Skip to content
Factory-direct from Lahore · Nationwide delivery in 2–4 days +92 319 4262451 WhatsApp

Kitchen wiring cable size: which wire for which point

PILONE CABLES TECHNICAL TEAM

Worktop sockets on 2.5 mm² — the wire the shop calls 7/.029 — on their own 16 A MCB. Lights and the exhaust fan on 1.5 mm² (3/.029) on 6 A. Anything over about 3 kW — and every AC point, whatever its wattage — gets its own 4 mm² (7/.036) circuit.

The kitchen is the only room where three or four heating appliances can switch on in the same minute, so it is sized as its own circuit group rather than as part of the house socket ring, and the whole group sits behind a 30 mA RCD — it is a wet-hand room with earthed metal in it.

The kitchen point wire, point by point

In a Pakistani kitchen on a 220 V single-phase supply, 2.5 mm² copper carries the general worktop socket circuit at 16 A, 1.5 mm² carries lighting and the exhaust fan at 6 A, and any single appliance that draws more than about 3 kW — a full-size electric oven, an instant geyser, a kitchen AC — is taken back to the distribution board on its own 4 mm² circuit rather than spurred off the sockets. That holds for a run in conduit at normal wall lengths; past about 20 m the socket circuit is decided by voltage drop instead, which is worked out further down.

Copper conductors, PVC insulated, 450/750 V. Current capacity and voltage drop per BS 7671, reference method C (clipped direct), 30°C ambient; conductor and stranding data per IEC 60228. Wattages are typical — read your own rating plate. Wire pulled through conduit and bunched carries less than the table figure; derate it. Verify sizing with a licensed electrician for your installation.
Kitchen pointTypical loadCable (strand code)CapacityMCB
Ceiling and under-cabinet lights10–100 W each1.5 mm² (3/.029)19.5 A6 A
Exhaust fan, chimney hood30–250 W1.5 mm² (3/.029)19.5 A6 A
Worktop sockets (kettle, microwave, toaster)700–2000 W each2.5 mm² (7/.029)27 A16 A
Refrigerator socket100–250 W running2.5 mm² (7/.029)27 A16 A
Washing machine point500–2000 W2.5 mm² (7/.029)27 A16 A
Electric oven up to 3 kW2000–3000 W2.5 mm² (7/.029)27 A16 A, dedicated
Oven and hob together, or over 3 kW3000–5000 W4 mm² (7/.036)36 A20 A, dedicated
Instant geyser at the sink3000–4500 W4 mm² (7/.036)36 A25 A, dedicated
Kitchen AC point1500–1800 W4 mm² (7/.036)36 A20 A, dedicated
Earth conductor to the kitchen6 mm² (7/.044)46 A

The single-core wire for those rows is what we draw: 3/.029 single core copper cable for the lights, 7/.029 single core copper cable for the sockets, 4mm single core copper cable for the dedicated circuits and 6mm single core copper cable for the earth.

Why the kettle decides the circuit

A kitchen is not a heavy room on paper. It is a heavy room for ninety seconds at a time, and that is what trips breakers. Take three ordinary appliances on the same worktop, at the top of their typical bands: an electric kettle at 2000 W, a microwave at 1200 W and a toaster at 800 W.

4000 W ÷ 220 V = 18.2 A. The 2.5 mm² cable is fine — it is rated 27 A, and even if the correction factors for conduit, bunching and a Lahore summer multiply out to 0.75 it still carries 27 × 0.75 = 20.3 A. The 16 A MCB is what gives up. That is the correct outcome, not a fault: the breaker is protecting a cable that is doing its job.

So a kitchen with a real appliance load gets two socket circuits, worktop split left and right, rather than one bigger cable. Two 16 A circuits on 2.5 mm² beat one 32 A circuit on 6 mm², because a tripped kettle does not take the fridge down with it. Keep the fridge on the circuit that has nothing else switching on it.

How far the kitchen is from the board

Heat sets the size on short runs, length sets it on long ones. 2.5 mm² drops 18 mV per amp per metre. Hold the whole installation to 3% of 220 V — 6.6 V — and give a final circuit about half of that, 3.3 V, because the run from the meter to the board has already spent the rest.

At the full 16 A the sum is 3.3 ÷ (18 × 16 ÷ 1000) = 11.5 m, which sounds alarming until you notice that a kitchen almost never sits at 16 A. At a realistic steady 8 A the same circuit reaches 3.3 ÷ (18 × 8 ÷ 1000) = 23 m. Between those two numbers is the honest answer: measure the route from the distribution board to the far socket, and if it is over about 20 m take the socket circuit up to 4 mm², which drops 11 mV/A/m instead of 18. Your own length goes into the voltage drop calculator.

How much wire one kitchen takes

Thirteen points is a full kitchen: three lights, an exhaust fan, six worktop and appliance sockets, a fridge socket, an oven point and an instant geyser point. Multiply points by the average run back to the board, then by the number of conductors each run carries.

Count the points

13 in the kitchen above. Count yours off the approved layout — a kitchen with a hob, a hood and a dishwasher runs to 16.

Set the average run

12 m per point: the share of the circuit run back to the board, plus the ceiling rise and the switch drop.

Count the conductors

2.5 per lighting run, where switch legs share a neutral; 3 per socket and appliance run, which each carry live, neutral and earth.

Lights and exhaust: 4 × 12 × 2.5 = 120 m of 1.5 mm². Sockets and fridge: 7 × 12 × 3 = 252 m of 2.5 mm². Oven and geyser: 2 × 12 × 3 = 72 m of 4 mm². Add 15% for cutting waste and failed pulls and it is 138 m, 290 m and 83 m — at 90 m to a coil, 2 coils, 4 coils and 1 coil. That is one room's share of a house list, not an addition to it; the whole-house method is on how much cable a house needs and a worked plot total is on 5 marla house wiring.

Wiring the kitchen circuits

Current capacity depends on how the cable is installed. Derate for conduit, bunching and ambient above 30°C, and take the correction factors for your method from BS 7671. Have a licensed electrician confirm the point count, the circuit split and every cable size for your kitchen before you buy — or start with the cable size calculator.

Frequently asked

Kitchen ke sockets ke liye konsa wire?
2.5 mm², jise dukaan par 7/.029 kehte hain, apne alag 16 A MCB par. Lights aur exhaust fan ke liye 1.5 mm² (3/.029) 6 A par kaafi hai. Oven, instant geyser ya kitchen AC — jo 3 kW se upar ho — unke liye alag 4 mm² (7/.036) circuit seedha DB se laayein.
Is 1.5mm enough for kitchen sockets?
No. 1.5 mm² is rated 19.5 A clipped direct, and after derating for conduit and summer heat it has little left over a 16 A socket breaker. It also drops 29 mV per amp per metre against 18 for 2.5 mm², so a long kitchen run loses noticeably more voltage. Keep 1.5 mm² on the 6 A lighting circuit.
What size cable for an electric oven in a kitchen?
Read the rating plate first. An oven up to 3000 W draws 3000 ÷ 220 = 13.6 A and runs on 2.5 mm² on its own 16 A MCB. An oven with a hob, or anything above 3 kW, goes on 4 mm² on a 20 A MCB. The full working is on the oven cable size guide.
Can the fridge share the kitchen socket circuit?
Electrically yes — a fridge draws 100–250 W running. Practically, give it the circuit that has nothing else switching on it, or its own socket on the second socket circuit. The fridge is the one load in the house you do not want tripped by a kettle while you are out.
Do kitchen sockets need an RCD?
Yes. A kitchen is a wet-hand room full of earthed metal appliance bodies, so the socket circuits belong behind a 30 mA residual current device. The RCD protects people; the MCB protects the cable. They are not alternatives to each other, and neither one substitutes for a proper earth at every point.
Kitchen mein kitne points hotay hain?
Aam tor par 8 se 15. Is page ki list mein 13 hain: 3 lights, 1 exhaust fan, 6 worktop sockets, 1 fridge socket, 1 oven point aur 1 instant geyser point. Hob, chimney aur dishwasher milaa kar 16 tak chala jata hai. Apni approved layout se ginti karein.
How many metres of wire for a kitchen?
For the 13-point kitchen above, about 138 m of 1.5 mm², 290 m of 2.5 mm² and 83 m of 4 mm² with 15% wastage included — 2, 4 and 1 coils at 90 m each. That is 13 points at a 12 m average run and 2.5 to 3 conductors per run. It is a share of the house total, not an extra.

The cable for this job

The sheathed sizes above suit an appliance tail and a surface run. Wiring in conduit is pulled as single core: 7/.029 copper cable price for the sockets, 3/.029 copper cable for the lights, and 4mm 3 core standard cable where the oven or geyser point needs its own earthed run.

Kitchen wiring cable, factory-direct

We draw the copper in Lahore and sell it at the day's rate — no dealer margin. Send the coil list and your city for today's number: Punjab in 1–2 days, rest of Pakistan in 2–4.

Send the coil list and your city