Skip to content
Factory-direct from Lahore · Nationwide delivery in 2–4 days +92 319 4262451 WhatsApp

Cable for tube wells and farms

PILONE CABLES TECHNICAL TEAM

A tube well is two cables, and only one of them is sized off the pump. The drop cable goes down the bore. The feeder from the meter to the well head is the one that costs money, and its size is set by the distance, not by the horsepower.

A farm load is small and far away — that is the whole electrical shape of it. A pump drawing 30 A is inside the capacity of 6 mm² copper, but put the well 150 metres out across the fields and 6 mm² loses 32.9 V on the way there. The cable that reaches is three or four sizes above the cable that carries. Work from the current printed on the pump's plate and the one-way metres: a 30 A pump 150 m out lands on 35 mm² for a 3% budget, or 25 mm² if 5% is acceptable.

The two cables on a tube well

Farm buyers ask for "tube well cable" as one thing and get quoted for one thing, then find on installation day that they needed two. They are different products with different problems.

The runs on an ordinary tube well or farm supply, and what decides each one. The submersible drop cable is specified by the pump maker for the pump and the depth — take it from the pump documentation, not from a general cable chart. Verify the whole installation with a licensed electrician.
RunWhat it isWhat decides the sizeWhere to look
Bore to pump, submergedSubmersible drop cable, permanently in waterThe pump maker's specification for that motor and that depthPump documentation
Meter or transformer to well headField feeder, usually buried or on polesOne-way distance — voltage drop, not currentThe table below
Well head panel to the motorShort tail from the starterFull-load current on the plateSubmersible pump cable
Farmhouse, sheds, chaff cutter, fansOrdinary distribution off the same supplyConnected load and diversityCable size calculator
Buried section of any of the aboveCable in a trench across worked groundArmour for the route, and a lower buried ratingUnderground cable

Two of those rows deserve a warning. Ploughing, levelling and new bunds move a lot of earth on a farm, so a buried field feeder wants armour and a recorded route far more than a house feed does. And the drop cable inside the bore is not a place to improvise: it lives in water for years, and the pump maker's specification is the specification.

The field run is what sets the size

Voltage drop is millivolts per amp per metre, times the current, times the one-way run. On a farm all three numbers work against you: the run is long, the pump is a motor that does not tolerate low volts, and rural supplies are often already sagging before the cable takes its share. This is the same 30 A pump at three ordinary distances.

Volts lost one way on a 30 A single-phase pump feeder. Figure = mV/A/m × 30 A × run ÷ 1000. Reference budgets on a 220 V supply: 3% = 6.6 V, 5% = 11 V. Voltage drop and current capacity per BS 7671 reference method C (clipped direct), 30°C ambient, copper, PVC; conductor data per IEC 60228. A buried run is on a different reference method and rates lower. Verify sizing with a licensed electrician for your installation.
SizeCapacity, 2 coresAt 100 mAt 150 mAt 200 m
6 mm²46 A21.9 V32.9 V43.8 V
10 mm²63 A13.2 V19.8 V26.4 V
16 mm²85 A8.4 V12.6 V16.8 V
25 mm²112 A5.25 V7.88 V10.5 V
35 mm²138 A3.75 V5.63 V7.5 V
50 mm²168 A2.79 V4.19 V5.58 V

Every size in that table carries 30 A without breathing hard — the smallest of them is rated 46 A. Not one of the columns is about capacity. Read across the 100 m column and 25 mm² is the first size inside 6.6 V; at 200 m nothing under 50 mm² holds that budget, and 35 mm² at 7.5 V passes only if you accept 5%. That is the farm sizing problem in one table, and it is why a shop that quotes on the pump rating alone quotes too small.

A motor at the end of an undersized feeder draws more current, runs hotter and trips its overload, and the starter usually gets blamed. Measure the voltage at the well head with the pump running, not at the meter. Check your own length in the voltage drop calculator, and have a licensed electrician confirm the size, the protection and the earthing for your installation.

Worked example: a 28 A pump, 160 m out

Single-phase supply, the plate on the pump reads 28 A full load, and the well head is 160 metres from the meter down the edge of the field. Take the plate's current, not the horsepower on the sticker.

Capacity. 16 mm² is 85 A with two loaded cores, clipped direct at 30°C. Even after a substantial derating for a buried run it is far above 28 A. On current alone the job is finished at 16 mm², or smaller.

Voltage drop. On 16 mm²: 2.8 × 28 × 160 ÷ 1000 = 12.54 V, which is 5.7% of 220 V. On 25 mm²: 1.75 × 28 × 160 ÷ 1000 = 7.84 V, or 3.6%. On 35 mm²: 1.25 × 28 × 160 ÷ 1000 = 5.6 V, or 2.5%.

Answer: 35 mm² if you want the motor to see a clean 3%, 25 mm² if a 5% budget is acceptable for your supply and starter. Either way the size is two or three steps above what the current asked for, and the choice between them is a decision about the budget rather than about the pump. On a supply that already sags at the tail of a rural feeder, take the larger one — the motor is spending the whole difference.

A 160 m feeder is also exactly where aluminium earns its keep: the cost per metre is lower and the length is where that shows. The size steps up for the same current because aluminium carries less than copper at the same cross-section, and the per-size figures are on aluminium cable with the trade-off set out in copper vs aluminium. Terminate aluminium only with lugs rated for it.

Cable for tube wells and farm equipment

Cable is priced off the day's copper rate, so we quote per metre and per coil on WhatsApp rather than publish a figure that goes stale. Send the pump's plate current, the one-way metres and your city: Punjab in 1–2 days, rest of Pakistan in 2–4.

What to have ready before you ask for a rate

Read the plate, not the sticker

The current on the motor's rating plate is the figure the cable is sized against. Horsepower on the box tells us nothing about what the feeder has to carry.

Measure the route, not the map

Pace the actual one-way run from the meter to the well head, along the way the cable will go, and add a few metres at each end. On a farm that route is rarely straight.

Say buried or overhead

A buried run needs armour and rates lower than the same cable in air. Tell us which, and whether the trench crosses ploughed ground, and we quote the right construction the first time.

Questions farm buyers ask

What size cable for a tube well 150 metres from the meter?
Start from the current on the pump's plate, not its horsepower. At 30 A over 150 m, 16 mm² copper drops 2.8 × 30 × 150 ÷ 1000 = 12.6 V, which is 5.7 percent of 220 V and too much. 25 mm² drops 7.88 V and 35 mm² drops 5.63 V. Every one of those sizes carries 30 A comfortably, so on a run this long the distance picks the size and the current does not.
Tube well ke liye kitne mm ki cable chahiye?
Do alag cable hain. Bore ke andar jane wali drop cable pump ke saath aati hai ya pump wale ki specification par li jati hai — woh permanent paani mein rehti hai. Meter se well head tak ki feeder cable alag hai, aur uska size faasle se tay hota hai. 30 amp par 150 meter ki run 16 mm² par 12.6 volt kha jati hai, 25 mm² par 7.88 volt aur 35 mm² par 5.63 volt. Plate ka current dekh kar chalein, horsepower se nahi.
Can I use aluminium cable for the run out to the well?
On a long field feeder it is the case aluminium was made for: the cost per metre is lower and the run is exactly where that matters. An aluminium conductor carries less current than copper of the same cross-section, so the size steps up for the same load, and the per-size figures are on the aluminium cable page. Terminate it only with lugs rated for aluminium, and keep copper for the short heavily worked ends at the panel.
Why does the pump run slow, hum or trip on a long field run?
Usually volts, not the pump. A motor at the end of a long undersized feeder sees less voltage than the meter does, and it answers by drawing more current, running hotter and tripping the overload — which then gets blamed on the starter. Measure the voltage at the well head while the pump is running, not at the meter. If the difference is large, the cable is the fault and a size up is the fix.

Send the plate current and the metres

Tell us the current printed on the pump's plate, the one-way distance from the meter to the well head, and whether the run is buried or on poles. You get the size and the day's factory rate, dispatched by courier or transport.

WhatsApp for a quote