How much wire does a 10 marla house need?

PILONE CABLES TECHNICAL TEAM

About 43 coils — 20 of 1.5 mm², 18 of 2.5 mm² and 5 of 4 mm² — which is roughly 3,780 m of single-core copper, plus about 92 ft of 16 mm² main cable from the meter to the distribution board.

That is a single-storey 10 marla house wired to 78 points on 17 circuits, pulled through conduit, with 15% cut in for wastage. Double storey takes about 79 coils. A coil is 90 m — the length the trade sells house wire in.

The 10 marla number, in coils and in metres

A single-storey 10 marla house of about 1,800 sq ft covered area, wired to 78 points on 17 circuits, needs roughly 3,780 m of single-core copper conductor: 1,725 m of 1.5 mm² for lights and fans, 1,615 m of 2.5 mm² for socket, kitchen and pump circuits, 411 m of 4 mm² for four AC points, two geysers and the hob, and about 29 m of 6 mm² for the main earth. In 90 m coils that is 20 + 18 + 5 = 43 coils. Those figures carry a 15% wastage margin and assume a centrally placed distribution board, conduit routing and one floor.

Technical sources quote metres. Shops sell coils. One standard coil of single-core building wire is 90 m, near enough 100 yards, so the conversion at the counter is metres ÷ 90, rounded up per size.

Costed 10 marla electrical estimates do exist online, but the ones we could find compress every wire in the house into a single lump figure with no size split, no length and no cable list. That is fine for a budget line and useless at the shop counter, which is where this page starts.

How the 43 coils are worked out

Three inputs, multiplied. Every one of them is visible, so you can move any of them to match your own house.

1. Count the points

78 on a single-storey 10 marla plan: 40 light and fan points, 30 socket points, 4 AC points, 2 geysers, 1 hob or oven, 1 pump. Count yours off the approved layout.

2. Set the average run

15 m per point: its share of the circuit run back to the DB, plus the ceiling rise and the switch drop. A 1,800 sq ft floor is roughly 35 × 51 ft, and a single central board is already a long reach on that footprint.

3. Count conductors per run

2.5 for lighting and fan circuits, where switch legs share neutrals; 3 for socket and appliance circuits, which each carry live, neutral and earth.

Lighting and fans: 40 × 15 × 2.5 = 1,500 m. Sockets and kitchen: 30 × 15 × 3 = 1,350 m. Pump, on an 18 m run: 1 × 18 × 3 = 54 m, giving 1,404 m of 2.5 mm². Four ACs, two geysers and the hob on 17 m runs: 7 × 17 × 3 = 357 m of 4 mm². Main earth: 25 m. Raw total 3,286 m. Add 15%: 3,286 × 1.15 = 3,779 m. Divide by 90 and round up per size: 43 coils.

Cross-check against the trade rule of 1.5–2 ft of conduit run per sq ft of plot. At 2,250 sq ft that is 1,030–1,370 m of runs, and at 2–3 conductors per run, 2,060–4,110 m of conductor. 3,779 m sits inside it. The method itself is on how much cable a house needs.

10 marla house wiring cable list

Planning quantities for a single-storey 10 marla house, 1,800 sq ft covered, 78 points, conduit wiring, 15% wastage included. Coils at 90 m, rounded up per size. A planning band, not a bill — count your own points off the approved layout.
CircuitSize (strand code)Conductor metresCoils
Lighting and fan circuits1.5 mm² (3/.029)1,725 m20
Socket, kitchen and pump circuits2.5 mm² (7/.029)1,615 m18
4 AC points, 2 geysers, hob4 mm² (7/.036)411 m5
Main earth conductor6 mm² (7/.044)29 mcut length
Meter to DB main cable16 mm² 2 core (7/.064)28 m / 92 ftcut length

Where the 78 points sit

A 10 marla plot is 2,250 sq ft. After setback, stairs, porch and lawn you build about 1,800 sq ft per floor — typically four bedrooms, a drawing room, a lounge, a kitchen, a store and three or four bathrooms.

A typical single-storey 10 marla point schedule. Those 78 points group into 17 circuits: 4 lighting, 4 socket, 1 kitchen, 4 AC, 2 geyser, 1 hob, 1 pump. With 20% spare that is 21 ways, so a 24-way board.
RoomLight and fanSocketAppliance
Bedroom 1 (master)641 AC
Bedroom 2531 AC
Bedroom 3431 AC
Bedroom 4431 AC
Drawing room64
Lounge and dining75
Kitchen and store451 hob
4 bathrooms42 geysers
Porch, stairs, lawn, outside31 pump
Total40308

Sizing the meter-to-DB main cable

This is the cable the coil list does not cover and almost no published estimate names. It runs from the WAPDA or K-Electric meter to your distribution board, it carries the whole house, and at 10 marla it is the first plot size where getting it wrong is expensive. Here is the sizing, in full, because the plot pages that carry a figure for it never show the working.

Step one, the load. Take the sanctioned load off your meter card — not off a guide. A 10 marla domestic connection is commonly sanctioned around 12 kW. At 220 V single phase, 12,000 ÷ 220 = 54.5 A. If your connection is three phase, divide by 400 × 1.732 = 693 instead, which puts the same 12 kW at 17.3 A per phase and drops you two cable sizes.

Step two, current capacity. On BS 7671 method C at 30°C, 10 mm² copper two-core carries 63 A and 16 mm² carries 85 A. Both clear 54.5 A on paper. A service cable buried, sleeved or run against a sun-facing wall does not sit at 30°C, which is the whole argument for not sizing to the edge.

Step three, voltage drop. The run is about 28 m (92 ft) from a boundary-wall meter to a board inside. On 10 mm²: 54.5 × 28 × 4.4 ÷ 1000 = 6.72 V. On 16 mm²: 54.5 × 28 × 2.8 ÷ 1000 = 4.28 V. The budget is 5% of 220 V, which is 11 V, so both pass — but the 10 mm² figure has already spent 61% of the house's entire drop allowance before the first circuit leaves the board.

The answer. 16 mm² two-core copper, about 92 running feet. 10 mm² is the minimum that passes; 16 mm² is what leaves the rest of the house a voltage budget to spend. In aluminium the same job goes a size up again. Two-core for a single-phase connection, four-core for three-phase. The rationale in full is on WAPDA meter cable size and main meter cable.

Meter-to-DB options for a 12 kW single-phase 10 marla connection over a 28 m run. Copper, PVC, BS 7671 method C at 30°C; drop = mV/A/m × 54.5 A × 28 m ÷ 1000, against an 11 V budget.
SizeCapacityDrop over 28 mBudget usedVerdict
6 mm²46 A11.15 V101%Fails both
10 mm²63 A6.72 V61%Minimum that passes
16 mm²85 A4.28 V39%Recommended
25 mm²112 A2.67 V24%For a 15 kW upgrade

Single storey vs double storey

Most 10 marla houses are built to two floors. The upper floor carries about 85% of the ground floor's points — no porch, no lawn, no pump — and gets its own board fed by a riser, not a set of circuits pulled up the stairs.

Same plot, same point density, one extra floor. Second-floor quantities derived as 0.85 of the ground floor plus the riser; coils rounded up per size.
ItemSingle storeyDouble storey
Points78144
1.5 mm² coils2036
2.5 mm² coils1834
4 mm² coils59
Total coils4379
Conductor metres3,779 m6,991 m
Boards1 × 24 way1 × 24 way + 1 × 18 way
Riser to upper board16 mm², about 16 m
Meter to DB16 mm²25 mm² on a 15 kW load

Note the last row. A double-storey 10 marla usually comes with a load upgrade, and the moment the sanctioned load moves from 12 to 15 kW the service current goes from 54.5 A to 68.2 A — past what 16 mm² should be asked to hold for the life of the house. Size the service for the finished building, not the ground floor.

3/29, 7/29 and what they actually measure

Ask for 1.5 mm² at a shop in Pakistan and you will be handed 3/.029. The strand code is the trade's real vocabulary and it is imperial: 3 strands of 0.029 inch. Multiply it out and the two systems do not line up exactly.

Strand code to true conductor area. Area = strands × π/4 × strand diameter², with 0.029 in = 0.7366 mm. The metric column is the size the code is sold as, not an exact equivalent.
Strand codeTrue areaSold asUsual job
3/.0291.29 mm²1.5 mm²Lights, fans
7/.0293.0 mm²2.5–3 mm²Sockets, kitchen
7/.0364.6 mm²4 mm²AC, geyser, hob
7/.0446.9 mm²6 mm²Earth, submains
7/.0529.6 mm²10 mm²Riser, small service
7/.06414.5 mm²16 mm²Meter to DB

3/.029 measures 1.29 mm², under a true 1.5 mm², so keep it on 6 A lighting circuits and off sockets. 7/.029 measures 3.0 mm², over a true 2.5 mm². How to verify a delivered coil against these numbers is set out on the 5 marla wiring page.

Current capacity, circuit by circuit

Copper conductors, PVC insulated, 450/750 V. Current capacity and voltage drop per BS 7671 (IEC 60364-5-52), installation reference method C (clipped direct), 30°C ambient; conductor resistance per IEC 60228. Wire pulled through conduit and bunched in a Lahore summer carries less than this — derate it. Verify sizing with a licensed electrician for your installation.
CircuitSizeCapacityVoltage dropBreaker
Lighting, fans1.5 mm²19.5 A29 mV/A/m6 A
Sockets, kitchen, pump2.5 mm²27 A18 mV/A/m16 A
AC points, geysers, hob4 mm²36 A11 mV/A/m20–25 A
Main earth6 mm²46 A7.3 mV/A/m
Riser to upper board16 mm²85 A2.8 mV/A/m63 A

Sizing one circuit rather than a whole house? The selection chart is on single-phase cable size, the AC circuit is worked through on cable for a 1.5 ton AC, and long runs are settled by the voltage drop calculator.

10 marla house wiring cost: what the number covers

Estimates for electrical work on the same size of house differ by several times over, and the reason is scope, not the house. One figure is the wire alone; the next adds conduit, boards and accessories; the third adds the electrician. Almost none of them say which, and comparing across them is meaningless until you know.

The three scopes a 10 marla electrical cost can mean. We quote scope A at the day's copper rate; B and C are bought elsewhere and are listed so you can read any quote correctly.
ScopeWhat is in itWho supplies it
A. Wire and cable onlyThe 43 coils, the 6 mm² earth conductor, the 16 mm² meter-to-DB main cablePilone Cables, factory-direct
B. A plus fittingsConduit pipe, back boxes, switches, sockets, the 24-way board and its MCBs, earth electrodeElectrical store
C. B plus labourChasing walls, laying conduit, pulling wire, terminating, testing, making good the plasterYour electrician or contractor

Scope A is the only one we price, and we price it at the day's copper rate because copper is what moves it. Per-point and per-square-foot labour rates sit on cable installation cost. Send the coil list on WhatsApp and scope A comes back as one figure for your city.

These are planning quantities worked from a stated point count, run length and conductor count — not a certified load calculation. Current capacities assume method C at 30°C; derate for conduit, bunching and summer ambient. Confirm the point schedule, circuit count and every cable size with a licensed electrician against your approved layout, or start with the cable size calculator.

Frequently asked

10 marla ghar ki wiring mein kitna wire lagta hai?
About 43 coils for a single storey: 20 coils of 1.5 mm² (3/.029), 18 of 2.5 mm² (7/.029) and 5 of 4 mm² (7/.036), roughly 3,780 m of conductor. Double storey takes about 79 coils. Add 29 m of 6 mm² earth wire and about 92 ft of 16 mm² main cable from the meter.
Meter se DB tak konsi cable jaye gi?
16 mm² two-core copper, about 92 running feet. On a 12 kW single-phase connection the load is 54.5 A; 10 mm² is the minimum that passes but spends 61% of the house's whole voltage-drop budget over 28 m, against 39% on 16 mm². Four-core if the connection is three phase.
Is the 10 marla electrical work cost only the wire, or does it include fittings and labour?
Three different scopes carry that name: wire and cable only; that plus conduit, switches, sockets and the DB; or all of it plus the electrician's labour. This page quantifies the first, which is the only one we supply. Published lump-sum figures usually mean the third, which is why they look so much larger.
10 marla mein kitne points hotay hain?
About 78 on a single storey: 40 light and fan points, 30 socket points, 4 AC points, 2 geysers, a hob and a pump, across four bedrooms, a drawing room, a lounge, a kitchen and four bathrooms. The point count is the input that moves the coil list most, so count yours.
DB box kitne way ka lena chahiye?
Those 78 points group into 17 circuits: 4 lighting, 4 socket, 1 kitchen, 4 AC, 2 geyser, 1 hob, 1 pump. Add 20% spare and you need 21 ways, so a 24-way board. On a double storey, split it: a 24-way downstairs and an 18-way upstairs fed by a 16 mm² riser.
One coil kitne meter ka hota hai?
A standard coil of single-core house wire in Pakistan is 90 m, close to 100 yards. Every quantity on this page converts through it: metres divided by 90, rounded up per size. Confirm the coil length in writing before you order, from us or anyone else — on 43 coils a small shortfall is a real number.
Double storey mein kitna extra wire lagega?
About 36 more coils, taking a 10 marla from 43 to roughly 79. The upper floor carries about 85% of the ground floor's points and needs its own 18-way board fed by a 16 mm² riser of about 16 m. Budget a heavier service cable too, because the sanctioned load usually goes up with the floor.
Earth wire ka size kya hoga ghar ki earthing ke liye?
6 mm² (7/.044) for the main earthing conductor from the board to the electrode, about 29 m on this layout. Point earths are carried inside each circuit — that is the third conductor in the socket and appliance runs, which is why those circuits are counted at 3 conductors and lighting at 2.5.

The cable that feeds the house

16mm two-core standard copper cable, cut back to show two PVC-insulated stranded conductors
16MM² · 2 CORE · 450/750 V · CU CLASS 2

16mm 2 Core Standard Cable

The meter-to-DB run on a 10 marla house: 7/1.70 class 2 copper, PVC insulated and sheathed, rated 85 A on method C. About 92 running feet on this layout.

Factory-direct price
Contact for quote
Message us for today’s rate
Send the coil list

Prices track the daily copper rate. Send the coil list and your city for today's factory rate on the whole lot.

The rest of the list: 3/.029 single core copper cable, 7/.029 single core copper cable, 4mm single core copper cable, 6mm single core copper cable for the earth.

Forty-three coils and the main run, one factory rate

We draw the copper in Lahore and sell it at the day's rate — no dealer margin. Send the coil list and your city for today's number: Punjab in 1–2 days, rest of Pakistan in 2–4.

Send the coil list and your city