4 mm² copper on a heavier single-phase cabinet at 220 V. On a 400 V three-phase unit, 4 mm² four-core.
This is the one appliance here where a chart cannot hand you the number. Display chillers, glass-door cabinets, walk-ins and condensing units run anything from a domestic-sized compressor to a three-phase machine, and the figure that sizes the cable is the full-load current on the plate. Find that first. 4 mm² is where most single cabinets land: 36 A on two loaded conductors, 32 A on three, clipped direct at 30 °C.
For a commercial freezer the cable is sized from the full-load current on the unit's rating plate, not from a wattage band, because the same words cover machines an order of magnitude apart: a 220 V single-phase glass-door cabinet and a 400 V three-phase condensing unit are both called a commercial freezer. Two things on the plate settle everything else — the supply voltage and phase count, which fix the core count, and the FLA, which fixes the size.
| What the plate says | Cores you need | Cable | Capacity |
|---|---|---|---|
| 220–240 V, 1 phase, FLA up to 16 A | 3 core | 2.5 mm² (7/.029) | 27 A |
| 220–240 V, 1 phase, FLA 16–25 A | 3 core | 4 mm² (7/.036) | 36 A |
| 380–415 V, 3 phase, FLA up to 25 A | 4 core | 4 mm² (7/.036) | 32 A |
| 380–415 V, 3 phase, FLA 25–35 A | 4 core | 6 mm² (7/.044) | 41 A |
| 380–415 V, 3 phase, FLA 35–50 A | 4 core | 10 mm² (7/.052) | 57 A |
Take a glass-door display freezer with 1200 W on the plate, 220 V single phase: 1200 ÷ 220 = 5.5 A running, and the plate's FLA will read higher, because the compressor's locked-rotor current is what the protection has to ride out. On its own 16 A way in 2.5 mm² that cabinet is inside every number. Now put three of them along one wall on one 16 A way, which is what happens when a shop grows a cabinet at a time: 3 × 5.5 = 16.5 A, over the breaker before a door has been opened.
Each cabinet is small; the row of them is not. What gives out is the shop's submain, not the freezer's tail, and the fix is a way each at the board and a submain sized for the total — the arithmetic in the commercial load calculation guide. Run 4 mm² where the cabinet is heavier than a domestic unit, where the board sits at the front of the shop and the freezer at the back, or where a bigger machine may replace it later. Where the plate says three phase, the run becomes four-core and the three-phase cable size rules take over.
Single-phase cabinet, three core so the earth matches: 4mm 3 core flexible cable for a tail behind the machine, or 4mm 3 core standard cable for a fixed run in conduit. Three-phase unit, four core: 4mm 4 core cable price, stepping up to 6mm 4 core cable where the plate's FLA passes 25 A.