Skip to content
Factory-direct from Lahore · Nationwide delivery in 2–4 days +92 319 4262451 WhatsApp

What size cable from an inverter to the battery?

PILONE CABLES TECHNICAL TEAM

Size it off the bank voltage, not the watts. A 1 kW inverter takes 25 mm² on a 12 V bank, 10 mm² on 24 V and 4 mm² on 48 V — and on 12 V the lead has to stay under about two metres.

The same inverter, the same load, four times the current at the bottom of the range: 1000 ÷ 12 = 83 A against 1000 ÷ 48 = 21 A. Current is what a cable is sized against, which is why this short run is the thickest copper in most houses and why halving the bank voltage costs you two cable sizes and three quarters of your run length. The fuse and the isolator are part of the same decision as the cable.

Why the battery lead is the thickest copper in the house

Power is volts times amps. Hold the power still and drop the voltage, and the current has to rise to make up the difference. A 1 kW load fed from the 220 V mains draws 1000 ÷ 220 = 4.5 A and runs happily on 1.5 mm². Pull that same 1 kW out of a 12 V battery bank and the conductor carries 83 A. Nothing about the load changed. The voltage did, and the copper follows the current.

An inverter-to-battery lead is sized from the direct current it carries, which is the inverter's rated output divided by the bank voltage, plus the 1.25 continuous-duty margin any load that runs for hours deserves. On the three bank voltages sold in Pakistan that gives 104 A of design current for a 1 kW inverter on 12 V, 52 A on 24 V and 26 A on 48 V, which take 25 mm², 10 mm² and 4 mm² copper respectively at 30°C clipped direct. Because 3% of a 12 V bank is only 0.36 V, that 25 mm² lead is out of voltage-drop budget past roughly two metres of route, while the 48 V lead reaches four times as far on a quarter of the copper. Size the cable, the fuse and the isolator together, and have a licensed electrician or your solar installer confirm them for the installation.

One reading note before the table. Inverters are often sold in VA rather than watts, and a 1000 VA unit is not 1000 W — the plate carries both figures, and it is the watt figure and the DC input current that this sum needs. Where the plate prints a maximum DC input current, use that number instead of the division: it already includes the inverter's own conversion loss, which the simple division does not.

Cable size by inverter rating and bank voltage

DC current = inverter rated output ÷ bank voltage; design current adds the 1.25 continuous-duty margin. Conversion loss inside the inverter puts the real draw above the simple division — where the plate gives a DC input current, size on that instead. Current capacity per BS 7671, installation reference method C (clipped direct), 30°C ambient, two loaded conductors; conductor data per IEC 60228. Route is the one-way distance the size covers at 3% of the bank voltage; buy twice it, because the positive and the negative both make the trip. Derate for conduit, bunching and high ambient. Verify the cable, the fuse and the isolator with a licensed electrician.
InverterBankDC currentDesign currentCableCapacityRoute at 3%
1 kW12 V83 A104 A25 mm²112 A2.0 m
1 kW24 V42 A52 A10 mm²63 A3.1 m
1 kW48 V21 A26 A4 mm²36 A5.0 m
2 kW12 V167 A208 Apast 35 mm² — see below
2 kW24 V83 A104 A25 mm²112 A4.0 m
2 kW48 V42 A52 A10 mm²63 A6.3 m
3 kW24 V125 A156 Apast 35 mm² — see below
3 kW48 V63 A78 A16 mm²85 A6.6 m
5 kW48 V104 A130 A35 mm²138 A8.9 m

Two rows have no cable in them, and they are the honest part of this table. A 2 kW inverter on a 12 V bank asks for 208 A and a 3 kW on 24 V asks for 156 A; both are past the 138 A that 35 mm² carries, the top of the DC range we draw. That is not a problem to solve with more copper — it is the bank telling you its voltage is wrong for the load. Take the same 3 kW inverter to a 48 V bank and it drops to 78 A on 16 mm², a fifth of the conductor. Where the bank voltage genuinely cannot move, paralleled conductors and busbar are an installer's design decision, not a size read off a chart.

Why the lead has to be short

On the mains, a volt lost in the cable is under half a percent of 220 V and nobody notices. On a 12 V bank a volt is 8% and the inverter shuts down on low voltage while the batteries are still half full. The percentage budget is the same 3% used everywhere else; the volts it buys you are not.

Same conductor, same current, three bank voltages. Drop per metre = 1.75 mV/A/m × 100 A ÷ 1000. The millivolt figure is the loop value — it already counts the conductor out and the conductor back — so the route is the one-way distance and the cable you buy is twice it. Voltage drop per BS 7671, reference method C, 30°C, copper; conductor data per IEC 60228.
Bank3% budgetDrop per metre on 25 mm² at 100 ARoute that budget buys
12 V0.36 V0.175 V — 1.5% per metre2.1 m
24 V0.72 V0.175 V — 0.73% per metre4.1 m
48 V1.44 V0.175 V — 0.36% per metre8.2 m

Worked through once: a 1 kW inverter on a 12 V bank has a design current of 104 A, and on 25 mm² that costs 1.75 × 104 × 1 ÷ 1000 = 0.182 V for every metre of route. Against a 0.36 V budget that is 2.0 m, and the lead you buy is 4 m — two metres of red and two of black. Move the inverter across the room to a 5 m route and the drop becomes 0.91 V, or 7.6% of the bank. No fuse trips, nothing gets hot, and the system simply underperforms and cuts out early every evening. This is the failure that gets blamed on the batteries.

The fix is almost never a bigger cable. It is a shorter one. Stand the inverter next to the bank, keep the leads as short as the terminals allow, and check any run you cannot shorten in the voltage drop calculator.

Sizing your own run, in four steps

1. Read the plate, not the box

Take the inverter's rated continuous output in watts and its bank voltage. Where a maximum DC input current is printed, use that figure and skip step 2 — it already includes the conversion loss.

2. Divide, then add the margin

Watts ÷ bank volts gives the current. Multiply by 1.25, because an inverter under load holds that current for hours. That answer is the design current.

3. Pick the first size above it

Read the capacity column for a size that carries more than the design current, then derate it for how the lead is actually run — through a conduit, bunched, or in a hot battery room.

4. Check the length last

Multiply mV/A/m × design current × route ÷ 1000 and compare it with 3% of the bank voltage. If it fails, shorten the run before you go up a size.

The fuse, the isolator and the lugs

A battery bank stays live whatever the inverter is doing, and a DC arc does not self-extinguish the way an AC one does. Never break a battery connection under load: open the isolator first. Capacities on this page assume the cable is clipped direct in open air at 30°C, which a battery cabinet is not — derate for the enclosure and the ambient. Have a licensed electrician or your solar installer size the cable, the fuse and the isolator as one design before anything is connected.

The cable for this run

Single-core stranded copper, one length in red and one in black, drawn on the Pilone line in Lahore — plain annealed copper, not tinned. Tinning earns its place in humid coastal service; ours is plain, and we would rather say so than sell you a word.

The same house usually buys DC cable at two points, and only one of them is the battery lead. The panel strings on the roof run in 6 mm², which is where the 6mm dc wire price in pakistan question comes from; a 3kW inverter on a 48 V bank takes 16 mm², so the 16mm dc cable price is the one to ask for on the lead itself. Below those sit the small rungs people ask for by name — 1mm dc wire, 1.5mm dc wire and 2.5mm dc wire — and none of them belongs anywhere near a battery: 2.5 mm² carries 27 A against the 104 A a 1kW inverter on 12 V asks for. Those sizes are panel-tail, controller and 12 V lighting copper, sold as 1mm dc cable, 1.5mm dc cable and 2.5 mm dc cable.

Smaller banks and smaller inverters take the lower rungs: 10mm DC cable for a 1kW unit on 24 V or a 2kW on 48 V, and 4mm DC cable for a 1kW on 48 V. The whole ladder, 0.75mm to 35mm, sits on the DC and solar cable page. Prices track the daily copper rate, so send the size and the metres for the day's figure — and ask which unit the number is in, per metre or per coil, before you compare it with anyone else's.

Frequently asked

Inverter aur battery ke beech kaun sa cable lagta hai?
Motai bank ke voltage se tay hoti hai, watt se nahin. Ek 1 kW inverter 12 V bank par 83 amp kheenchta hai, is liye 25 mm² chahiye; wohi inverter 48 V bank par sirf 21 amp par chalta hai aur 4 mm² kaafi hai. Single-core copper ke do lead lagte hain, ek positive aur ek negative, aur battery ke terminal ke paas fuse zaroori hai.
What size cable for a 1000W inverter to a 12V battery?
25 mm². 1000 ÷ 12 = 83 A, and the 1.25 continuous-duty margin makes that 104 A of design current; 25 mm² carries 112 A clipped direct at 30°C. Keep the run under about two metres, because 3% of 12 V is only 0.36 V. Buy twice the route length — the positive and the negative each make the trip.
Why is battery cable so much thicker than house wiring?
Because a cable is sized against current, and low voltage means high current for the same power. A 1 kW load on the 220 V mains draws 1000 ÷ 220 = 4.5 A. The same 1 kW pulled out of a 12 V bank is 83 A, eighteen times the current, and the copper follows. The watts did not change; the voltage did.
How far can the inverter be from the battery bank?
Not far. On a 12 V bank 3% is 0.36 V, and 25 mm² at 100 A spends 0.175 V in every metre of route — so about two metres, and then the lead is out of budget. A 24 V bank buys four metres on the same copper and a 48 V bank buys eight. Stand the inverter beside the batteries and the problem goes away.
Can I use 7/29 house wire for the battery leads?
No. 7/.029 is about 3 mm², sold as 2.5–3 mm², and it carries 27 A. A 1 kW inverter on a 12 V bank asks for 104 A of design current. Three or four of them twisted together is not a 25 mm² conductor either — it is four hot wires and four loose terminals. Run one single-core conductor of the right size.
Do I need a fuse between the battery and the inverter?
Yes, and it belongs at the battery end, as close to the positive terminal as the installation allows. A battery has no breaker upstream of it: into a short it delivers whatever it can until something melts. Cable size does not protect against that — the fuse does. Size the fuse, the isolator and the cable together with a licensed electrician.

Battery leads, at the factory rate

We draw the copper in Lahore and sell it at the day's rate — no dealer margin, and the line that made the coil answers the message. Send the inverter rating, the bank voltage and the route length: Punjab in 1–2 days, rest of Pakistan in 2–4.

WhatsApp for a quote