also the point where a 7 marla house starts pressing on a single-phase connection. Three 1.5 ton units running together are roughly 21–27 A before anything else is switched on. That is still comfortable on a 10 kW connection, but a fourth AC or an instant geyser is the conversation where three-phase starts to make sense.

Single storey vs double storey

The upper floor carries about 85% of the ground floor's points — no porch, no main entrance, no pump — and adds a riser from the ground board to a second board upstairs.

Same plot, same point density, one extra floor. Second-floor quantities derived as 0.85 of the ground floor plus the riser; coils rounded up per size.
ItemSingle storeyDouble storey
Points60111
1.5 mm² coils1425
2.5 mm² coils1222
4 mm² coils36
Total coils2953
Conductor metres2,522 m4,666 m
Boards1 × 18 way1 × 18 way + 1 × 18 way
Riser to upper board16 mm², about 14 m

Meter to DB: the cable the lists leave out

The coil list wires the house. It does not feed it. The run from the WAPDA or K-Electric meter to your distribution board is a separate two-core cable, and it is the line missing from almost every plot-size wiring list published.

Assume a 10 kW sanctioned load, typical for a 7 marla domestic connection — read the real figure off your meter card. At 220 V single phase that is 10,000 ÷ 220 = 45.5 A. Over a 25 m (82 ft) run, 10 mm² copper carries 63 A and drops 45.5 × 25 × 4.4 ÷ 1000 = 5.00 V, inside the 11 V that 5% of 220 V allows. So 10 mm² passes. Run 16 mm²: it carries 85 A, drops 3.18 V, and holds when the third AC and the second geyser are both on. The sizing rationale in full is on WAPDA meter cable size; the same run in aluminium is a size up, and is on 16mm 2 core aluminium cable.

3/29, 7/29 and what they actually measure

Ask for 1.5 mm² at a shop in Pakistan and you will be handed 3/.029. The strand code is the trade's real vocabulary and it is imperial: 3 strands of 0.029 inch. The two systems do not line up exactly, and the gap matters on the first two rows.

Strand code to true conductor area. Area = strands × π/4 × strand diameter², with 0.029 in = 0.7366 mm. The metric column is the size the code is sold as, not an exact equivalent.
Strand codeTrue areaSold asUsual job
3/.0291.29 mm²1.5 mm²Lights, fans
7/.0293.0 mm²2.5–3 mm²Sockets, kitchen
7/.0364.6 mm²4 mm²AC, geyser
7/.0446.9 mm²6 mm²Earth, submains
7/.0529.6 mm²10 mm²Meter to DB
7/.06414.5 mm²16 mm²Heavy service run

3/.029 measures 1.29 mm², under a true 1.5 mm², so keep it on 6 A lighting circuits and off sockets. 7/.029 measures 3.0 mm², over a true 2.5 mm², which is why it is the socket wire here. How to verify a delivered coil against these numbers is set out on the 5 marla wiring page.

Current capacity, circuit by circuit

Copper conductors, PVC insulated, 450/750 V. Current capacity and voltage drop per BS 7671 (IEC 60364-5-52), installation reference method C (clipped direct), 30°C ambient; conductor resistance per IEC 60228. Wire pulled through conduit and bunched in a Lahore summer carries less than this — derate it. Verify sizing with a licensed electrician for your installation.
CircuitSizeCapacityVoltage dropBreaker
Lighting, fans1.5 mm²19.5 A29 mV/A/m6 A
Sockets, kitchen, pump2.5 mm²27 A18 mV/A/m16 A
AC points, geysers4 mm²36 A11 mV/A/m20–25 A
Main earth6 mm²46 A7.3 mV/A/m
Meter to DB16 mm²85 A2.8 mV/A/m63 A

Sizing one circuit rather than a whole house? The selection chart is on single-phase cable size, and long runs are settled by the voltage drop calculator.

7 marla house wiring cost: what the number covers

Published totals for wiring one size of house differ by several times over, and the reason is scope, not the house. One quote is the wire alone; the next adds conduit, boards and accessories; the third adds the electrician. Find out which before you compare two numbers.

The three scopes a 7 marla wiring cost can mean. We quote scope A at the day's copper rate; B and C are bought elsewhere and are listed so you can read any quote correctly.
ScopeWhat is in itWho supplies it
A. Wire and cable onlyThe 29 coils, the 6 mm² earth conductor, the 16 mm² meter-to-DB main cablePilone Cables, factory-direct
B. A plus fittingsConduit pipe, back boxes, switches, sockets, the 18-way board and its MCBs, earth electrodeElectrical store
C. B plus labourChasing walls, laying conduit, pulling wire, terminating, testing, making good the plasterYour electrician or contractor

Scope A is the only one we price, and we price it at the day's copper rate because copper is what moves it. Per-point and per-square-foot labour rates sit on cable installation cost. Send the coil list on WhatsApp and scope A comes back as one figure for your city.

These are planning quantities worked from a stated point count, run length and conductor count — not a certified load calculation. Current capacities assume method C at 30°C; derate for conduit, bunching and summer ambient. Confirm the point schedule, circuit count and every cable size with a licensed electrician against your approved layout, or start with the cable size calculator.

Frequently asked

7 marla ghar ki wiring mein kitna wire lagta hai?
About 29 coils for a single storey: 14 coils of 1.5 mm² (3/.029), 12 of 2.5 mm² (7/.029) and 3 of 4 mm² (7/.036), roughly 2,520 m of conductor. Double storey takes about 53 coils. Add 25 m of 6 mm² earth wire and about 82 ft of main cable from the meter.
One coil kitne meter ka hota hai?
A standard coil of single-core house wire in Pakistan is 90 m, close to 100 yards. Every quantity on this page converts through it: metres divided by 90, rounded up per size. Confirm the coil length in writing before you order, from us or anyone else, because it is the figure that quietly varies.
Is the 7 marla house wiring cost only the wire, or does it include fittings and labour?
Three different scopes go by that name: wire and cable only; that plus conduit, switches, sockets and the DB; or all of it plus the electrician's labour. This page quantifies the first, which is the only one we supply. Ask any quote which scope it covers before comparing it with another.
7 marla mein kitne points hotay hain?
About 60 on a single storey: 32 light and fan points, 22 socket points, 3 AC points, 2 geysers and a pump, across three bedrooms, a drawing room, a lounge, a kitchen and three bathrooms. Your layout will move that, and the point count is what drives the coil list.
DB box kitne way ka lena chahiye?
Those 60 points group into 14 circuits: 4 lighting, 3 socket, 1 kitchen, 3 AC, 2 geyser, 1 pump. Add 20% spare and you need 17 ways, so an 18-way board. Do not buy the 12-way because the circuits fit today — the first thing you add will land on a shared MCB.
Meter se DB tak konsi cable jaye gi?
On a 10 kW single-phase connection the load is 45.5 A, so 10 mm² two-core copper passes on both current and voltage drop over a 25 m run. Run 16 mm² instead: 85 A capacity, 3.18 V drop, and headroom for the third AC. Check your sanctioned load on the meter card first.
Double storey mein kitna extra wire lagega?
About 24 more coils, taking a 7 marla from 29 to roughly 53. The upper floor carries about 85% of the ground floor's points and adds a 16 mm² riser of about 14 m to a second 18-way board. Lay the riser conduit before you plaster, even if the floor is years away.

The wire for this list

Coil of 3/.029 single-core PVC-insulated copper house wiring cable
3/.029 · 1.29 MM² · SINGLE CORE · 450/750 V

3/.029 Single Core Copper Cable

The longest line on a 7 marla list at 14 coils. Stranded copper, PVC insulated, 450/750 V, drawn on the Pilone line in Lahore for lighting and fan circuits.

Factory-direct price
Contact for quote
Message us for today’s rate
Send the coil list

Prices track the daily copper rate. Send the coil list and your city for today's factory rate on the whole lot.

Also on this list: 7/.029 single core copper cable, 4mm single core copper cable, 6mm single core copper cable for the earth, and 16mm 2 core cable for the meter run.

Twenty-nine coils, one factory rate

We draw the copper in Lahore and sell it at the day's rate — no dealer margin. Send the coil list and your city for today's number: Punjab in 1–2 days, rest of Pakistan in 2–4.

Send the coil list and your city