Skip to content
Factory-direct from Lahore · Nationwide delivery in 2–4 days +92 319 4262451 WhatsApp

What size cable for an electric oven — and why it is not a plug-in job

PILONE CABLES TECHNICAL TEAM

4 mm² copper on its own 20 A MCB, hardwired — the size the trade calls 7/36.

A built-in electric oven draws 2000–3500 W, which is 9.1–15.9 A on Pakistan's 220 V supply, and it holds that current for an hour at a time. 4 mm² is rated 36 A clipped direct at 30°C, so it still clears a 20 A breaker after derating for conduit and a hot kitchen; only an oven at the 2000–2500 W end of the range drops to 2.5 mm² on a 16 A MCB. Run it 3-core so the earth is 4 mm² too, and terminate at a cooker connection unit, not a plug.

Why a continuous load gets sized differently

A kettle takes 2000 W for three minutes. An oven takes it for ninety. Nothing in the current figure changes, but everything downstream of it does: the cable sits at its working temperature the whole time, the conduit around it warms up, and there is no diversity to borrow — the oven is simply on.

For a built-in electric oven in Pakistan, run 4 mm² copper on a dedicated 20 A MCB: the oven draws 2000–3500 W, which is 2000 ÷ 220 = 9.1 A to 3500 ÷ 220 = 15.9 A, and 4 mm² is rated 36 A clipped direct at 30°C. 2.5 mm² carries the load on paper at 27 A, but apply a 0.75 correction for conduit and kitchen ambient and it becomes 20.3 A against a 20 A breaker — the margin is gone. 4 mm² becomes 27 A and keeps 7 A.

Circuit sheet for one built-in electric oven on a 220 V single-phase supply. Copper, PVC. Current capacity and voltage drop per BS 7671, reference method C (clipped direct), 30°C ambient, two loaded conductors; conductor and stranding data per IEC 60228. Check your own oven's rating plate first. Verify sizing with a licensed electrician for your installation.
ParameterValue
ApplianceBuilt-in electric or baking oven
Power, typical2000–3500 W
Running current at 220 V9.1–15.9 A
Breaker rating20 A MCB, dedicated
Live, neutral and earth4 mm² copper
Trade code7/.036
Capacity, 4 mm²36 A
Derated at 0.7527 A
TerminationCooker connection unit

The ladder, by what the plate says

The plate on the back of the oven, not the model name, sets the row. Find your wattage, read across, and take the breaker in the last column — the cable is chosen against the breaker, not against the oven.

Current = watts ÷ 220. Sizes and capacities per BS 7671 reference method C (clipped direct), 30°C ambient, copper, PVC, two loaded conductors; stranding per IEC 60228. Wattages are typical plate figures for domestic units — read your own. Verify sizing with a licensed electrician for your installation.
Oven ratingCurrent at 220 VCableTrade codeMCB
2000 W9.1 A2.5 mm²7/.02916 A
2500 W11.4 A2.5 mm²7/.02916 A
3000 W13.6 A4 mm²7/.03620 A
3500 W15.9 A4 mm²7/.03620 A
6000 W, oven + hob27.3 A6 mm²7/.04432 A

Length rarely decides this circuit, but check it anyway. Hold the installation to 3% of 220 V — 6.6 V — and give the final circuit half of it, 3.3 V, since the submain has spent the rest. A 3000 W oven at 13.6 A on an 18 m kitchen run drops 11 × 13.6 × 18 ÷ 1000 = 2.69 V on 4 mm², inside that 3.3 V. The same run in 2.5 mm² drops 18 × 13.6 × 18 ÷ 1000 = 4.41 V and is over it. The last row is a cooker circuit, not an oven circuit — that job is on the electric stove wire size guide.

Current capacity depends on how the cable is installed. Derate for conduit, grouping, and ambient temperature above 30°C, and take the correction factors for your own method out of BS 7671. Confirm your oven's nameplate rating and have a licensed electrician match the breaker to it — or start with the cable size calculator.

The cable for this job

Two-core standard cable with black outer sheath, cut back to show red and black insulated stranded copper conductors
4MM² · 2 CORE · 450/750 V · CU CLASS 2

4mm 2 Core Standard Cable

Class 2 stranded copper, 7/0.85, PVC insulated and sheathed, 450/750 V, drawn on the Pilone line in Lahore. Rated 36 A clipped direct at 30°C, 11 mV/A/m, 4.61 ohm/km.

Factory-direct price
Contact for quote
Message us for today’s rate
WhatsApp for today's rate

Cable is priced off the day's copper rate, so we quote per metre and per coil on WhatsApp rather than publish a figure that goes stale. Send the metres and your city.

For an oven point take the three-core version so the earth is 4 mm² too: 4mm 3 core cable for the chased run, or 4mm 3 core flexible cable for the tail into the cabinet. The two-core sizes — 4mm 2 core cable price, 4mm 2 core flexible cable — suit circuits with the earth run separately.

Frequently asked

Oven ke liye kitne mm ka wire chahiye?
4 mm² copper — trade code 7/.036 — apne alag 20 A MCB par, aur 3-core lein taake earth bhi 4 mm² ho. Built-in oven 2000 se 3500 W leta hai, yani 220 volt par 9.1 se 15.9 amp, aur yeh load ek ghanta lagataar chalta hai. Oven ko plug par nahi, cooker connection unit par hardwire karayen.
Is 2.5mm cable enough for an electric oven?
Only for the small end of the range. A 2000–2500 W oven draws 9.1–11.4 A and 2.5 mm² on a 16 A MCB carries it. At 3000–3500 W the breaker has to go to 20 A, and 2.5 mm² derated for conduit and kitchen heat at a 0.75 factor is 20.3 A — no margin left over the breaker at all. 4 mm² derates to 27 A and keeps 7 A.
Can the oven and the hob share one circuit?
Not on this cable. A built-in oven and a four-zone electric hob together can reach 6000 W, which is 27.3 A at 220 V — past 4 mm² on a 20 A breaker. That combination is a cooker circuit in 6 mm² on a 32 A MCB, and it is sized on the maker's figures for both units, not on a chart.
Does a built-in oven need a plug or a hardwired connection?
Hardwired. A 13 A plug and socket is at its limit before a 3500 W oven is, and the connection sits behind a cabinet where nobody can see it warming. Terminate the 4 mm² at a cooker connection unit with a switch, mounted beside the oven housing where the isolation is reachable without pulling the unit out.

4mm cable for the oven circuit, at the factory rate

We draw the copper in Lahore and sell it at the day's rate — no dealer margin, and the line that made the coil answers the message. Tell us the metres and your city: Punjab in 1–2 days, rest of Pakistan in 2–4.

WhatsApp for a quote