Single-core class 5 copper conductor for solar panel and inverter wiring, PVC insulated and rated to 1000 V DC. Made on the Pilone line in Lahore.
Prices track the daily copper rate. Coil and bulk pricing on request.
| Property | Value |
|---|---|
| Conductor | Plain annealed copper, class 5 flexible stranded |
| Nominal area | 4 mm² × 1 core |
| Strand construction | 56 / 0.30 mm |
| Max conductor resistance at 20°C | 4.95 Ω/km |
| Current capacity (two loaded conductors — DC positive and return) | 36 A |
| Voltage drop | 11 mV/A/m |
| Voltage rating | 1000 V DC |
| Insulation / sheath | PVC / PVC, 70°C conductor rating |
| Conductor copper weight | ≈ 35.6 kg/km |
| Reference standards | IEC 60228 (conductors), IEC 60227 (PVC cables) |
On a DC circuit the current goes out on the positive and back on the negative. At this cable's 11 mV/A/m, the volts lost over a one-way run are:
| Current | 10 m run | 20 m run | 30 m run |
|---|---|---|---|
| 15 A | 1.65 V | 3.30 V | 4.95 V |
| 20 A | 2.20 V | 4.40 V | 6.60 V |
| 25 A | 2.75 V | 5.50 V | 8.25 V |
| 30 A | 3.30 V | 6.60 V | 9.90 V |
The same loss matters more at low voltage: 3.30 V over a 10 m run at 30 A is 6.9% of a 48 V battery bank but 0.83% of a 400 V panel string. Check the loss limit your inverter maker gives, or work it through the voltage drop calculator.
| Size | Current capacity | Voltage drop | Copper per 100 m |
|---|---|---|---|
| 4 mm² (this cable) | 36 A | 11 mV/A/m | 3.6 kg |
| 6 mm² | 46 A | 7.3 mV/A/m | 5.3 kg |
Two-conductor DC reference current, BS 7671 method C, 30°C ambient. Same class 5 copper construction in every size.
We quote 4mm DC cable at the day's copper rate and dispatch from the Lahore line. Tell us the construction (PVC or XLPE/PVC) and how many meters you need.