Size the AC cable on the VA rating: 2.5 mm² up to 2000 VA, 4 mm² at 3000 VA, 6 mm² at 5000 VA.
The AC current is the rating divided by 220 V, so a 1000 VA unit is 4.5 A and a 5000 VA unit is 22.7 A, and the same size serves both AC runs — mains into the inverter, and inverter out to the backup board. The thick short cable between the inverter and the battery bank is a different job on a different voltage, and it is sized in the inverter battery cable guide.
Most of the confusion about inverter cable is that one install has three separate runs and people quote one size for all of them. They carry different currents at different voltages.
| Run | What it carries | Voltage | Sized from |
|---|---|---|---|
| Distribution board to inverter | Pass-through load plus the battery charging current | 220 V AC | The ladder below |
| Inverter to backup board | The backup load only | 220 V AC | The ladder below |
| Battery bank to inverter | Many times the AC current | 12, 24 or 48 V DC | Battery cable guide |
The last row is why a 1 kVA UPS sits on a 2.5 mm² AC cable and a battery lead as thick as a thumb: 1000 ÷ 220 = 4.5 A on the AC side, but 1000 ÷ 12 = 83 A off a 12 V battery before losses. Same power, about one eighteenth of the voltage, so about eighteen times the current.
For a single-phase UPS or inverter in Pakistan, take the AC cable each side from the unit's VA rating divided by 220 V: 800–2000 VA is 3.6–9.1 A and runs in 2.5 mm² on a 16 A MCB, 3000 VA is 13.6 A and runs in 4 mm² on a 20 A MCB, and 5000 VA is 22.7 A and runs in 6 mm² on a 32 A MCB. Every row is three-core, because the backup supply has to carry its own earth.
| Inverter rating | AC current at 220 V | Cable | Trade code | Capacity | MCB |
|---|---|---|---|---|---|
| 800 VA | 3.6 A | 2.5 mm² | 7/.029 | 27 A | 16 A |
| 1000 VA | 4.5 A | 2.5 mm² | 7/.029 | 27 A | 16 A |
| 1500 VA | 6.8 A | 2.5 mm² | 7/.029 | 27 A | 16 A |
| 2000 VA | 9.1 A | 2.5 mm² | 7/.029 | 27 A | 16 A |
| 3000 VA | 13.6 A | 4 mm² | 7/.036 | 36 A | 20 A |
| 5000 VA | 22.7 A | 6 mm² | 7/.044 | 46 A | 32 A |
| 7500 VA | 34.1 A | 10 mm² | 7/.052 | 63 A | 40 A |
Work a real one through. A 3000 VA hybrid inverter backing up two rooms: 3000 ÷ 220 = 13.6 A, so 4 mm² on a 20 A MCB. Over a 10 m run from the board to the inverter, 4 mm² drops 11 × 13.6 × 10 ÷ 1000 = 1.50 V. Hold the installation to 3% of 220 V — 6.6 V — and give the final circuit half of it, 3.3 V, since the submain has spent the rest; 1.50 V is comfortably inside that. Derate the table figures for conduit, bundling and summer ambient before you set the breaker: at a 0.75 correction, 4 mm² still holds 27 A against that 20 A MCB.
Class 2 stranded copper, 7/1.04, PVC insulated and sheathed, 450/750 V, drawn on the Pilone line in Lahore. Rated 46 A on two loaded cores clipped direct at 30°C, 7.3 mV/A/m. The size for a 5 kVA inverter each side.
Cable is priced off the day's copper rate, so we quote per metre and per coil on WhatsApp rather than publish a figure that goes stale. Send the metres and your city.
For the smaller ratings: 2.5mm 3 core flexible cable up to 2000 VA, 4mm 3 core cable at 3000 VA, and 10mm 3 core cable at 7500 VA.
We draw the copper in Lahore and sell it at the day's rate — no dealer margin, and the line that made the coil answers the message. Send the inverter rating, the metres and your city: Punjab in 1–2 days, rest of Pakistan in 2–4.