2.5 mm² copper — 7/.029 — 3 core, on its own 16 A MCB. Not on a lighting circuit.
A domestic deep freezer runs at 100–300 W, which is 0.5–1.4 A at 220 V. The running current is small and the size is not chosen for it. The point is a 13 A socket outlet, and a socket outlet is wired for the breaker that protects it, not for the one appliance you have in mind today.
For a deep freezer in Pakistan the point is 2.5 mm² copper, three core with the earth, on a dedicated 16 A MCB feeding an unswitched socket: the cabinet draws 0.5–1.4 A at 220 V against the 27 A it carries clipped direct at 30 °C, and the reason for all that headroom is the breaker rather than the freezer. Read the wattage off your own rating plate — shop cabinets run well above the domestic band.
| Parameter | Value |
|---|---|
| Appliance | Deep freezer, upright or chest, domestic |
| Power, typical (running) | 100–300 W |
| Running current at 220 V | 0.5–1.4 A |
| Start surge | LRA on the plate — rule of thumb, 2–3× running |
| Duty | Continuous, 24 hours |
| Outlet | 13 A socket, unswitched |
| Breaker | 16 A MCB, its own way |
| Cable | 2.5 mm² copper (7/.029) |
| Cores | 3 core — live, neutral, earth |
| Capacity and margin | 27 A, so +11 A over the MCB |
Take the biggest domestic cabinet in the band, 300 W: 300 ÷ 220 = 1.4 A. Over a 20 m run in 2.5 mm² the cable loses 18 × 1.4 × 20 ÷ 1000 = 0.50 V; in 1.5 mm² it would lose 29 × 1.4 × 20 ÷ 1000 = 0.81 V. Both are nothing against a 220 V supply, and on those two figures alone 1.5 mm² looks like plenty.
It is not, and this is the sentence the thin appliance charts leave out: the cable is not protecting the freezer, the breaker is protecting the cable. A 13 A socket sits on a 16 A MCB, and a fault at the socket — or the second appliance somebody plugs in next winter — can put the full breaker current down that wire before it moves. 1 mm² is rated 10 A and 1.5 mm² is 19.5 A, both before derating; only the 2.5 at 27 A keeps a real margin once conduit and a Pakistani summer have taken their share. Size the cable to its protection, never to the appliance. That is the whole difference between this page and our refrigerator and freezer wire size guide, which answers 1.5 mm²: that guide sizes a dedicated cold-appliance point on a 10 A MCB, while this one sizes a 13 A socket outlet on a 16 A way — same cabinet, bigger breaker, bigger cable.
Take the three-core version so the earth is 2.5 mm² as well: 2.5mm 3 core flexible cable for a sheathed run to the socket, or 2.5mm single core copper (7/.029) where singles are pulled through conduit. Either way the freezer point is 2.5 mm², three core, and that is the cable to order for this job. Aside on the card below: the 1.5mm flexible is the size for the light and fan points on the same board, not for a 16 A socket way.
Class 5 flexible copper, 30/0.25 strands, PVC insulated and sheathed, drawn on the Pilone line in Lahore. Rated 19.5 A clipped direct at 30 °C — the size for fan, light and appliance-lead work rather than a 16 A socket way.