4 mm² copper on a 25 A MCB for a 4.5 kW instant geyser. 2.5 mm² on a 20 A MCB if the unit is 3 kW.
An instant geyser has no tank to heat slowly, so it puts its whole element on the circuit the moment the tap opens: 4500 W is 20.5 A at 220 V, 3000 W is 13.6 A. 4 mm² carries 36 A clipped direct at 30°C and 2.5 mm² carries 27 A, both measured before derating. The number on the rating plate is what decides between them — not the word "instant".
Instant and tankless units sold in Pakistan run from about 2000 W on a single-tap kitchen heater to 6 kW on a multi-point unit feeding a shower and a basin. That is a threefold spread in current, which is why one answer cannot cover the category. Read the marking on the unit, then read the row.
| Marked on the unit | Current at 220 V | Cable (copper) | MCB |
|---|---|---|---|
| 2000 W single-tap instant | 9.1 A | 2.5 mm² (7/.029) | 16 A |
| 3000 W / 3 kW instant | 13.6 A | 2.5 mm² (7/.029) | 20 A |
| 4500 W / 4.5 kW instant | 20.5 A | 4 mm² (7/.036) | 25 A |
| 6 kW multi-point instant | 27.3 A | 6 mm² (7/.044) | 32 A |
| Power selector set below the maximum | Size for the maximum | Size for the maximum | Size for the maximum |
An instant geyser in Pakistan takes its cable from the element rating on the plate, not from the type of unit: 3000 W draws 13.6 A at 220 V and runs on 2.5 mm² copper with a 20 A MCB, 4500 W draws 20.5 A and needs 4 mm² with a 25 A MCB, and a 6 kW multi-point unit draws 27.3 A and needs 6 mm² with a 32 A MCB. Those capacities assume copper clipped direct at 30°C ambient with two loaded conductors, per BS 7671 reference method C; a cable bunched in conduit through a hot roof void carries less and moves each row up a size.
The last row is the one that catches people. Several instant units carry a power selector or watt-lock switch that caps the draw at a lower figure, and it is tempting to size the circuit around the setting rather than the element. Do not. Anyone in the house can move that switch, and the day it goes back to maximum the cable and the breaker have to hold the full rating.
Both are resistive loads, but they sit at opposite ends of the wattage range. A storage tank has minutes to bring a full load of water up to temperature, so a 2 kW element drawing 9.1 A does the job. An instant unit has to raise the temperature of water while it flows, in seconds, and it buys that with wattage. That is why the same word has two correct answers: a 2 kW storage geyser and a 4.5 kW instant geyser are 9.1 A and 20.5 A, one cable size apart and two MCB ratings apart. The full wattage chart, the 2.5 mm² against 4 mm² argument and the derating arithmetic are on the geyser wire size chart; tank sizes in gallons are in the storage geyser wiring guide.
Instant geysers sold here advertise a built-in ELCB, usually a module moulded into the cord or the plug. It is worth having and it is not the same thing as protecting the circuit. A device sitting at the appliance watches what happens downstream of itself: the element, and the short piece of flex after it. The fixed cable running through the wall from the distribution board is upstream, and nothing in that moulded block is watching it.
So it does not replace a 30 mA RCCB at the board, and it certainly does not replace an earth. The protective conductor has to be continuous from the metal body of the geyser back to the board, which makes the point a three-core job — live, neutral and earth. Two-core cable has no earth conductor in it. Keep the MCB, the RCCB and the isolator outside the wet zone, as in the bathroom wiring guide.
The size for a 4.5 kW instant unit: live, neutral and earth in one sheath, 7/0.85 stranded copper, PVC insulated and sheathed, 450/750 V, rated 36 A clipped direct at 30°C. Fixed wiring for a wall-mounted instant geyser point, drawn on the Pilone line in Lahore.
Prices track the daily copper rate. Send the length and your city on WhatsApp for the exact figure.
A 6 kW multi-point unit takes 6mm 3 core cable. A 3 kW single-point unit on a clipped or plastered run takes 7/.029 copper cable pulled as singles with an earth. Also made in 4mm²: 4mm 2 core cable where a protective conductor is already run, and 4mm 3 core flexible cable for the tail off the isolator.
We draw the copper in Lahore and sell it at the day's rate — no dealer margin. Send the wattage off the rating plate, the length and your city: Punjab in 1–2 days, rest of Pakistan in 2–4.