Skip to content
Factory-direct from Lahore · Nationwide delivery in 2–4 days +92 319 4262451 WhatsApp
PILONE · 35MM² · CLASS 2 · SWA ARMOURED

35mm Steel Wire Armoured Cable

Class 2 stranded copper conductor with a galvanized steel wire armour layer between PVC insulation and outer sheath, for underground feeds and industrial runs that need mechanical protection. Made on the Pilone line in Lahore.

Factory-direct price
Contact for quote
Message us for today’s rate
In stock
WhatsApp for today's rate

Prices track the daily copper rate. Coil and bulk pricing on request.

Specifications

Conductor resistance per IEC 60228 class 2. Current capacity and voltage drop per BS 7671, installation reference method C (clipped direct), 30°C ambient, PVC insulation, taken as the nearest published reference for armoured construction. Voltage rating and armour build are typical for PVC/SWA/PVC cable — confirm the exact construction with Pilone Cables. Derate for grouping and higher ambient temperature. Verify sizing with a licensed electrician for your installation.
PropertyValue
ConductorPlain annealed copper, class 2 stranded circular
Nominal area35 mm²
Strand construction19 / 1.53 mm
Max conductor resistance at 20°C0.524 Ω/km
Current capacity, 2 loaded conductors138 A
Current capacity, 3 loaded conductors119 A
Voltage drop1.25 mV/A/m
Voltage rating600/1000 V (typical)
Insulation / sheathPVC / PVC, 70°C conductor rating
ArmourGalvanized steel wire armour (SWA) between inner and outer PVC sheath
Conductor copper weight≈ 311.2 kg/km
Typical useDistribution feeders and machine connections in industrial plants; larger underground feeds between buildings
Current capacity depends on how the cable is installed. Derate for grouping and high ambient temperature. Have a licensed electrician confirm the size for your load and run length — or start with the cable size calculator.

How far a 35 mm² run can go

Voltage drop sets the longest run before lights dim and motors struggle. BS 7671 allows 3% on lighting circuits and 5% on other circuits; on a 230 V single-phase supply that is 6.9 V and 11.5 V. At this cable's 1.25 mV/A/m, the longest one-way run is:

Longest one-way run for 35 mm² armoured cable, single-phase 230 V, at 1.25 mV/A/m. Loads shown up to the cable's 138 A capacity. Three-phase circuits allow longer runs.
LoadLighting circuit (3%)Other circuits (5%)
63 A87 m146 m
80 A69 m115 m
100 A55 m92 m
125 A44 m73 m

Check your own load and length with the voltage drop calculator. Every 100 m of each core holds 31.1 kg of copper; cable is priced from the day's copper rate, which is why each size up costs more.

Next size up or down

Armoured cable sizes either side of 35 mm², same reference conditions as the specification table.
SizeCurrent capacity, 2 loadedVoltage dropCopper per 100 m of core
25 mm²112 A1.75 mV/A/m22.2 kg
35 mm² (this cable)138 A1.25 mV/A/m31.1 kg
70 mm²213 A0.63 mV/A/m62.2 kg

Other armoured sizes

Current capacity with two loaded conductors, BS 7671 reference method C, 30°C ambient. Same class 2 steel wire armoured construction in every size.

Frequently asked

What is the price of 35mm armoured cable in Pakistan?
The price moves with the daily copper rate, so we quote it the day you order. We sell factory-direct from Lahore, with no dealer margin on top. Message us on WhatsApp for today's price per meter.
What is 35mm armoured cable used for?
Distribution feeders and machine connections in industrial plants, and larger underground feeds between buildings. It carries 138 A with two loaded conductors on method C, and 119 A with three loaded conductors.
Can I get 35mm armoured cable delivered?
Yes. We dispatch from Lahore — courier for single coils, transport for bulk. Punjab arrives in 1–2 days, the rest of Pakistan in 2–4 days. See delivery details.

Send us the length and your city

We quote 35mm armoured cable at the day's copper rate and dispatch from the Lahore line. Tell us the run length and how many meters you need.