What size wire for LED lights — and why LEDs do not make it thinner

PILONE CABLES TECHNICAL TEAM

1.5 mm² copper — the wire shops sell as 3/.029 — on a 6–10 A lighting MCB. Two cores plus earth for one-way switching, three plus earth for two-way.

An LED fixture is 5–20 W, which is 0.02–0.09 A at 220 V. That is the lightest load in a house and it is not what the cable is sized on. A lighting circuit is sized on the breaker protecting it, on the switch wiring it has to carry, and on what somebody will hang off it in ten years' time.

The lamp does not size the cable

A light point in a Pakistani house is wired in 1.5 mm² copper (3/.029) on a 6–10 A lighting MCB whether the fitting is a 12 W LED downlight or a 60 W filament lamp, because the conductor is chosen for the circuit and its protection rather than for the fitting on the end of it. The arithmetic makes the case on its own: twenty-four 12 W downlights total 288 W, which is 288 ÷ 220 = 1.31 A on a cable rated 19.5 A clipped direct at 30°C. The same twenty-four points in 60 W lamps would have drawn 6.5 A. Both sit comfortably inside 1.5 mm², so switching to LED changes the running current by a factor of five and changes the correct cable by nothing.

One lighting circuit on a 220 V single-phase supply. Voltage drop = mV/A/m × current × one-way run ÷ 1000. Current capacity and voltage drop per BS 7671, reference method C (clipped direct), 30°C ambient, two loaded conductors; conductor and stranding data per IEC 60228. Derate for conduit, grouping and ambient above 30°C. Verify sizing with a licensed electrician for your installation.
ParameterValue
FixtureLED bulb, panel, downlight or strip driver
Power, typical5–20 W each
Current at 220 V0.02–0.09 A each
Circuit cable1.5 mm² copper (3/.029)
Capacity of that cable19.5 A
Voltage drop figure29 mV/A/m
Breaker6–10 A lighting MCB
Cores, one-way switching2 plus earth
Cores, two-way switching3 plus earth
24 downlights at 12 W288 W — 1.31 A
Drop on that circuit over 25 m0.95 V

What actually decides a lighting circuit

Voltage drop is not the limit here and neither is heat. Twenty-four downlights 25 m from the board lose 29 × 1.31 × 25 ÷ 1000 = 0.95 V, well inside any sensible budget. Three other things do the deciding, and none of them is the lamp.

Current capacity depends on how the cable is installed. Derate for conduit, grouping, and ambient temperature above 30°C, and take the correction factors for your own method from BS 7671. Have a licensed electrician confirm the size for the whole circuit, not a single fitting — or start with the cable size calculator.

The cable for this job

Coils of single-core PVC-insulated copper wiring cable in red, black and green-yellow
1.5MM² · SINGLE CORE · 450/750 V · COPPER

1.5mm Single Core Solid Cable

Solid copper conductor, PVC insulated, 450/750 V, drawn on the Pilone line in Lahore. Rated 19.5 A clipped direct at 30°C — the wire light points are pulled in.

Factory-direct price
Contact for quote
Message us for today’s rate
WhatsApp for today's rate

Cable tracks the daily copper rate, so we quote per metre and per coil on WhatsApp. Send the length and your city.

The stranded equivalent is 1.5mm 3/.029 copper cable. For a fixture tail or a pendant, 0.75mm 3 core flexible cable.

Frequently asked

LED lights ke liye kitne mm ka wire chahiye?
1.5 mm² copper, jise dukaan par 3/.029 kehte hain, 6 se 10 A ke lighting MCB par. Ek LED sirf 5–20 W leti hai, yani 0.09 amp tak, magar wire poore circuit ke hisab se chuna jata hai, bulb ke hisab se nahi. Two-way switch ke liye teen core plus earth chahiye.
LEDs use far less power — can I use a thinner wire than before?
No. Twenty-four 12 W downlights draw 1.31 A where the same points in 60 W lamps drew 6.5 A, and 1.5 mm² is the right conductor for both. The cable is chosen to sit above the breaker protecting the circuit and to leave room for points added later, neither of which changes when the lamps do.
Why does the MCB trip the moment a bank of LED lights is switched on?
Because of inrush, not overload. Each driver draws a very short, high current as its capacitors charge, and many drivers switching together can trip a sensitive breaker at that instant while the circuit runs normally afterwards. The fix is the breaker's rating and curve, chosen by your electrician. A thicker cable changes nothing.
How many cores do I need for a two-way light switch?
Three plus earth between the two switch positions, so both switches can pass the live either way. One-way switching needs two plus earth. Deciding this before the conduit goes in is worth more than any argument about conductor size, because the core count is what forces the wall open a second time.