Tinned-copper XLPE/PVC solar DC cable for rooftop and ground-mount PV systems. Made on our own line in Lahore and delivered anywhere in Faisalabad in 1–2 days — at the day's factory rate, with no dealer margin on top.
Class 5 stranded copper conductor per IEC 60228. Current capacity and voltage drop per BS 7671, installation reference method C (clipped direct), 30°C ambient, two loaded conductors, PVC-reference insulation figures. Solar DC cable insulation (XLPE) is rated to 90°C, which typically allows a higher continuous rating than the PVC figures shown — confirm DC circuit sizing with your inverter or panel manufacturer.
Size
Current capacity
Voltage drop
4 mm²
36 A
11 mV/A/m
6 mm²
46 A
7.3 mV/A/m
10 mm²
63 A
4.4 mV/A/m
16 mm²
85 A
2.8 mV/A/m
25 mm²
112 A
1.75 mV/A/m
35 mm²
138 A
1.25 mV/A/m
Match the size to the string current and the run length — voltage drop on a long DC run costs real solar yield. Confirm the size for your array with your installer or a licensed electrician, or start with the cable size calculator.
Get today's rate for Faisalabad
Cable prices move with the daily copper rate, so we quote on the day. Send the size, the core count, and the length you need — we reply with the factory price and dispatch from Lahore.