What size wire for a 1 ton AC in Pakistan — 2.5mm or 4mm?

PILONE CABLES TECHNICAL TEAM

2.5 mm² copper, on its own 16 A type C MCB. 4 mm² once the run passes 30 m.

A 1 ton unit draws 1000–1200 W, which is 4.5–5.5 A on Pakistan's 220 V supply, and the compressor start puts a brief surge on top of that. 2.5 mm² is rated 27 A clipped direct at 30°C, so it keeps its margin over the 16 A breaker even after derating — which is exactly what 1.5 mm² cannot do. Run it as 3-core so the earth is 2.5 mm² too, on a circuit of its own from the board.

The circuit sheet for a 1 ton AC

Read the rating plate on the outdoor unit before you trust any chart — it carries the maximum current for your model. Failing that, the working figures are these: 1000 W ÷ 220 V = 4.5 A and 1200 W ÷ 220 V = 5.5 A, with a start surge on top — as a rule of thumb two to three times the running current, though the LRA on the plate is the number to size against. Ask for wire for AC 1 ton in a shop and you get 7/.029, the 2.5 mm²; on a normal house run that is the correct answer.

Circuit sheet for one 1 ton unit on a 220 V single-phase supply. Copper, PVC, BS 7671 reference method C (clipped direct), 30°C ambient; conductor data per IEC 60228. Check your own rating plate first. Verify sizing with a licensed electrician for your installation.
ParameterValue
Appliance1 ton split or window air conditioner
Power, typical1000–1200 W
Running current at 220 V4.5–5.5 A
Start surgeLRA on the plate — rule of thumb, 2–3× running
Breaker rating16 A MCB
Breaker curveType C
Live and neutral2.5 mm² copper
Earth (CPC)2.5 mm² — the third core
Cable make-up3 core, 450/750 V PVC
CircuitDedicated from the DB

Why 2.5mm² and not 1.5mm²

For a 1 ton air conditioner in Pakistan, 2.5 mm² copper on a dedicated 16 A type C MCB is the right size on any run up to about 30 metres: the unit draws 4.5–5.5 A at 220 V, 2.5 mm² is rated 27 A clipped direct at 30°C, and it still clears the breaker after derating. 1.5 mm² does not: rated 19.5 A, it clears the same 16 A breaker by 3.5 A on paper and drops below it once derated.

The 1 ton AC wire size in mm is 2.5 mm² live, 2.5 mm² neutral and 2.5 mm² earth. This is the ladder that decision is read off.

Margin is the two-core capacity less the 16 A MCB rating, before derating; derated margin applies a worked correction of 0.75 for a warm enclosed run. Read the two-core column for a single-phase AC point even on a 3 core cable — live and neutral are the only loaded conductors. Copper, PVC. Current capacity and voltage drop per BS 7671, reference method C (clipped direct), 30°C ambient; conductor and stranding data per IEC 60228. Verify sizing with a licensed electrician for your installation.
Size2 loaded cores3 loaded coresVoltage dropClass 2 strandsMargin on 16 ADerated margin
1.5 mm²19.5 A17.5 A29 mV/A/m7/0.53+3.5 A−1.4 A
2.5 mm²27 A24 A18 mV/A/m7/0.67+11 A+4.3 A
4 mm²36 A32 A11 mV/A/m7/0.85+20 A+11.0 A

The derated column is what the breaker actually sits under, and it is where 1.5 mm² fails and 2.5 mm² holds — take the exact factors for your method and ambient from BS 7671.

How far the AC can be from the distribution board

Heat decides the size on short runs; length decides it on long ones. A 1 ton unit draws little current, so 2.5 mm² stretches further here than it would on a bigger unit.

Volts lost in the cable at 5.5 A, the top of the running band at 220 V. Figure = mV/A/m × 5.5 A × run ÷ 1000. Run is one way, along the route the cable takes. Voltage drop per BS 7671, reference method C, 30°C, copper, PVC. Verify sizing with a licensed electrician for your installation.
Run1.5 mm²2.5 mm²4 mm²
10 m1.60 V0.99 V0.61 V
15 m2.39 V1.49 V0.91 V
20 m3.19 V1.98 V1.21 V
25 m3.99 V2.48 V1.51 V
30 m4.79 V2.97 V1.82 V
40 m6.38 V3.96 V2.42 V

Hold the installation to 3% of 220 V — 6.6 V — and give the AC final circuit half of it, 3.3 V, because the submain from the meter to the board has already spent the rest. On that budget 2.5 mm² runs 3.3 ÷ 0.099 = 33 m and 4 mm² runs 55 m. So the rule here is 2.5 mm² up to about 30 m, 4 mm² beyond — a unit on the far side of a 10 marla plot, or a second-floor point fed from a ground-floor board. Check yours in the voltage drop calculator.

1 ton AC ke liye kitne mm ka wire chahiye?

2.5 mm² copper wire, apne alag 16 A MCB par. Trade mein isko 7/.029 kehte hain. 3-core lein taake earth bhi 2.5 mm² ho. Agar distribution board se AC point tak 30 meter se zyada faasla hai, to 4 mm² (7/.036) lein — wahan garmi nahi, lambai faisla karti hai.

1.5 mm² (3/.029) na lein. Conduit aur garmi ke baad uski capacity 16 A breaker se neeche chali jati hai, aur phir cable breaker se pehle fail hoti hai.

Wiring the circuit

Current capacity depends on how the cable is installed. Derate for conduit, grouping, and ambient temperature above 30°C. Have a licensed electrician confirm the size for your load and run length — or start with the cable size calculator.

The cable for this job

Two-core cable with black outer sheath, cut back to show red and black insulated stranded copper conductors
2.5MM² · 2 CORE · 450/750 V · CU CLASS 5

2.5mm 2 Core Flexible Cable

Class 5 stranded copper, 50/0.25, PVC insulated and sheathed, 450/750 V, drawn on the Pilone line in Lahore. Rated 27 A clipped direct at 30°C.

Factory-direct price
Contact for quote
Message us for today’s rate
WhatsApp for today's rate

This is the price of the wire, not the air conditioner. Cable tracks the daily copper rate, so we quote per metre and per coil on WhatsApp — send the length and your city for the exact figure.

For an AC point take the 3 core version, so the earth is 2.5 mm² too: 2.5mm 3 core flexible cable. On a run past 30 m step up to 4mm 3 core standard cable, or 4mm 2 core cable price where the earth is run separately.

Frequently asked

1 ton AC ke liye kitne mm ka wire chahiye?
2.5 mm² copper — trade code 7/.029 — apne alag 16 A MCB par, aur 3-core lein taake earth bhi 2.5 mm² ho. Agar board se AC point tak 30 meter se zyada faasla hai to 4 mm² (7/.036) lein.
Can I use 1.5mm cable for a 1 ton AC?
No. 1.5 mm² is rated 19.5 A clipped direct at 30°C, only 3.5 A above the 16 A breaker, and that margin disappears once the cable is derated for conduit and summer heat: at a combined correction of 0.75 it becomes 19.5 × 0.75 = 14.6 A, below the breaker protecting it. 2.5 mm² derates to 20.3 A on the same assumption and stays above.
What MCB for a 1 ton AC, and which curve?
16 A, type C, on a circuit of its own. The 16 A rating sits above the 4.5–5.5 A running current with room for the start surge, which as a rule of thumb is two to three times the running current — the LRA on the plate is the real figure. A type C curve rides the inrush; a type B on the same circuit can nuisance-trip at switch-on.
What is the 1 ton inverter AC wire size?
The same 2.5 mm². An inverter compressor ramps up instead of slamming on, so the start surge is smaller, but the cable is sized against the maximum current on the rating plate and that does not shrink. Aggregator answers that recommend 1 mm² for an inverter unit are wrong on a 16 A breaker: 1 mm² two-core is rated 10 A, below the breaker before any derating at all. The mechanism is set out in the inverter AC cable guide.
Do I need a separate circuit for a 1 ton AC?
Yes. Room sockets and lighting are usually wired in 1.5 mm² and share one breaker across several points. Even the smallest AC needs its own run from the distribution board, its own 16 A MCB and its own earth.