Skip to content
Factory-direct from Lahore · Nationwide delivery in 2–4 days +92 319 4262451 WhatsApp

2.5mm or 4mm cable? 27 A against 36 A, and what 7/029 really is

PILONE CABLES TECHNICAL TEAM

2.5 mm² carries 27 A and 4 mm² carries 36 A, both clipped direct at 30°C. Take 2.5 mm² for socket and lighting circuits on a 16 A breaker; take 4 mm² for an AC point, a geyser, or any circuit on a 20 A breaker.

The current rating is only half the decision. 2.5 mm² loses 18 mV per amp per metre and 4 mm² loses 11, so on a long run the thinner cable runs out of voltage budget before it runs out of current capacity. This page is about fixed house wiring on a 220 V supply, not speaker cable.

2.5 mm vs 4mm wire, side by side

One size up is a 33% gain in current capacity, a 39% cut in voltage drop, and 60% more copper in the conductor. Those three numbers are the whole argument, and every row below comes from the same two standards.

Copper conductors, PVC insulated, 450/750 V. Conductor resistance and strand construction per IEC 60228; current capacity and voltage drop per BS 7671, installation reference method C (clipped direct), 30°C ambient. Conductor copper mass computed at 8.89 kg/km per mm². Verify sizing with a licensed electrician for your installation.
Property2.5 mm²4 mm²
Standard (class 2) strands7/0.677/0.85
Flexible (class 5) strands50/0.2556/0.30
Max resistance, class 2, 20°C7.41 Ω/km4.61 Ω/km
Max resistance, class 5, 20°C7.98 Ω/km4.95 Ω/km
Capacity, 2 loaded cores27 A36 A
Capacity, 3 loaded cores24 A32 A
Voltage drop18 mV/A/m11 mV/A/m
Conductor copper22.2 kg/km35.6 kg/km
Trade code7/.0297/.036

Read the two-core row for an ordinary single-phase circuit, even on a three-core cable: live and neutral are the only loaded conductors and the earth carries nothing in normal service. The three-core row is for three-phase.

4mm vs 2.5mm cable: which size belongs on which circuit

On a 220 V single-phase supply, 2.5 mm² copper is the right size for socket, lighting and small-appliance circuits protected at 16 A, on runs under about 20 metres, clipped or in surface trunking. 4 mm² is the right size for an air conditioner point, a geyser, a kitchen submain, any circuit protected at 20 A, and any run past 20 metres — because at 36 A against 27 A it keeps a working margin over the breaker once the cable is derated for conduit, bundling and summer ambient, and at 11 mV/A/m against 18 it spends its voltage budget more slowly. You drop to 2.5 mm² only when the load, the breaker and the run length all allow it.

The run length that forces the jump

Heat decides the size on short runs; length decides it on long ones. Voltage drop is millivolts per amp per metre, times the current, times the one-way run. Take a real circuit: 20 A of load, 20 metres from the distribution board, 220 V supply. On 2.5 mm² that is 18 × 20 × 20 ÷ 1000 = 7.2 V, which is 3.3% of 220 V. On 4 mm² it is 11 × 20 × 20 ÷ 1000 = 4.4 V, or 2.0%. Hold the installation to 3% — 6.6 V on a 220 V supply — and 2.5 mm² has already spent its budget at 20 metres while 4 mm² still has a third of it left.

Longest one-way run that stays inside a 6.6 V budget, which is 3% of a 220 V supply. Length = 6.6 ÷ (mV/A/m ÷ 1000 × current). Measure the route the cable takes, not the straight line across the room. Voltage drop per BS 7671, reference method C, 30°C, copper, PVC. Where the submain has already spent part of the drop, give the final circuit only its share. Verify sizing with a licensed electrician for your installation.
Load2.5 mm²4 mm²6 mm²
10 A36.7 m60.0 m90.4 m
16 A22.9 m37.5 m56.5 m
20 A18.3 m30.0 m45.2 m
24 A15.3 m25.0 m37.7 m

Across the table 4 mm² buys about 1.64 times the run length of 2.5 mm² at the same current, because 18 ÷ 11 = 1.64. That ratio holds at every load, which is why the question "how far can I run it" has one answer and not a chart full of them. Put your own current and length into the voltage drop calculator before you buy the coil.

Where the 18 and the 11 come from

No competing page shows this, and it is two lines of arithmetic. IEC 60228 caps a 2.5 mm² class 2 conductor at 7.41 Ω/km measured at 20°C. A PVC cable working at its 70°C conductor rating is 50 degrees hotter, and copper gains roughly a fifth of its resistance over that rise, so call it 7.41 × 1.2 = 8.9 Ω/km. Current flows out along one conductor and back along the other, so the loop is twice that: 2 × 8.9 = 17.8, which the tables round to 18 mV/A/m.

Do the same on 4 mm²: 4.61 × 1.2 = 5.53, doubled is 11.06, tabulated as 11 mV/A/m. The arithmetic reproduces every row of the voltage-drop column on this site, which means you can check our numbers rather than trust them. It also explains why a cable pushed hotter than 70°C drops more than the table says.

7/029 or 7/036 — what to ask for at the shop

The counter does not speak in mm². Ask for 2.5 and you are handed 7/.029; ask for 4 and you are handed 7/.036. The codes are imperial: the first number is the strand count, the second is one strand's diameter in inches. Convert one and the whole system opens up. 0.029 inch × 25.4 = 0.7366 mm; one strand is π/4 × 0.7366² = 0.426 mm²; seven of them make 2.98 mm². The same three steps on 7/.036 give 0.914 mm per strand, 0.657 mm² each, 4.60 mm² in the conductor.

Do it for every code the trade sells and you get the table below. Nobody publishes it, and every line of it can be checked with a calculator.

Computed area is π/4 × strand diameter² × strand count, with the inch figure converted at exactly 25.4 mm and no intermediate rounding — figures rounded partway through the sum differ in the second decimal. "Sold as" is the nominal metric size the Pakistani trade prices the code at; every seller here, Pilone included, labels by that nominal size, and the resistance and capacity figures on this page are the IEC 60228 and BS 7671 values for the nominal size. Capacity is two loaded conductors, reference method C (clipped direct), 30°C, copper, PVC.
Trade codeStrand diameterComputed areaSold asDifferenceCapacity, 2 cores
3/.0290.737 mm1.28 mm²1.5 mm²15% under19.5 A
7/.0290.737 mm2.98 mm²2.5 mm²19% over27 A
7/.0360.914 mm4.60 mm²4 mm²15% over36 A
7/.0441.118 mm6.87 mm²6 mm²14% over46 A
7/.0521.321 mm9.59 mm²10 mm²4% under63 A
7/.0641.626 mm14.53 mm²16 mm²9% under85 A

Read the "difference" column carefully, because it is the source of most shop-counter arguments. A code that computes above its nominal size is not a bonus and one that computes below it is not a swindle — they are two naming systems meeting in one market, and the imperial ladder was never built to land on the metric one. 7/.029 computes 19% above 2.5 mm², which is why some sellers call it 3 mm²; 7/.052 computes 4% below 10 mm² and is still sold as 10.

The figure that settles whether a conductor is fit for its label is resistance, because that is what IEC 60228 actually defines: 7.41 Ω/km for 2.5 mm² class 2, 4.61 for 4 mm². Both are measurable on a delivered coil with a decent meter, and a conductor that meets the resistance cap for the size it is sold as is the size it is sold as, whatever the strand code computes to. Ask for the resistance figure, not the reassurance. The two single-core codes are stocked as 7/.036 single core copper cable and 7/.029 copper cable.

What the price difference actually is

Cable is priced off the day's copper rate, so the honest way to compare two sizes is by the copper in them, not by a rupee figure that goes stale in a week. A 2.5 mm² conductor holds 22.2 kg of copper per kilometre; a 4 mm² conductor holds 35.6. Per 100 metres that is 2.22 kg against 3.56 kg, and 35.6 ÷ 22.2 = 1.6. So 4 mm² costs about 1.6 times the copper of 2.5 mm², per core, on the same length — and a three-core cable multiplies both sides equally, so the ratio does not move.

Set that against what it buys: 9 A more capacity, 1.64 times the run length, and a circuit that still clears its breaker after derating. On a single AC point of 15 to 20 metres the whole difference is under two kilograms of copper. Repeated across every circuit in a house it stops being small, which is why a house is wired in 1.5 and 2.5 mm² with 4 mm² kept for the circuits that need it, rather than upsized everywhere. Send us the metres and your city for both rates in one message.

Current capacity depends on how the cable is installed. Derate for conduit, grouping and ambient temperature above 30°C, and take the correction factors for your own method from BS 7671. Have a licensed electrician confirm the size for your load and run length — or start with the cable size calculator.

The cable for this job

Two-core 4mm standard cable with black outer sheath cut back to show red and black insulated stranded copper conductors
4MM² · 2 CORE · 450/750 V · CU CLASS 2

4mm 2 Core Standard Cable

Class 2 stranded copper, 7/0.85, PVC insulated and sheathed, 450/750 V, drawn on the Pilone line in Lahore. Rated 36 A clipped direct at 30°C, 4.61 Ω/km at 20°C.

Factory-direct price
Contact for quote
Message us for today’s rate
WhatsApp for today's rate

Cable tracks the daily copper rate, so we quote per metre and per coil on WhatsApp rather than publish a figure that goes stale. Ask for both sizes in one message and compare.

For a circuit with its own earth take the three-core: 4mm 3 core standard cable for a fixed run in conduit, or 4mm 3 core flexible cable where the tail has to bend. At the smaller size, 2.5mm 2 core standard cable and 2.5mm 3 core cable price cover the socket and lighting circuits.

Frequently asked

What is the difference between 2.5mm and 4mm wire?
Capacity, voltage drop and copper. 4 mm² carries 36 A against 27 A clipped direct at 30°C, loses 11 mV per amp per metre against 18, and holds 35.6 kg of copper per kilometre against 22.2. In trade codes they are 7/.036 and 7/.029. The capacity decides the breaker; the voltage drop decides how far the circuit can run.
Is 2.5mm wire enough for a 1.5 ton AC, or do I need 4mm?
4 mm². Both sizes carry the running current of about 8 A, but the AC point sits on a 20 A breaker and the cable has to clear that breaker after derating. In conduit in summer heat 2.5 mm² loses its margin while 4 mm² keeps roughly 7 A of it. The full working is in the 1.5 ton AC wire size guide.
7/29 ya 7/36 — ghar ki wiring ke liye kaun sa behtar hai?
Dono chahiye, alag alag circuit ke liye. Sockets, lights aur fans par 7/.029 (2.5 mm², 27 A) 16 A breaker ke saath theek hai. AC point, geyser, oven ya 20 A breaker wale circuit par 7/.036 (4 mm², 36 A) lein. Agar run 20 meter se lamba hai ya wire conduit mein deewar ke andar hai, to bara size hi lein.
What does 7/.036 mean, and is it really 4mm?
Seven strands of 0.036 inch. Convert it: 0.036 × 25.4 = 0.914 mm per strand, each strand is pi/4 × 0.914 squared = 0.657 mm², and seven of them make 4.60 mm² of copper. So the code computes about 15% above the 4 mm² it is sold as. The label is the nominal metric size; the test of fitness is the resistance cap, 4.61 ohm/km for 4 mm² class 2.
How much longer can I run 4mm cable than 2.5mm before voltage drop is a problem?
About 1.64 times as far, at any current, because 18 ÷ 11 = 1.64. On a 6.6 V budget — 3% of 220 V — a 20 A circuit reaches 18.3 m on 2.5 mm² and 30 m on 4 mm². At 16 A it is 22.9 m against 37.5 m. Measure the route the cable takes, not the straight line.
Which is cheaper, 2.5mm or 4mm cable, and is the difference worth it?
2.5 mm² is cheaper, and the gap is a copper-weight gap: 4 mm² holds 1.6 times the copper per metre, so it costs roughly 1.6 times as much per core at any day's copper rate. On one AC point of 15 to 20 m that is under two kilograms of copper. On a whole house it is worth keeping 4 mm² for the circuits that need it.
Which cable size is best for house wiring in Pakistan?
There is no single size — a house is wired in three. 1.5 mm² for lights and fans, 2.5 mm² for sockets and the kitchen, 4 mm² for AC points and the geyser, with 10 or 16 mm² from the meter to the board. Quantities by plot size are in the house wiring cable guide.
Can I put 2.5mm and 4mm circuits on the same distribution board?
Yes, and that is the normal arrangement. Each way is protected by its own MCB sized to its cable: 16 A on the 2.5 mm² socket circuits, 20 A on the 4 mm² AC and geyser circuits. What must never happen is a 20 A breaker feeding 2.5 mm², or two appliance circuits sharing one way.
Does 2.5mm vs 4mm mean the same thing for speaker cable?
No. This page is fixed mains wiring at 220 V, where the size is set by the breaker and the voltage drop budget. Speaker cable carries a few volts into a few ohms and is chosen on a different basis entirely. If you landed here from a speaker or audio search, none of the ampacity figures above apply to that job.

2.5mm and 4mm cable at the factory rate

We draw the copper in Lahore and sell it at the day's rate — no dealer margin, and the line that made the coil answers the message. Send both sizes, the metres and your city: Punjab in 1–2 days, rest of Pakistan in 2–4.

WhatsApp for both rates