EV charger far from the board: how run length changes the cable

PILONE CABLES TECHNICAL TEAM · UPDATED 21 SEPTEMBER 2026

A cable can carry the current comfortably and still be the wrong size, because the volts ran out first.

Voltage drop is current × route length × the tabulated mV/A/m, divided by 1000, and BS 7671 allows 5% on a power circuit — 11 V on a 220 V supply, 20 V on 400 V. At the 31.8 A a 7 kW single-phase charger draws, 4 mm² spends that 11 V at about 31 m and 6 mm² at about 47 m. Garages, gates and back walls are often further from the board than people estimate, which is why distance decides the cable on EV jobs more often than the load does.

The arithmetic, and the budget

Two numbers and one multiplication. The current is the charger's draw. The mV/A/m figure is a property of the cable size, tabulated per BS 7671. Multiply them by the one-way route length in metres, divide by 1000, and you have the volts lost in the run.

The budget is 5% of the supply voltage on a power circuit: 11 V on 220 V single phase, 20 V on 400 V three phase. Note that single-phase circuits get roughly half the budget in absolute volts, which is why long single-phase charger runs are the ones that bite. Measure the route rather than the straight line — cable follows walls, goes up and over doorways, and takes the long way round a car port.

Reach at a 7 kW single-phase charging current of 31.8 A on a 220 V supply, two loaded conductors. Route length at which voltage drop reaches the 11 V that BS 7671's 5% allows, calculated as 11 / (31.8 x mV/A/m / 1000). Voltage drop and current capacity per BS 7671 reference method C (clipped direct), 30°C ambient; stranding per IEC 60228. Current capacity shown before derating. Verify sizing with a licensed electrician.
SizeCurrent capacityVoltage dropReach at 31.8 A
2.5 mm²27 A18 mV/A/m19 m
4 mm²36 A11 mV/A/m31 m
6 mm²46 A7.3 mV/A/m47 m
10 mm²63 A4.4 mV/A/m79 m
16 mm²85 A2.8 mV/A/m123 m

The 2.5 mm² row is there for completeness rather than as an option — its 27 A capacity is already below the 31.8 A the charger draws, so it fails the current check before distance is even considered.

The same run on three phase

An 11 kW three-phase charger draws 15.9 A per phase against a 20 V budget, and both of those work in its favour. Half the current and nearly double the budget means roughly four times the reach for the same cable size.

Reach at an 11 kW three-phase charging current of 15.9 A per phase on a 400 V supply, three loaded conductors. Route length at which voltage drop reaches the 20 V that BS 7671's 5% allows, calculated as 20 / (15.9 x mV/A/m / 1000). Per BS 7671 reference method C (clipped direct), 30°C ambient; stranding per IEC 60228. Current capacity shown before derating. Verify sizing with a licensed electrician.
SizeCurrent capacityVoltage dropReach at 15.9 A
2.5 mm²24 A18 mV/A/m70 m
4 mm²32 A11 mV/A/m114 m
6 mm²41 A7.3 mV/A/m172 m
10 mm²57 A4.4 mV/A/m286 m

A 22 kW three-phase charger draws 31.8 A per phase — the same current as the 7 kW single-phase unit, but against the larger 20 V budget. On 6 mm² that gives 20 ÷ (31.8 × 7.3 ÷ 1000) = 86 m of reach, against 47 m for the same cable and the same current on a 220 V supply. The supply voltage, not the charger, is doing most of the work.

Measure the route, not the distance

Every figure on this page is driven by one input people habitually underestimate. Voltage drop is calculated from the metres of cable installed, not from how far apart the two ends look. Cable does not travel diagonally across a lawn: it follows walls, climbs to go over a doorway, drops to enter the board, and goes the long way round anything it cannot pass through.

Walk the route with a tape and add the verticals. A charge point that sits 15 m from the board across open ground is regularly 25 m of installed cable once the path is real, and at 31.8 A on 4 mm² that is the difference between 5.2 V and 8.7 V of drop. Add a little for the slack at each end and for the drop into the enclosure. It costs nothing to measure generously at this stage and a great deal to discover the shortfall after the cable is clipped up.

Outdoors is a different question from long.

If the route crosses a yard, a driveway or anywhere a shovel or a trolley can reach it, the size of the conductor is not the protection that matters. That is a case for armoured cable, where steel wire armour does the protecting rather than the PVC sheath. Buried and outdoor runs also sit in different thermal conditions from a wall-clipped cable, which changes the derating again.

When the run is genuinely long

Detached garages, farm gates, boundary walls and plot-corner parking all produce runs that make the tables above look optimistic. Three approaches, in the order worth considering them.

Move the board, not the cable

A sub-board nearer the charge point shortens the high-current run and often costs less than the copper it saves, especially above 40 m.

Go up a size

Each step up roughly halves the volts lost per metre. It is the simplest answer and, on a single run, frequently the cheapest.

Commission lower

Most chargers can be set below their maximum. Less current is less drop, and an overnight charge rarely needs the full rate.

What does not work is accepting the drop. A charger fed below its expected voltage does not simply charge more slowly in a tidy way — the cable is dissipating the difference as heat along its whole length, continuously, for the hours the session lasts. That is the failure mode worth designing out rather than living with.

Both checks have to pass and the larger size wins: the cable must carry the current after derating for installation method, ambient temperature and grouping, and it must hold voltage drop inside 5% over the real route. Work yours through the voltage drop calculator and the cable size calculator, follow the charger manufacturer's instructions, and have a licensed electrician confirm the design before the circuit is energised.

Frequently asked

How far can an EV charger be from the distribution board?
It depends on the cable size and the charging current. At the 31.8 A a 7 kW single-phase charger draws, 4 mm2 reaches about 31 m and 6 mm2 about 47 m before voltage drop uses the 11 V that 5% of 220 V allows. On a three-phase supply the reach is far greater, because the current per conductor is lower and the budget is 20 V. Measure the route the cable will actually follow, not the straight line.
What cable do I need for an EV charger 30m away?
At 30 m and 31.8 A, 4 mm2 drops 31.8 x 30 x 11 / 1000 = 10.5 V, which is just inside the 11 V budget with almost nothing spare, and 6 mm2 drops 7.0 V. Both also have to pass the current check after derating for conduit, ambient temperature and grouping. That combination is exactly why 30 m runs are usually taken up a size, and why the final call belongs to a licensed electrician.
Does voltage drop matter for EV charging?
More than for most circuits, because the charger holds near-full current for hours rather than minutes. The volts lost in the cable are dissipated as heat along the whole run for the entire session. A drop that would be unremarkable on a short intermittent load becomes a continuous heating problem on a charging circuit.
Can I use a longer cable and a smaller size to save money?
No. Longer runs need larger conductors, not smaller ones, because voltage drop accumulates with distance. Each step up in size roughly halves the volts lost per metre. If the copper cost is the obstacle, a sub-board nearer the charge point or a lower commissioned charging current are the two honest ways to reduce it.