Skip to content
Factory-direct from Lahore · Nationwide delivery in 2–4 days +92 319 4262451 WhatsApp

Backup wiring: size the changeover feed, not the biggest appliance

PILONE CABLES TECHNICAL TEAM

Size the changeover output for the total of every circuit behind it, at the lowest voltage your inverter or generator actually delivers.

On the grid those circuits each had their own cable out of the distribution board; on backup they all pass through one run. A 4,000 W backup load is 4000 ÷ 220 = 18.2 A at full voltage, but 4000 ÷ 190 = 21.1 A when the inverter output sags on a tired battery bank — and constant-power loads keep taking the watts, so the amps rise exactly when the supply weakens. Size against that higher current, and leave headroom on top, because the run usually shares a cupboard or a roof space with the machine that heats it.

Why a circuit runs hotter on backup than on the grid

Householders notice this and assume the inverter is faulty. It is arithmetic, and three things stack up.

One cable does the work of four. A board splits the house into ways: lights, fans, sockets, kitchen, each on its own conductor. Put all of them behind one changeover and its output carries the sum, not the largest. Nothing in the board reports that, because the individual MCBs still see their own small currents.

Constant-power loads draw more current at lower voltage. An inverter air conditioner, a switch-mode charger, a fridge compressor and a motor on a fixed mechanical load all hold their output as the voltage falls, which means the current climbs to compensate. On a battery bank near the end of its charge, the same appliances that drew 18 A at 220 V draw 21 A at 190 V.

The ambient is not 30 °C. Current-capacity tables assume 30 °C air. A generator in a closed store or an inverter on a roof in June sits well above that, and the first metres of the feed sit in it too. Derate for the position — take the correction factors for your own method and ambient from BS 7671 rather than a rule of thumb. If a run already gets hot on backup, work through cable overheating before adding anything else to it.

Changeover feed size by backup load

A changeover feed is sized for the sum of every circuit behind it, not for the largest appliance on it, and the current is worked out at the lowest voltage the inverter or generator actually delivers rather than at 220 V. A 4,000 W backup load is 18.2 A at 220 V and 21.1 A at 190 V, so the cable has to clear 21.1 A before any derating — on BS 7671 reference method C at 30 °C that is 2.5 mm² at 27 A on paper, and 4 mm² at 36 A once the hot enclosure the feed runs through is allowed for.

Add the running watts of everything you intend to put behind the changeover, from the rating plates, then read the row. The load figure is watts, not the inverter's kVA badge — a 3 kVA machine feeding 1,500 W of house needs a 1,500 W feed, and a 3 kVA machine that you intend to load fully needs a 3,000 W one.

Single-phase backup feed, 220 V nominal. Current at 190 V is the same watts divided by a sagging output — illustrative, and the figure to size against for constant-power loads. “Smallest size” is the smallest copper size whose two-core capacity carries the 190 V current with margin left for derating: where a size clears that current by less than about 6 A, the margin is gone the moment the run sits in conduit or a warm cupboard, so the row steps up. “Size we would fit” is one step up again, because this run usually shares a hot enclosure with the machine and because backup loads grow. Both the 6 A working margin and that further step are our judgment, not a standard's requirement. Current capacity per BS 7671 (IEC 60364-5-52), reference method C (clipped direct), 30 °C ambient, copper, PVC; conductor data per IEC 60228. Derate for conduit, bundling and higher ambient. Verify sizing with a licensed electrician for your installation.
Backup loadAt 220 VAt 190 VSmallest sizeSize we would fit
1,000 W4.5 A5.3 A1.5 mm² (19.5 A)2.5 mm²
2,000 W9.1 A10.5 A1.5 mm² (19.5 A)2.5 mm²
3,000 W13.6 A15.8 A2.5 mm² (27 A)4 mm²
5,000 W22.7 A26.3 A4 mm² (36 A)6 mm²
7,500 W34.1 A39.5 A6 mm² (46 A)10 mm²
10,000 W45.5 A52.6 A10 mm² (63 A)16 mm²

The breaker on that feed follows the cable, never the load: its rating must sit under the cable's capacity after derating. Fitting a larger device because the backup feed keeps tripping is the mistake set out on wire size too small.

Worked: a house on a 5 kVA inverter

Take a double-storey house that backs up lights, fans, sockets, the fridge and one inverter AC. Read every figure off its own rating plate; these are typical values to show the method.

Ten ceiling fans at a typical 75 W each is 750 W. Twenty-five LED points at a typical 12 W each is 300 W. A fridge running at a typical 180 W, a television at 100 W, an inverter air conditioner holding a typical 1,200 W in steady state, and 1,500 W of sockets and kitchen appliances actually in use. Total: 750 + 300 + 180 + 100 + 1,200 + 1,500 = 4,030 W.

At 220 V that is 4030 ÷ 220 = 18.3 A. At a sagging 190 V it is 4030 ÷ 190 = 21.2 A. The smallest copper that carries 21.2 A on method C is 2.5 mm² at 27 A — which leaves under 6 A of margin before a single derating factor is applied, in a cupboard that is warmer than 30 °C. The feed we would fit is 4 mm², rated 36 A, three-core so the earth runs at full size: 4mm 3 core standard cable. Add a second AC to the backup later and the same sum lands on 6mm 3 core standard cable.

Length rarely decides this run, because the inverter usually stands within a few metres of the board. Where it does not — a generator in an outhouse, an inverter on the roof of a double-storey — check the drop as well as the heat, using the run-length limits on voltage drop.

The changeover itself, and the one thing never to do

A backup source wired without a proper changeover can energise the incoming supply during an outage. Have a licensed electrician install the changeover and confirm the cable size for your backup load, run length, installation method and ambient — or start with the cable size calculator. We supply and size cable; we do not install or inspect systems.
Cable size calculator Send your backup load

Three other runs, and none of them is this cable

A backup installation is four separate cable decisions and people routinely price only one. The battery leads carry very high current at 12, 24 or 48 V over a short distance, so they are sized by a different rule entirely — that is the inverter-to-battery cable. A solar array feeds the same inverter on DC cable rated to a higher temperature, typically 90 °C for XLPE or XLPO against 70 °C for ordinary PVC, covered on solar panel to inverter cable. The AC feed into a UPS or inverter input is on cable for a UPS or inverter. This page is the last of the four: the AC output of the changeover into the circuits it backs up.

Frequently asked

Load shedding backup ke liye kitne mm ka wire chahiye?
Jitne circuits changeover ke peeche daal rahe hain, un sab ke watt jama karein, phir current nikalein. Takreeban 2,000 W tak 2.5 mm², 3,000 W tak 4 mm², 5,000 W tak 6 mm², aur 7,500 W tak 10 mm² — copper, method C, 30 °C. Yaad rahe ke inverter ki voltage girne par current barhta hai, isliye size hamesha upar wale figure par lein.
What size cable for a changeover switch?
Not the size of the biggest appliance — the size for the sum of every circuit behind the changeover. On the grid those circuits each had their own cable out of the board; on backup they all pass through one run. Add the running watts from the rating plates, divide by the lowest voltage your inverter actually delivers rather than 220 V, and size against that current.
Why does the same wire get hot on the UPS but not on WAPDA?
Two reasons stack. The changeover output carries what the grid split across several ways in the board, so the current through that one run is the total. And constant-power loads — an inverter AC, a switch-mode charger, a motor on a fixed load — draw more current as the voltage sags on a tired battery bank. A 4,000 W backup load is 18.2 A at 220 V and 21.1 A at 190 V.
Can I run the generator into a socket instead of fitting a changeover?
No. A double-ended lead into a socket backfeeds the street through the meter, which is a danger to anyone working on the line during an outage, and it leaves the generator's own output live on exposed pins. It also puts the whole backup load through one socket and its final-circuit cable. A changeover switch that transfers live and neutral together is the only correct connection.
Does the backup circuit need its own earth?
The earth stays continuous. A changeover switches live and neutral between the two sources; it does not switch the earth, and the backed-up circuits keep the installation's existing earthing arrangement. How the inverter or generator frame is bonded depends on the machine and the installation, so that part belongs to the licensed electrician who installs the changeover, not to a cable chart.

Backup feed cable, at the factory rate

We draw the copper in Lahore and sell it at the day's rate — no dealer margin, and the line that made the coil answers the message. Send the backup load in watts, the run length and your city: Punjab in 1–2 days, rest of Pakistan in 2–4.

WhatsApp for a quote