4 mm² copper on its own 25 A type C MCB, 3-core, up to about a 25 m run. 6 mm² beyond that.
A 2 ton unit draws 2000–2400 W, which is 9–11 A on Pakistan's 220 V supply. This is the tonnage where 4 mm² starts to run out of room: it clears a 25 A breaker by 11 A on paper, but only by about 2 A once the cable is derated for conduit and summer heat. That margin, not the running current, is what decides 4 against 6.
Read the rating plate on the outdoor unit first — it carries the real maximum current for your model. Failing that: 2000 W ÷ 220 V = 9.1 A and 2400 W ÷ 220 V = 10.9 A, with a start surge on top — as a rule of thumb two to three times the running current, though the LRA on the plate is the number to size against.
| Parameter | Value |
|---|---|
| Appliance | 2 ton split or window air conditioner |
| Power, typical | 2000–2400 W |
| Running current at 220 V | 9.1–10.9 A |
| Start surge | LRA on the plate — rule of thumb, 2–3× running |
| Breaker rating | 25 A MCB |
| Breaker curve | Type C |
| Live and neutral, to 25 m | 4 mm² copper |
| Live and neutral, past 25 m | 6 mm² copper |
| Earth (CPC) | Same size — the third core |
| Cable make-up | 3 core, 450/750 V PVC |
For a 2 ton air conditioner in Pakistan, 4 mm² copper on a dedicated 25 A type C MCB is the size up to about a 25 metre run: the unit draws 9–11 A at 220 V and 4 mm² is rated 36 A clipped direct at 30°C, which clears the breaker by 11 A on paper and by about 2 A once the cable is derated for conduit and summer heat. Past 25 metres, or where the run is enclosed and hot, take 6 mm² — it keeps about 9.5 A of margin on the same assumptions.
So on a 2 ton unit the argument is 4 against 6, and it is decided by margin over a 25 A breaker rather than by the running current — every size in this table carries 11 A without noticing. On a 1.5 ton unit the same argument sits one rung down, at 2.5 against 4.
| Size | 2 loaded cores | 3 loaded cores | Voltage drop | Class 2 strands | Margin on 25 A | Derated margin |
|---|---|---|---|---|---|---|
| 2.5 mm² | 27 A | 24 A | 18 mV/A/m | 7/0.67 | +2 A | −4.8 A |
| 4 mm² | 36 A | 32 A | 11 mV/A/m | 7/0.85 | +11 A | +2.0 A |
| 6 mm² | 46 A | 41 A | 7.3 mV/A/m | 7/1.04 | +21 A | +9.5 A |
| 10 mm² | 63 A | 57 A | 4.4 mV/A/m | 7/1.35 | +38 A | +22.3 A |
The derated column is where the answer lives. Suppose the factors for conduit in a wall and a hot roof space multiply out to 0.75: 2.5 mm² falls to 27 × 0.75 = 20.3 A, under the breaker meant to protect it; 4 mm² falls to 36 × 0.75 = 27 A and holds by 2 A; 6 mm² falls to 46 × 0.75 = 34.5 A and keeps 9.5 A. Two amps is a working margin only if you know the route is cool and open. Take the exact factors for your method and ambient from BS 7671.
A 2 ton unit pulls roughly a third more current than a 1.5 ton, and voltage drop scales straight with current — so the same cable reaches about a third less far.
| Run | 2.5 mm² | 4 mm² | 6 mm² | 10 mm² |
|---|---|---|---|---|
| 10 m | 1.96 V | 1.20 V | 0.80 V | 0.48 V |
| 15 m | 2.94 V | 1.80 V | 1.19 V | 0.72 V |
| 20 m | 3.92 V | 2.40 V | 1.59 V | 0.96 V |
| 25 m | 4.91 V | 3.00 V | 1.99 V | 1.20 V |
| 30 m | 5.89 V | 3.60 V | 2.39 V | 1.44 V |
| 40 m | 7.85 V | 4.80 V | 3.18 V | 1.92 V |
Hold the installation to 3% of 220 V — 6.6 V — and give the AC final circuit half of it, 3.3 V, because the submain from the meter to the board has already spent the rest. On that budget 4 mm² runs 3.3 ÷ 0.120 = 27 m and 6 mm² runs 41 m. So: 4 mm² up to about 25 metres, 6 mm² beyond it — and earlier than that if the run is in conduit through a hot roof, bunched with other circuits, or a second AC point is planned on the same route. A ground-floor board feeding a second-floor outdoor unit is usually already past the line. Check your figure in the voltage drop calculator; the same sum for the smaller unit is in the 1.5 ton AC wire size guide.
4 mm² copper (trade mein 7/.036), apne alag 25 A MCB par, agar board se AC point tak 25 meter tak ka faasla hai. Us se zyada lambai par, ya jab wire garam chhat ke andar conduit mein ja raha ho, to 6 mm² (7/.044) lein. 3-core lein taake earth bhi usi size ka ho.
2.5 mm² (7/.029) is unit ke liye kaafi nahi. Derating ke baad uski capacity 25 A breaker se neeche chali jati hai.
Class 2 stranded copper, 7/0.85, PVC insulated and sheathed, 450/750 V, drawn on the Pilone line in Lahore. Rated 36 A clipped direct at 30°C.
This is the price of the wire, not the air conditioner. Cable tracks the daily copper rate, so we quote per metre and per coil on WhatsApp — send the length and your city for the exact figure.
For an AC point take the 3 core version, so the earth matches: 4mm 3 core standard cable. Past 25 m, or on an enclosed hot route, step up to 6mm 3 core standard cable — also made as 6mm 2 core cable and 6mm 3 core flexible cable.
We draw the copper in Lahore and sell it at the day's rate — no dealer margin. Send the metres and your city and we will price both sizes so you can see the difference: Punjab in 1–2 days, rest of Pakistan in 2–4.