What size wire for a chest freezer in a store room or garage?

PILONE CABLES TECHNICAL TEAM

2.5 mm² copper — 7/.029 — 3 core, on its own 16 A MCB.

A chest freezer runs at 150–400 W, about 0.7–1.8 A at 220 V, so running current never decides this. Where the cabinet stands does. It sits in a store room, a garage or a covered veranda — hotter than the rest of the house — and is usually the furthest socket from the board. A store room in June sits well above the 30 °C the capacity table assumes, and it is heat, not distance, that eats the margin. 2.5 mm² still clears its 16 A breaker after derating; 1.5 mm² does not.

The circuit sheet for a store-room freezer point

For a chest freezer in Pakistan the point is 2.5 mm² copper, three core with the earth, on a dedicated 16 A MCB, and the size is chosen for the room rather than for the compressor: at 150–400 W the cabinet draws 0.7–1.8 A of the 27 A it carries clipped direct at 30 °C, but a store room in June is nowhere near 30 °C and the cable is usually in conduit. That is where the margin goes. Read the wattage off your own rating plate first.

Circuit sheet for one chest freezer, 220 V single phase. Wattage is a typical band — read your own rating plate. The 0.75 correction factor is an illustration, not a standard value: take the real factors for your method and ambient from BS 7671. Capacity per BS 7671 reference method C (clipped direct), 30 °C ambient; conductor data per IEC 60228. Verify sizing with a licensed electrician.
ParameterValue
ApplianceChest freezer, domestic or shop cabinet
Power, typical (running)150–400 W
Running current at 220 V0.7–1.8 A
DutyContinuous, 24 hours
Breaker16 A MCB, its own way
Cable2.5 mm² copper (7/.029)
Cores3 core — live, neutral, earth
Capacity at 30 °C27 A
Capacity if factors multiply to 0.7520.3 A — still above the 16 A MCB

The store room is the whole argument

Take a real job: a cabinet 28 m of cable route from the board, in a room well above 30 °C through a Punjab summer, cable in conduit chased into the wall. Start with the drop, because that is the number people expect to decide it. At the top of the band, 400 ÷ 220 = 1.8 A, so the 2.5 loses 18 × 1.8 × 28 ÷ 1000 = 0.91 V against 29 × 1.8 × 28 ÷ 1000 = 1.46 V on 1.5 mm². Both are inside any sensible budget. Voltage drop does not settle this one.

Derating does. Suppose the correction factors for conduit in a wall and a hot store room multiply out to 0.75: the 2.5 falls from 27 A to 20.3 A and the 1.5 from 19.5 A to 14.6 A. Against the 16 A MCB protecting a 13 A socket, the heavier size still clears it and the lighter one no longer does. Take the exact factors for your own method out of BS 7671 — the point is not the 0.75, it is that the derated figure, never the table figure, is what the breaker has to sit under. That is also why our refrigerator and freezer wire size guide answers 1.5 mm² and this page answers 2.5 mm²: a dedicated fridge point is a hard-wired way on a 10 A MCB, while a store-room freezer plugs into a 13 A socket outlet on a 16 A way, and the cable has to clear the bigger breaker after derating, not the appliance.

This is a continuous load in a hot, often damp room, so it wants a working earth, a socket nobody switches off by accident, and a dedicated way at the board. Derate for conduit, grouping and ambient above 30 °C, and have a licensed electrician confirm the size for your installation, or start with the cable size calculator.

The cable for this job

Take the three-core version so the earth is 2.5 mm² as well: 2.5mm 3 core flexible cable for a run to a socket behind the cabinet, or 2.5mm single core copper (7/.029) where the electrician pulls singles through conduit.

Flexible cable with the black outer sheath stripped back, showing a black and a red insulated core and the fine copper strands inside each
2.5MM² · CLASS 5 FLEX · CU

2.5mm Flexible Copper Cable

Class 5 flexible copper, 50/0.25 strands, PVC insulated and sheathed, drawn on the Pilone line in Lahore. Rated 27 A clipped direct at 30 °C, 18 mV/A/m on voltage drop.

Factory-direct price
Contact for quote
Message us for today’s rate
WhatsApp for today's rate

Cable is priced off the day's copper rate, so we quote per metre and per coil on WhatsApp. Send the size, the metres and your city.

Frequently asked

Chest freezer ke liye kitne mm ka wire chahiye?
2.5 mm² copper — trade code 7/.029 — 3 core, apne alag 16 A MCB par. Freezer khud sirf 0.7–1.8 A leta hai, magar wire ka size store room ki garmi aur board se doori dekh kar liya jata hai. Garam kamre aur conduit mein 1.5 mm² ka margin khatam ho jata hai, 2.5 mm² ka nahi.
Is 1.5mm enough for a chest freezer?
On the load alone, yes — 19.5 A against 1.8 A. After derating, no. In conduit in a hot store room, correction factors of about 0.75 bring 1.5 mm² down to 14.6 A, under the 16 A MCB protecting it, while the 2.5 falls to 20.3 A and still clears it. The cable has to outrank its breaker, not the appliance.
Can I run a chest freezer from an extension board in the next room?
It is the commonest bad fix and it fails in two ways. An extension flex is thin, it is often left coiled, and a coiled loaded cable cannot shed its heat. The board is also the first thing anyone unplugs to charge something. Run a proper point instead — the cable is cheaper than a freezer full of spoiled food.
Does a chest freezer need its own MCB?
Yes, and for availability rather than capacity. On its own 16 A way, nothing else on the board can trip the freezer off, and a fault in the freezer does not take the store-room lights with it. Use an unswitched socket or a switch out of casual reach so it cannot be turned off by mistake.

Wiring a dedicated freezer point?