Skip to content
Factory-direct from Lahore · Nationwide delivery in 2–4 days +92 319 4262451 WhatsApp

What size wire for a refrigerator in Pakistan — and can the freezer share it?

PILONE CABLES TECHNICAL TEAM

1.5 mm² copper on a 10 A MCB — the wire the trade sells as 3/29.

A domestic fridge, freezer or deep freezer draws 100–400 W, which is 0.5–1.8 A on Pakistan's 220 V supply, and 1.5 mm² carries 19.5 A clipped direct at 30°C. That margin is not there for the running load, which is tiny. It is there for the compressor start, and for the fact that the cable is buried in a warm wall and shares a conduit.

The running load is not what the wire is sized for

A fridge is a small load that switches on and off all day. Between cycles it takes almost nothing; when the compressor kicks in, the motor pulls a brief surge — as a rule of thumb two to three times the running current, with the LRA on the rating plate as the figure to trust. That is why a 1.8 A appliance is not wired in the thinnest thing on the shelf.

For a refrigerator point in a Pakistani home, run 1.5 mm² copper on a 10 A MCB, three cores so the earth is 1.5 mm² as well: the appliance draws 100–400 W, which is 100 ÷ 220 = 0.5 A to 400 ÷ 220 = 1.8 A, and 1.5 mm² is rated 19.5 A clipped direct at 30°C. Go up to 2.5 mm² only where the same point also feeds a second cold appliance, or where the fridge socket sits on the general room circuit with heating appliances on it.

Circuit sheet for one domestic fridge or deep freezer point on a 220 V single-phase supply. Copper, PVC. Current capacity and voltage drop per BS 7671, reference method C (clipped direct), 30°C ambient, two loaded conductors; conductor and stranding data per IEC 60228. Read the plate on your own unit. Verify sizing with a licensed electrician for your installation.
ParameterValue
ApplianceRefrigerator, freezer or deep freezer
Power, typical100–400 W
Running current at 220 V0.5–1.8 A
Start surgeLRA on the plate — rule of thumb, 2–3× running
Breaker rating10 A MCB
Live, neutral and earth1.5 mm² copper
Trade code3/.029
Capacity, 1.5 mm²19.5 A

1.5mm wire for refrigerator points, and where the thin stuff fails

The fridge point in the wall is rarely the problem. The lead between the wall and the fridge is. A common extension board is made in 0.75 mm², which is rated 6 A and drops 62 mV per amp per metre — more than twice what 1.5 mm² drops.

Capacity and voltage drop by size, two loaded conductors, per BS 7671 reference method C (clipped direct), 30°C ambient, copper, PVC; class 5 stranding per IEC 60228. Drop at start is 62, 44, 29 or 18 mV/A/m × 5.4 A × 10 m ÷ 1000.
SizeCapacityVoltage dropClass 5 strandsDrop at a 5.4 A start, 10 m
0.75 mm²6 A62 mV/A/m24/0.203.35 V
1 mm²10 A44 mV/A/m32/0.202.38 V
1.5 mm²19.5 A29 mV/A/m30/0.251.57 V
2.5 mm²27 A18 mV/A/m50/0.250.97 V

Work it through on a 1.8 A fridge whose compressor starts at three times running, so 5.4 A, sitting on a 10 m extension lead: 62 × 5.4 × 10 ÷ 1000 = 3.35 V lost inside the lead itself, at the exact moment the motor most needs voltage. On 1.5 mm² the same start loses 1.57 V. Neither figure trips anything, and neither is a fire — it is the compressor that pays, in a house where the street voltage is already sagging. Run the fridge from a wall socket on its own way from the board.

Current capacity depends on how the cable is installed. Derate for conduit, grouping, and ambient temperature above 30°C — the wall behind a fridge is warmer than the room. Have a licensed electrician confirm the size for your load and run length — or start with the cable size calculator.

Fridge and deep freezer on one point

Very common in Pakistani kitchens and stores, and the current answer is easy: a 250 W fridge and a 350 W deep freezer together are 600 W, or 600 ÷ 220 = 2.7 A. Even if both compressors happened to start together at three times running, 8.1 A still sits inside a 10 A MCB and well inside 1.5 mm². The cable is not the reason to separate them.

The reason is what one fault costs. Share the point and a single tripped breaker, a burnt socket or a chewed lead takes out both stores of food, and in a house that already loses power to load-shedding, that is the failure that actually happens. Two ways from the board, one for each, is a few metres of 1.5 mm² and a spare MCB.

The cable for this job

Coil of flexible copper cable with black PVC outer sheath
1.5MM² · 2 CORE · 300/500 V · CU CLASS 5

1.5mm 2 Core Flexible Cable

Class 5 stranded copper, 30/0.25, PVC insulated and sheathed, 300/500 V, drawn on the Pilone line in Lahore. Rated 19.5 A clipped direct at 30°C, 29 mV/A/m.

Factory-direct price
Contact for quote
Message us for today’s rate
WhatsApp for today's rate

Cable is priced off the day's copper rate, so we quote per metre and per coil on WhatsApp rather than publish a figure that goes stale. Send the metres and your city.

For a fridge point take the three-core version so the earth matches: 1.5mm 3 core flexible cable. For a chased conduit run, 1.5mm single core solid cable pulled as separate conductors. All 1.5mm sizes and specs.

Frequently asked

What size wire for a refrigerator in Pakistan?
1.5 mm² copper — the trade code 3/.029 — on a 10 A MCB, run as three cores so the earth matches. A domestic fridge draws 100–400 W, which is 0.5–1.8 A at 220 V, and 1.5 mm² carries 19.5 A clipped direct at 30°C. The margin is not for the running load; it is for the compressor start and for the cable being buried in a warm wall.
Can the fridge and the deep freezer run from one socket?
On the numbers, yes: a 250 W fridge and a 350 W freezer together are 600 W, or 2.7 A at 220 V, nowhere near the 19.5 A the cable carries. The reason to split them is not current. One tripped MCB or one loose socket then spoils both stores of food at once, and in a load-shedding house that is the failure that actually happens.
Kya fridge extension board par chal sakta hai?
Behtar nahi. Aam extension lead 0.75 mm² ka hota hai, jiski capacity sirf 6 A hai aur voltage drop 62 mV/A/m. Compressor start ke waqt agar current 5.4 A ho jaye to 10 metre ke lead mein 62 × 5.4 × 10 ÷ 1000 = 3.35 V khud lead kha jata hai — theek us lamhe jab motor ko voltage sab se zyada chahiye. Fridge ko deewar ke socket se seedha chalayen.
Does an inverter fridge need a different wire?
No. The point stays 1.5 mm² on a 10 A MCB. An inverter compressor ramps up instead of slamming on, so the start surge is gentler, and the running current varies with how hard the unit is working — but the maximum current on the rating plate is what the cable is sized against, and that figure does not shrink.

1.5mm cable for the fridge point, at the factory rate

We draw the copper in Lahore and sell it at the day's rate — no dealer margin, and the line that made the coil answers the message. Tell us the metres and your city: Punjab in 1–2 days, rest of Pakistan in 2–4.

WhatsApp for a quote