Skip to content
Factory-direct from Lahore · Nationwide delivery in 2–4 days +92 319 4262451 WhatsApp

Voltage drop table — mV/A/m for every copper cable size

BY PILONE CABLES TECHNICAL TEAM

Volt drop = mV/A/m × amps × metres ÷ 1000. Three-phase: multiply the answer by 0.866.

Read the mV/A/m figure for your size off the table below, multiply by the current the circuit actually carries and by the one-way run in metres, then divide by 1000 to get volts. Hold the result inside 2.5% of the supply — 5.75 V on a 230 V single-phase supply, 10.00 V on a 400 V three-phase supply. A 4 mm² run carrying 8 A over 25 m drops 11 × 8 × 25 ÷ 1000 = 2.2 V, well inside the budget.

The voltage drop formula

Voltage drop in a copper cable is its mV/A/m figure multiplied by the current in amps and by the one-way run in metres, divided by 1000 to give volts; for a three-phase circuit the result is multiplied by 0.866. The mV/A/m figures published here are BS 7671 (IEC 60364-5-52) values for PVC-insulated copper conductors at their 70°C operating temperature, reference method C, clipped direct, 30°C ambient, and Pilone Cables sizes against a 2.5% design target — 5.75 V on a 230 V single-phase supply, 10.00 V on a 400 V three-phase supply.

Every term in the formula, and where its value comes from. Conductor data per IEC 60228; volt drop and current capacity per BS 7671 (IEC 60364-5-52), reference method C (clipped direct), 30°C ambient, PVC, copper. Verify sizing with a licensed electrician for your installation.
TermWhat it isWhere you get it
mV/A/mMillivolts lost per amp carried, per metre of runThe table below, by size
AmpsThe current the circuit actually carries, not the breaker ratingWatts ÷ volts, or the rating plate
MetresOne-way run, along the route the cable takesMeasured, not paced — add a metre at each end
÷ 1000Converts millivolts to voltsFixed
× 0.866Three-phase correction, √3 ÷ 2Applied only on three-phase circuits
BudgetThe volts you are allowed to lose2.5% of supply: 5.75 V at 230 V, 10.00 V at 400 V

Two things the formula does not ask for, and both catch people out. It does not ask for the return length — the mV/A/m figure already counts the current going out and coming back, so measure one way only. And it does not ask for the breaker size. A 63 A breaker on a circuit that draws 20 A drops the volts of 20 A, not 63 A.

Voltage drop table: mV/A/m by copper size

This is the reference table. The single-phase column is the published figure; the three-phase column is that figure × 0.866. The ready-reckoner column is there for a quick sanity check in the field: it is the volts this size loses at 10 A over 10 m.

Copper conductors, PVC insulated, 70°C conductor temperature. Volt drop and current capacity per BS 7671 (IEC 60364-5-52), reference method C (clipped direct), 30°C ambient, no derating applied; DC resistance at 20°C per IEC 60228 class 2. Two loaded conductors for single-phase, three for three-phase. Derate the capacity for conduit, bunching and ambient above 30°C. Verify sizing with a licensed electrician for your installation.
SizeSingle-phaseThree-phaseAt 10 A over 10 mCapacity, 2 loadedCapacity, 3 loadedResistance, class 2
0.75 mm²62 mV/A/m53.7 mV/A/m6.20 V6 A6 A
1 mm²44 mV/A/m38.1 mV/A/m4.40 V10 A10 A
1.5 mm²29 mV/A/m25.1 mV/A/m2.90 V19.5 A17.5 A12.1 Ω/km
2.5 mm²18 mV/A/m15.6 mV/A/m1.80 V27 A24 A7.41 Ω/km
4 mm²11 mV/A/m9.53 mV/A/m1.10 V36 A32 A4.61 Ω/km
6 mm²7.3 mV/A/m6.32 mV/A/m0.73 V46 A41 A3.08 Ω/km
10 mm²4.4 mV/A/m3.81 mV/A/m0.44 V63 A57 A1.83 Ω/km
16 mm²2.8 mV/A/m2.42 mV/A/m0.28 V85 A76 A1.15 Ω/km
25 mm²1.75 mV/A/m1.52 mV/A/m0.175 V112 A96 A0.727 Ω/km
35 mm²1.25 mV/A/m1.08 mV/A/m0.125 V138 A119 A0.524 Ω/km
50 mm²0.93 mV/A/m0.81 mV/A/m0.093 V168 A144 A0.387 Ω/km
70 mm²0.63 mV/A/m0.55 mV/A/m0.063 V213 A184 A0.268 Ω/km
95 mm²0.46 mV/A/m0.40 mV/A/m0.046 V258 A223 A0.193 Ω/km
120 mm²0.36 mV/A/m0.31 mV/A/m0.036 V299 A259 A0.153 Ω/km

The capacity columns are on the table for one reason: a run that passes on volt drop can still be over the conductor. Both checks have to pass, and on short runs it is capacity that decides the size while on long runs it is volt drop. 0.75 mm² and 1 mm² are flexible-cord sizes and IEC 60228 class 2 solid or stranded resistance is not published for them here, so those two rows carry a dash. The capacity figures here are the base method C values before any derating; the corrected ones, for conduit, bunching and Pakistani summer ambient, are on the cable current capacity chart.

Worked example 1 — single phase, 230 V

An air conditioner point on a house circuit. 4 mm² copper, 8 A running current, 25 m from the distribution board to the isolator.

1. Read the figure

4 mm² single-phase is 11 mV/A/m.

2. Multiply

11 × 8 × 25 = 2200 mV. Divide by 1000: 2.2 V.

3. Compare with the budget

2.2 ÷ 230 = 0.96%, against a 5.75 V budget. It passes with 3.55 V spare.

Because it passes with room to spare, the useful next question is how far that size could go before the budget runs out: 5750 ÷ (11 × 8) = 65 m at this current. Below 4 mm² the arithmetic tightens fast. The same 8 A over the same 25 m on 2.5 mm² gives 18 × 8 × 25 ÷ 1000 = 3.6 V, which still passes, but its ceiling is 5750 ÷ (18 × 8) = 40 m. On 1.5 mm² it is 29 × 8 × 25 ÷ 1000 = 5.8 V — over budget at 25 m, and that size is under the 20 A breaker such a circuit usually carries anyway. The 1.5 ton AC cable guide works the same circuit through in full.

Worked example 2 — three phase, 400 V, and the 0.866 factor

A three-phase submain. 25 mm² four-core copper, 60 A per phase, 45 m from the main switch to the sub-board.

1. Read the figure

25 mm² single-phase is 1.75 mV/A/m. Three-phase: 1.75 × 0.866 = 1.52 mV/A/m.

2. Multiply

1.52 × 60 × 45 = 4104 mV. Divide by 1000: 4.1 V.

3. Compare with the budget

4.1 ÷ 400 = 1.0%, against a 10.00 V budget. It passes with 5.9 V spare.

Where does 0.866 come from? On a balanced three-phase circuit the drop that matters is line to line, and the phase-to-phase relationship puts a factor of √3 into the numerator and 2 into the denominator: √3 ÷ 2 = 0.866. In plain terms, three-phase distribution moves the same power with less volt drop than single phase, which is why long factory and farm runs go three-phase. Check the capacity as well as the drop: at 60 A this cable is inside the 96 A three-loaded-conductor rating before derating, and the run could reach 10000 ÷ (1.52 × 60) = 110 m before the budget is spent. The cable itself is our 25mm 4 core standard cable; the sizing context sits on 3 phase cable size.

What the 2.5% budget means in volts

A percentage is not a number you can check a cable against. Convert it to volts first, then the arithmetic above either fits inside it or does not.

Budget in volts = percentage × supply voltage. Pilone Cables and the voltage drop calculator size against the 2.5% row. Design standards commonly allow more than that — a tighter target leaves room for the submain you did not measure. Verify the limit that applies to your installation with a licensed electrician.
Budget230 V single-phase400 V three-phaseUse
2.5%5.75 V10.00 VOur design target for a final circuit
3%6.90 V12.00 VCommonly applied to lighting circuits
5%11.50 V20.00 VCommonly applied to other loads, whole installation

The budget is spent once, across the whole path from the meter to the appliance, not once per cable. If the submain from the meter to the distribution board has already used 2 V, the final circuit has 3.75 V left of a 5.75 V allowance, not the full amount. On a long plot — a kanal house with the meter at the boundary wall and the board inside — the submain can eat most of it before a single room is wired, which is why the meter to distribution board cable is sized on drop rather than on load.

Two consequences worth stating plainly. Lighting shows the drop first: filament and older fittings dim visibly, and an LED driver may hum or flicker. Motors show it worst: a motor at reduced voltage draws more current to hold its torque, gets hotter, and the extra current makes the drop worse still. That feedback loop is what burns out a water pump at the far end of a long run, and it is covered on voltage drop problems.

Longest single-phase run each size can hold

The formula rearranged. Longest run in metres = 5750 ÷ (mV/A/m × amps). Find your current across the top, your size down the side, and read the metres where they meet.

Metres of one-way run at the 2.5% budget on a 230 V single-phase supply (5.75 V). A dash means the current is above that size's capacity clipped direct at 30°C, so the size fails on the conductor before volt drop is even reached. Copper, PVC, BS 7671 reference method C, 30°C, no derating applied for conduit, bunching or ambient. Verify sizing with a licensed electrician for your installation.
Size10 A16 A20 A32 A40 A63 A100 A
0.75 mm²
1 mm²13 m
1.5 mm²20 m12 m
2.5 mm²32 m20 m16 m
4 mm²52 m33 m26 m16 m
6 mm²79 m49 m39 m25 m20 m
10 mm²131 m82 m65 m41 m33 m21 m
16 mm²205 m128 m103 m64 m51 m33 m
25 mm²329 m205 m164 m103 m82 m52 m33 m
35 mm²460 m288 m230 m144 m115 m73 m46 m
50 mm²618 m386 m309 m193 m155 m98 m62 m
70 mm²913 m570 m456 m285 m228 m145 m91 m
95 mm²1250 m781 m625 m391 m312 m198 m125 m
120 mm²1597 m998 m799 m499 m399 m254 m160 m

Read the 2.5 mm² row honestly and a common Pakistani wiring habit falls apart. At 20 A it holds 16 m. A socket ring or a geyser point at the far corner of a 10 marla house is past that before the cable leaves the corridor, and the answer is 4 mm² or 6 mm², not a bigger breaker. A bigger breaker protects nothing about volt drop; it only lets the same thin conductor carry more current and lose more volts.

Longest three-phase run at the 10 V budget

Same rearrangement, three-phase figures: longest run = 10000 ÷ (mV/A/m × 0.866 × amps). Currents are per phase.

Metres of one-way run at the 2.5% budget on a 400 V three-phase supply (10.00 V), balanced load. A dash means the current is above that size's three-loaded-conductor capacity clipped direct at 30°C. Copper, PVC, BS 7671 reference method C, 30°C, no derating applied. Verify sizing with a licensed electrician for your installation.
Size20 A32 A40 A63 A100 A160 A200 A
4 mm²52 m33 m
6 mm²79 m49 m40 m
10 mm²131 m82 m66 m
16 mm²206 m129 m103 m65 m
25 mm²330 m206 m165 m105 m
35 mm²462 m289 m231 m147 m92 m
50 mm²621 m388 m310 m197 m124 m
70 mm²916 m573 m458 m291 m183 m115 m
95 mm²1255 m784 m628 m398 m251 m157 m126 m
120 mm²1604 m1002 m802 m509 m321 m200 m160 m

Sizes below 4 mm² are left off this table because a three-phase circuit rarely runs that small and the rows would be dashes. Note what the two tables say side by side: 25 mm² at 63 A reaches 52 m single-phase and 105 m three-phase. Same copper, double the reach, because the drop factor and the supply voltage both work in your favour.

Check these figures against IEC 60228 yourself

A volt-drop table with no derivation is a table you have to trust. This one you can audit. Take the IEC 60228 class 2 DC resistance at 20°C, double it because the current travels out and back, then multiply by about 1.20 because a PVC cable at its 70°C rating has around 20% more resistance than the same copper at 20°C. The result lands on the published mV/A/m figure across the whole ladder.

Column 2 is IEC 60228 class 2 DC resistance at 20°C. Column 3 doubles it for the out-and-back path. Column 4 applies the 1.20 factor for a conductor at its 70°C PVC rating. Column 5 is the BS 7671 figure published in the table above. The two right-hand columns agree the whole way down to within the rounding of the published figure. At the largest sizes a resistance-only sum stops being the whole answer in any case, because conductor reactance starts to count alongside resistance.
SizeR at 20°C× 2 (out and back)× 1.20 (70°C)Published mV/A/m
1.5 mm²12.1 Ω/km24.2029.0429
2.5 mm²7.41 Ω/km14.8217.7818
4 mm²4.61 Ω/km9.2211.0611
6 mm²3.08 Ω/km6.167.397.3
10 mm²1.83 Ω/km3.664.394.4
16 mm²1.15 Ω/km2.302.762.8
25 mm²0.727 Ω/km1.4541.741.75
35 mm²0.524 Ω/km1.0481.261.25
50 mm²0.387 Ω/km0.7740.930.93
70 mm²0.268 Ω/km0.5360.640.63
95 mm²0.193 Ω/km0.3860.460.46
120 mm²0.153 Ω/km0.3060.370.36

That is the whole reason the mV/A/m figure is not simply twice the resistance you find on a datasheet. A cold conductor and a working conductor are not the same conductor. It is also the check to run on any volt-drop chart you are handed: if its figures come out near twice the 20°C resistance with no temperature allowance, it is under-reporting the drop by about a fifth. Conductor resistance and stranding for our own goods are published on every product page — for instance 10mm 3 core standard cable and 16mm 4 core standard cable.

The supply is 230 V on paper and less on the street

The budget column is worked at 230 V because that is the declared single-phase voltage the tables are built on. Pakistani supply is not always that. On a 220 V measurement the same 2.5% is 5.50 V, and a 5.75 V drop that was exactly 2.5% becomes 2.61%. When WAPDA or K-Electric supply sags to 190 V at peak, that same 5.75 V is 3.03% of what the appliance actually sees.

There is a second effect, and it is the one that matters. A constant-power load draws more current at lower voltage: 1800 W at 230 V is 7.8 A, at 190 V it is 9.5 A. More current through the same cable means more drop, on top of the sag that started it. So a sagging supply and a thin cable compound each other. What that does not mean is that thicker copper fixes a bad supply. Take that same 9.5 A over a 20 m run: 2.5 mm² drops 18 × 9.5 × 20 ÷ 1000 = 3.42 V and 4 mm² drops 11 × 9.5 × 20 ÷ 1000 = 2.09 V, so the bigger cable hands back 1.33 V at the terminals against the 40 V the street took. Size the cable properly for the run, and treat street voltage as a separate problem with a separate solution.

Volt drop is one check of several, and passing it does not make a cable safe. It says nothing about current capacity after derating for conduit, bunching or a 45°C roof void, nothing about earth fault loop impedance, and nothing about disconnection time. Take the correction factors for your own installation method from BS 7671, and have a licensed electrician confirm the size, the breaker and the earthing before you buy.

Frequently asked

What is the voltage drop formula for a cable?
Volts lost = mV/A/m × amps × metres ÷ 1000. Take the mV/A/m figure for the size from the table on this page, multiply by the current the circuit carries and by the one-way run length, then divide by 1000. On a three-phase circuit multiply the answer by 0.866. Compare the result against 2.5% of the supply: 5.75 V at 230 V, 10.00 V at 400 V.
Cable ka voltage drop kaise nikalte hain?
Size ka mV/A/m number lein, usay current (amp) aur run ki lambai (meter) se multiply karein, phir 1000 se divide karein — jawab volt mein aa jayega. Misal ke tor par 4 mm² par 8 amp, 25 meter: 11 × 8 × 25 ÷ 1000 = 2.2 volt. Three-phase ho to jawab ko 0.866 se multiply karein. Limit 2.5% hai — 230 volt par 5.75 volt.
Why is the three-phase voltage drop multiplied by 0.866?
Because 0.866 is the square root of 3 divided by 2. On a balanced three-phase circuit the drop that matters is measured line to line, and that relationship produces the factor. The practical result is that three-phase carries the same power over a longer run for the same cable: 25 mm² at 63 A reaches 52 m single-phase and 105 m three-phase on the same 2.5% budget.
Is the voltage drop limit 5.75 V or 10 V?
Both, on different supplies. 2.5% of a 230 V single-phase supply is 5.75 V; 2.5% of a 400 V three-phase supply is 10.00 V. The budget is spent once across the whole path from the meter to the appliance, not once per cable, so if the submain has already used 2 V the final circuit has 3.75 V left, not the full 5.75 V.
Does voltage drop depend on the breaker size?
No. The formula uses the current the circuit actually carries, not the rating of the MCB protecting it. A 20 A load on a 63 A breaker drops the volts of 20 A. Fitting a larger breaker never reduces volt drop — it only allows more current through the same conductor, which increases the drop. The fix for a long run is a bigger cable.
Is mV/A/m the same as the conductor's resistance?
Close, but not the same. The published mV/A/m figure is roughly twice the IEC 60228 resistance at 20 °C, multiplied by about 1.20. Doubling accounts for the current going out and coming back; the 1.20 accounts for a PVC cable running at its 70 °C rating, where copper resistance is around a fifth higher than cold. 2.5 mm² class 2 is 7.41 Ω/km, and 7.41 × 2 × 1.20 = 17.78, against a published 18 mV/A/m.
My supply reads 220 V, not 230 V. Does the table still work?
The mV/A/m figures do not change with supply voltage — they depend on the conductor, not the source. What changes is the budget and the current. 2.5% of 220 V is 5.50 V rather than 5.75 V, and a constant-power load draws more amps at lower volts, which increases the drop. Work the volts out with the table, then compare against 2.5% of the voltage you actually measure.
What size cable do I need for a 60 metre run?
It depends on the current, and the longest-run table on this page answers it directly. At 20 A single-phase, 60 m needs 10 mm² — 6 mm² holds 39 m and 10 mm² holds 65 m. At 32 A the same 60 m needs 16 mm². Enter your own load and length in the voltage drop calculator and have a licensed electrician confirm it.

Got the size the run needs?

We draw the copper in Lahore and quote the day's factory rate — no dealer margin. Send the size, the total metres and your city: Punjab in 1–2 days, rest of Pakistan in 2–4.

WhatsApp for today's rate