Skip to content
Factory-direct from Lahore · Nationwide delivery in 2–4 days +92 319 4262451 WhatsApp
6mm 4 core standard cable with the sheath cut back, showing four PVC insulated cores and the stranded copper conductor inside each
PILONE · 6MM² · 4 CORE · 450/750 V · CU CLASS 2

6mm 4 Core Standard Cable

PILONE CABLES TECHNICAL TEAM

4.8/5 · 127 buyer ratings

41 A on three phases, 7/1.04 class 2 copper, 450/750 V. Four cores for 400 V feeders and motor runs, PVC insulated and sheathed, drawn on the Pilone line in Lahore.

Factory-direct price
Contact for quote
In stock
Message us for today’s rate
WhatsApp for today's rate

Quoted per metre at the day's copper rate. Send the length in metres and your city and the coil figure comes back with it.

Check the coil before you pay for it

Every coil leaves our factory with a QR code printed on the packaging. Scan it and the factory record for that batch opens: brand, cable size, batch number, year of manufacture and conductor. Compare the batch number on screen with the one printed on your coil — if the two do not match, it did not come from us.

41 A on three phases — roughly 22.7 kW at 400 V.

6mm² 4 core standard cable carries 41 A with three conductors loaded, clipped direct at 30°C. On a 400 V three-phase supply that is 41 × 400 × 1.732 = 28.4 kVA, about 22.7 kW once a 0.8 power factor is allowed for. It is the size for a small sub-board feeder or a pump motor, behind a breaker rated below 41 A. The rate is quoted per metre at the day's copper price.

Specifications

6mm² 4 core standard cable is rated 41 A with three loaded conductors on BS 7671 reference method C (clipped direct) at 30°C ambient; the same copper carries 46 A when only two conductors are loaded. Its conductors are class 2 stranded copper, seven strands of 1.04 mm each, resistance capped at 3.08 Ω/km by IEC 60228, voltage drop 7.3 mV per amp per metre. Derate all of it for conduit, grouping and ambient above 30°C, and have a licensed electrician confirm the size for the run.

Resistance per IEC 60228. Current capacity and voltage drop per BS 7671, installation reference method C (clipped direct), 30°C ambient. Three loaded conductors is the normal four-core case: three phases carrying current, neutral carrying only the imbalance. Copper weight is the conductor only, before insulation and sheath. Verify sizing with a licensed electrician for your installation.
PropertyValue
ConductorPlain annealed copper, class 2 stranded
Nominal area6 mm² × 4 cores
Strand construction7 / 1.04 mm per core
Market strand code7/.044 (computes to 6.87 mm²)
Max conductor resistance at 20°C3.08 Ω/km
Current capacity (method C, 3 loaded)41 A
Current capacity (method C, 2 loaded)46 A
Voltage drop7.3 mV/A/m
Voltage rating450/750 V
Insulation / sheathPVC / PVC, 70°C conductor rating
Conductor copper weight213 kg/km (4 × 53.3 kg/km)
Copper in a 90 m coil19.2 kg
Reference standardsIEC 60228 (conductors), IEC 60227 (PVC cables)

Long feeders fail on voltage drop before they fail on heat. Take it phase to neutral, which is the conservative way to do it by hand: a 30 A feeder run 40 m on 6mm² drops 30 × 40 × 7.3 ÷ 1000 = 8.8 V, against the 11 V that BS 7671's 5% allowance gives on a 220 V phase. Push the same feeder to 60 m and the drop is 13.1 V, over the line, and the answer is 10mm 4 core standard cable at 4.4 mV/A/m. Run your own numbers in the voltage drop calculator, or read the sizing rules on three-phase cable size.

What a coil holds, and what the rate is per

Two quotes for the same cable are not comparable until you know the unit. Shops in this market price per foot, per metre, and per coil, and coil is not a fixed quantity: 30 m, 45 m and 90 m packs are all sold, some sellers quote 301 ft, and some sell 80-yard lengths. The table below turns each pack into metres, feet, and the weight of copper inside it.

Conversions, not prices. Copper weight is the four conductors only, at 213 kg per km of cable, before PVC insulation, sheath and drum. Divide any coil quote by the length in metres to get the rate per metre; divide the per-metre rate by 3.281 for the rate per foot.
PackLengthIn feetCopper inside
Cut length1 m3.281 ft0.21 kg
Half coil45 m148 ft9.6 kg
Full coil90 m295 ft19.2 kg
301 ft coil91.7 m301 ft19.6 kg

Use it as a check you can run yourself. Copper weighs 8.89 kg per km for every mm², so 6 mm² across four cores is 24 × 8.89 = 213 kg per km, and 9% of a kilometre is a 90 m coil holding 19.2 kg of bare copper. A real coil weighs more than that once the PVC is counted; it should never weigh less. That is a method, not an accusation against any seller. More conversions on the price per metre page.

Where this cable belongs

Sub-distribution boards

Feeder from a main panel to a smaller board — three phases plus neutral in one sheath.

Motor and pump feeders

Three-phase pumps and small machines up to about 22.7 kW at 400 V and 0.8 power factor.

House and shop risers

Floor-to-floor distribution on trays and in trunking, where each floor takes a different phase.

41 A is the clipped-direct figure at 30°C with three conductors loaded. In conduit, bunched with other circuits, or in a Lahore summer, the cable carries less — BS 7671 applies an ambient correction factor and a grouping factor, and the usable current is the tabulated 41 A multiplied by both. Have a licensed electrician apply the factors for your installation and confirm the size for your load and run length, or start with the cable size calculator.

Turning 41 A into a load you can name

Buyers arrive with a kW figure from a machine plate, not an amp figure. Three steps convert one to the other on a 400 V three-phase supply.

1. Amps to kVA

41 A × 400 V × 1.732 = 28.4 kVA. The 1.732 is the root-three factor for three-phase.

2. Apply the power factor

28.4 kVA × 0.8 = 22.7 kW. Use the power factor printed on the motor plate, not 0.8, when you have it.

3. Leave the breaker room

The breaker sits below the cable: a 32 A three-phase MCB under a 41 A cable, not the other way round.

Work backwards for your own machine: divide the plate kW by 0.8 to get kVA, then by 1.732 × 400 to get amps. A 15 kW motor is 15 ÷ 0.8 = 18.75 kVA, and 18,750 ÷ (1.732 × 400) = 27 A — comfortably inside 6mm² before derating, and worth checking against the run length for voltage drop.

6mm² in 2, 3 and 4 core, and the sizes either side

Current capacity per BS 7671 reference method C (clipped direct), 30°C ambient, class 2 copper except where the flexible build is named. Three loaded conductors on the 4 core builds, two on the 2 and 3 core. Verify sizing with a licensed electrician for your installation.
CableCurrentWhere it goes
6mm 4 core standard cable (this page)41 AThree phases and neutral at 400 V
6mm 3 core standard cable46 ASingle phase with its own earth core
6mm 2 core standard cable46 ALine and neutral only, earth taken separately
4mm 4 core standard cable32 AOne size down: light three-phase runs
10mm 4 core standard cable57 AOne size up: longer feeders and bigger motors
6mm 4 core flexible cable41 AClass 5, for machine tails and portable panels

What buyers say

5/5

“Excellent quality copper cables. Fast delivery across Pakistan. Highly recommended for electrical projects.”

AHMAD HASSAN

5/5

“Best cable manufacturer in Lahore. 99.9% pure copper as promised. Very satisfied with the product quality.”

MUHAMMAD ALI

5/5

“Good quality cables at competitive prices. Delivery was quick to Karachi. Will order again.”

IMRAN KHAN

Frequently asked

What is the price of 6mm 4 core cable in Pakistan?
The rate follows the daily copper price, so it is quoted on the day. Ask for it per metre: a per-foot figure is 3.281 times smaller than the same rate per metre, and a coil figure means nothing until the coil length is stated. We quote factory-direct from the Lahore line, with no dealer margin.
What is 6mm 4 core cable used for?
Small 400 V three-phase work: a feeder from the main panel to a sub-distribution board, a motor feeder for a pump or a small machine, and floor-to-floor risers in houses and shops. It carries 41 A with three conductors loaded, clipped direct at 30°C, which is about 22.7 kW at 0.8 power factor.
How many kW will 6mm 4 core cable carry on three phase?
Work it from the amps. 41 A across 400 V three-phase is 41 × 400 × 1.732 = 28.4 kVA. At a power factor of 0.8, typical for motor load, that is about 22.7 kW. Check the power factor on the machine plate, and derate the 41 A for conduit, grouping and summer ambient.
What is the difference between 6mm 4 core and 6mm 3 core cable?
Core count follows the circuit, not the load. Four core carries three phases and a neutral, so three conductors are loaded and the rating drops to 41 A. Three core carries line, neutral and earth on single phase, so only two are loaded and the same copper is rated 46 A.
Do I need armoured cable instead?
Use armoured cable where the run goes underground, crosses open ground, or can be struck. For indoor runs on trays, in trunking, or clipped to a wall, standard 4 core is the normal choice and costs less. If the run is buried, the armour is not optional.