How much wire does a 3 marla house need?

PILONE CABLES TECHNICAL TEAM

About 11 coils — 6 of 1.5 mm², 4 of 2.5 mm² and 1 of 4 mm² — which is roughly 900 m of single-core copper, plus about 60 ft of 10 mm² main cable from the meter to the distribution board.

That is a single-storey 3 marla house wired to 28 points on 7 circuits, pulled through conduit, with 15% cut in for wastage. Build the second floor and the coil count roughly doubles. A coil is 90 m — the length the trade sells house wire in.

Coils first, because that is how you buy it

Every technical source quotes house wiring in metres. Every shop in Pakistan sells it in coils. One standard coil of single-core building wire is 90 m, near enough 100 yards, so the conversion you need at the counter is metres ÷ 90.

A single-storey 3 marla house of about 560 sq ft covered area, wired to 28 points on 7 circuits, needs roughly 900 m of single-core copper conductor: 460 m of 1.5 mm² for lights and fans, 345 m of 2.5 mm² for socket circuits, 83 m of 4 mm² for the AC and geyser points, and about 17 m of 6 mm² for the main earth. In 90 m coils that is 6 + 4 + 1 = 11 coils. Those figures already carry a 15% wastage margin and assume a centrally placed distribution board, conduit routing and a single floor.

Nobody sells you a 460 m length. You buy 6 coils of 1.5 mm² and hold the offcut. That is why the buy list rounds up and the metre column does not.

How the 11 coils are worked out

Three inputs, multiplied. Change any one of them and the answer moves, which is the whole point of showing them.

1. Count the points

28 on a single-storey 3 marla plan: 16 light and fan points, 10 socket points, 1 AC point, 1 geyser point. Count yours off the layout before you order.

2. Set the average run

10 m per point. That is the conduit length attributable to one point — its share of the circuit run back to the DB, plus the ceiling rise and the switch drop. A 560 sq ft floor is roughly 22 × 25 ft, so the far corner sits about 10 m of routed pipe from a central board.

3. Count conductors per run

2.5 for lighting and fan circuits, where switch legs share neutrals; 3 for socket and appliance circuits, which each carry live, neutral and earth.

Lighting and fans: 16 × 10 × 2.5 = 400 m. Sockets: 10 × 10 × 3 = 300 m. AC and geyser, on a slightly longer 12 m run: 2 × 12 × 3 = 72 m. Main earth conductor: 15 m. Raw total 787 m. Add 15% for cutting waste, pulls that fail and second attempts: 787 × 1.15 = 905 m. Divide by 90 and round up per size, and you get 11 coils.

Cross-check it against the trade rule of 1.5–2 ft of conduit run per sq ft of plot. At 675 sq ft that is 309–411 m of runs, and at 2–3 conductors per run, roughly 620–1,230 m of conductor. 905 m sits inside the band. The full method, circuit by circuit, is on how much cable a house needs.

3 marla house wiring cable list

Planning quantities for a single-storey 3 marla house, 560 sq ft covered, 28 points, conduit wiring, 15% wastage included. Coils at 90 m, rounded up per size. This is a planning band, not a bill — count your own points off the approved layout.
CircuitSize (strand code)Conductor metresCoils
Lighting and fan circuits1.5 mm² (3/.029)460 m6
Socket circuits, kitchen2.5 mm² (7/.029)345 m4
AC point, geyser point4 mm² (7/.036)83 m1
Main earth conductor6 mm² (7/.044)17 mcut length
Meter to DB main cable10 mm² 2 core copper (7/.052)18 m / 60 ftcut length

Where the 28 points sit

A 3 marla plot is 675 sq ft. After setback and staircase you build about 560 sq ft per floor, which on most plans is two bedrooms, a lounge, a kitchen, one bathroom and a small entrance.

A typical single-storey 3 marla point schedule. Point counts drive both the coil list and the number of ways in the distribution board.
RoomLight and fanSocketAppliance
Bedroom 1431 AC
Bedroom 242
Lounge43
Kitchen22
Bathroom11 geyser
Entrance, stairs, outside1
Total16102

Those 28 points group into 7 circuits: 2 lighting, 2 socket, 1 kitchen, 1 AC, 1 geyser. Add one spare way and an 8-way distribution board covers it. If a second floor is coming, buy the 12-way now — changing the board later means opening the wall it sits in.

Single storey or double storey

Most 3 marla plots are built upward, not outward. The upper floor carries about 85% of the ground floor's points — no porch, no main entrance, no pump — and adds a sub-main from the ground-floor board to a small board upstairs.

Same plot, same point density, one extra floor. Second-floor figure derived as 0.85 of the ground floor plus the riser; coils rounded up per size.
ItemSingle storeyDouble storey
Points2852
1.5 mm² coils610
2.5 mm² coils48
4 mm² coils12
Total coils1120
Conductor metres905 m1,675 m
Boards1 × 8 way1 × 12 way + 1 × 6 way
Riser to upper board10 mm², about 10 m

Meter to DB: the one cable people forget

The coil list wires the house. It does not feed it. The cable from the WAPDA or K-Electric meter to your distribution board is a separate, heavier, two-core run, and it is the line missing from almost every 3 marla wiring list published.

Assume a 5 kW sanctioned load, which is typical for a 3 marla domestic connection — check the figure on your meter card, not on a guide. At 220 V single phase that is 5,000 ÷ 220 = 22.7 A. Over an 18 m (60 ft) run, 6 mm² copper carries 46 A and drops 22.7 × 18 × 7.3 ÷ 1000 = 2.99 V, inside the 11 V budget that 5% of 220 V allows. So 6 mm² passes on the numbers. Run 10 mm² copper anyway: it carries 63 A, drops 1.80 V, and absorbs the second AC you will add. The sizing rationale in full is on WAPDA meter cable size; the same run in aluminium is a size up, and is on 16mm 2 core aluminium cable.

3/29, 7/29 and what they actually measure

Ask for 1.5 mm² at a shop in Pakistan and you will be handed 3/.029. The strand code is the trade's real vocabulary, and it is an imperial one: 3 strands of 0.029 inch. It is worth knowing what that converts to, because the two numbering systems do not line up exactly.

Strand code to true conductor area. Area = strands × π/4 × strand diameter², with 0.029 in = 0.7366 mm. Metric equivalent is the size the code is sold as, not an exact match.
Strand codeTrue areaSold asUsual job
3/.0291.29 mm²1.5 mm²Lights, fans
7/.0293.0 mm²2.5–3 mm²Sockets, kitchen
7/.0364.6 mm²4 mm²AC, geyser
7/.0446.9 mm²6 mm²Earth, submains
7/.0529.6 mm²10 mm²Meter to DB
7/.06414.5 mm²16 mm²Heavy service run

Read the first two rows carefully. 3/.029 measures 1.29 mm², under a true 1.5 mm², so keep it on 6 A lighting circuits and off sockets. 7/.029 measures 3.0 mm², over a true 2.5 mm², which is why it is the socket wire of choice here.

Current capacity, circuit by circuit

Copper conductors, PVC insulated, 450/750 V. Current capacity and voltage drop per BS 7671 (IEC 60364-5-52), installation reference method C (clipped direct), 30°C ambient; conductor resistance per IEC 60228. Wire pulled through conduit and bunched in a Lahore summer carries less than this — derate it. Verify sizing with a licensed electrician for your installation.
CircuitSizeCapacityVoltage dropBreaker
Lighting, fans1.5 mm²19.5 A29 mV/A/m6 A
Sockets, kitchen2.5 mm²27 A18 mV/A/m16 A
AC point, geyser4 mm²36 A11 mV/A/m20 A
Main earth6 mm²46 A7.3 mV/A/m
Meter to DB10 mm²63 A4.4 mV/A/m40 A

Choosing between sizes on a specific circuit rather than a whole house? The selection chart lives on single-phase cable size, and long runs are settled by the voltage drop calculator.

3 marla wiring cost: what the number covers

Published totals for wiring the same size of house differ by several times over, and the reason is almost never the house. It is scope. One quote is the wire alone; the next adds conduit, boards and accessories; the third adds the electrician. Before you compare two numbers, find out which of these three they cover.

The three scopes a 3 marla wiring cost can mean. We quote scope A at the day's copper rate; scopes B and C are bought elsewhere and are shown so you can read a quote correctly.
ScopeWhat is in itWho supplies it
A. Wire and cable onlyThe 11 coils, the earth conductor, the meter-to-DB main cablePilone Cables, factory-direct
B. A plus fittingsConduit pipe, back boxes, switches, sockets, the distribution board and its MCBs, earth electrodeElectrical store
C. B plus labourChasing walls, laying conduit, pulling wire, terminating, testing, making good the plasterYour electrician or contractor

Scope A is the only one we price, and we price it at the day's copper rate because that is what moves it. Per-point and per-square-foot labour rates sit on cable installation cost. Send the coil list on WhatsApp and you get scope A as one figure for your city.

Wiring a 3 marla plot that grows upward

A 3 marla house is narrow and deep, and it is rarely finished at one storey. That shapes three decisions that do not come up on a wider plot.

Put the board where the riser will be. On 22 ft of frontage there is one sensible vertical route, usually beside the staircase. Fix the ground-floor distribution board at the foot of it. If the board goes in a bedroom wall because that is where the meter happened to land, every future floor pays for it in extra run length and a chased wall.

Lay the riser conduit before you plaster, even if the floor is years away. An empty 25 mm pipe from the ground board to the roof slab costs almost nothing during construction. Retrofitting it costs a wall. When the floor is built you pull 10 mm² through it, land it on a 6-way board upstairs, and the second-floor wiring never touches the ground-floor circuits. The full construction sequence is on wiring for a new house.

If a floor will be rented, split it at the board, not at the socket. An upper portion on its own sub-board and its own sub-meter is the clean arrangement, and it is a different circuit design from a single-family house — the shared-riser and sub-meter case is covered on the apartment and portion wiring guide.

One more thing specific to the small plot: do not shave the coil list. The gap between 11 coils and 9 is two coils of copper and a circuit you cannot add later without opening plaster. On a 3 marla house the wire is the cheapest part of the wall it sits in.

These are planning quantities worked from a stated point count, run length and conductor count — not a certified load calculation. Current capacities assume method C at 30°C; derate for conduit, bunching and summer ambient. Confirm the point schedule, circuit count and every cable size with a licensed electrician against your approved layout, or start with the cable size calculator.

Frequently asked

3 marla ghar ki wiring mein kitna wire lagta hai?
About 11 coils for a single storey: 6 coils of 1.5 mm² (3/.029), 4 of 2.5 mm² (7/.029) and 1 of 4 mm² (7/.036), roughly 900 m of conductor in total. Double storey takes about 20 coils. Add the meter-to-DB main cable and about 17 m of 6 mm² earth wire on top of that.
One coil kitne meter ka hota hai?
A standard coil of single-core house wire in Pakistan is 90 m, which is close to 100 yards. That is the unit every quantity on this page converts through: metres divided by 90 gives coils. Always confirm the coil length in writing before you order, from us or anyone else, because it is the figure that quietly varies.
Is that a wiring cost or just the wire?
Just the wire. A 3 marla wiring cost can mean three different things: wire and cable only, that plus conduit, switches and the DB, or all of it plus the electrician's labour. This page quantifies the first. Compare any two quotes only after you know which scope each one covers.
Konsa wire kis kaam ka hai — 3/29 ya 7/29?
3/.029 measures 1.29 mm² and belongs on lighting and fan circuits behind a 6 A breaker. 7/.029 measures 3.0 mm² and is the socket and kitchen wire, on 16 A. Do not run sockets on 3/.029 — it is under a true 1.5 mm², so it has less margin than the label suggests.
3 marla mein kitne points hotay hain?
About 28 on a single storey: 16 light and fan points, 10 socket points, one AC point and one geyser point, across two bedrooms, a lounge, a kitchen and a bathroom. Your layout will move that by a few either way, and the point count is what drives both the coil list and the board size.
DB box kitne way ka lena chahiye?
Those 28 points group into 7 circuits: 2 lighting, 2 socket, 1 kitchen, 1 AC, 1 geyser. With one spare way that is an 8-way distribution board. If a second floor is planned, fit a 12-way now and a small 6-way board upstairs later — replacing a board means opening the wall around it.
Kitna extra wire lena chahiye wastage ke liye?
15% is built into every figure on this page. That covers cutting waste, failed pulls and the extra length terminations eat. If your conduit runs are long or the layout is not final, take 20%. Copper offcuts are not wasted money — they are the spare you will want when a point moves.

The wire for this list

Coil of 3/.029 single-core PVC-insulated copper house wiring cable
3/.029 · 1.29 MM² · SINGLE CORE · 450/750 V

3/.029 Single Core Copper Cable

The biggest line on a 3 marla list at 6 coils. Stranded copper, PVC insulated, 450/750 V, drawn on the Pilone line in Lahore for lighting and fan circuits.

Factory-direct price
Contact for quote
Message us for today’s rate
Send the coil list

Prices track the daily copper rate. Send the coil list and your city for today's factory rate on the whole lot.

Also on this list: 7/.029 single core copper cable, 4mm single core copper cable, 6mm single core copper cable for the earth, and 10mm 2 core standard cable for the meter run.

Eleven coils, one factory rate

We draw the copper in Lahore and sell it at the day's rate — no dealer margin. Send the coil list and your city for today's number: Punjab in 1–2 days, rest of Pakistan in 2–4.

Send the coil list and your city