Skip to content
Factory-direct from Lahore · Nationwide delivery in 2–4 days +92 319 4262451 WhatsApp

What size cable for a submersible pump — by HP and run length

PILONE CABLES TECHNICAL TEAM

There is no one size. A 1 HP pump on a 220 V supply takes 1.5 mm² out to 63 m, 2.5 mm² out to 102 m and 4 mm² out to 167 m. The run length picks the size, not the horsepower alone.

This page is for a pump hanging in the water at the bottom of a borehole or tubewell. If your pump sits on the ground and fills an overhead tank, the run is short and the sums are different — that job is on cable for a water motor.

Measure the whole route before you pick anything: borehole depth, plus wellhead to the starter panel, plus panel back to the board. Every size below is worked against a 5% voltage-drop budget on 220 V, which is 11 V. Your motor's nameplate current beats the assumed current in every row.

Submersible pump cable size chart, mm² by HP and metres

Find your horsepower down the side, your total one-way run along the top, and read the size. Nothing in this table is copied from another chart — every cell is the smallest size whose voltage drop stays inside 11 V at the assumed current, and the arithmetic is in the next section so you can check it.

Smallest copper size that holds voltage drop inside 5% of 220 V (11 V) at the assumed full-load current, and still carries the recommended MCB. Run is one way, along the route the cable actually takes. Single-phase 220 V, two loaded conductors. Voltage drop and current capacity per BS 7671, reference method C (clipped direct), 30°C ambient; conductor data per IEC 60228. The assumed currents are typical plate figures — use the full-load current printed on your own motor if it differs. Verify sizing with a licensed electrician for your installation.
PumpAssumed FLC10 m25 m50 m75 m100 m150 m200 m
0.5 HP3.5 A1.51.51.51.51.52.54
1 HP6 A1.51.51.52.52.546
1.5 HP8.5 A1.51.52.544610
2 HP11 A2.52.52.5461010
3 HP16 A2.52.546101016
5 HP26 A66610161625

Sizes are mm². Two rows carry a floor that voltage drop alone would not set: a 2 HP pump on a 20 A breaker cannot sit on 1.5 mm², because 1.5 mm² is rated 19.5 A and the cable must carry more than the breaker; a 5 HP pump on a 40 A breaker starts at 6 mm² for the same reason. The single HP figure you were given at the pump shop is right only at one length, and it is over-spec at the short end and unsafe at the long end everywhere else. That is the whole case for reading a chart with metres in it.

Three phase changes these numbers completely, and in your favour: a 400 V supply gives nearly twice the drop budget — 20 V instead of 11 V — at about a third of the current. Those runs are on 3 HP motor cable size and 5 HP motor cable size.

Why voltage drop picks the size, not the current rating

A 2.5 mm² copper cable is rated 27 A. A 2 HP pump draws about 11 A. On the current rating alone, 2.5 mm² looks like twice the cable you need at any length. It is not, and here is the number that says so: at 80 m that same cable loses 15.8 V of the 220 the motor was meant to get.

The formula is one line, and every chart on this page is built from it. Volts lost = mV/A/m × amps × metres ÷ 1000. The mV/A/m figure is a property of the conductor size, published in BS 7671. Turn the formula round and it gives the longest run each size can feed inside an 11 V budget: metres = 11,000 ÷ (mV/A/m × amps).

Longest one-way run that keeps voltage drop inside 5% of 220 V, single phase. Derived as 11,000 mV ÷ (mV/A/m × assumed FLC). Voltage drop values per BS 7671, reference method C, 30°C, copper, PVC; conductor and stranding data per IEC 60228. Long entries are the physics, not a recommendation — check current capacity and mechanical suitability too. Verify sizing with a licensed electrician for your installation.
SizeTrade codemV/A/m1 HP, 6 A2 HP, 11 A3 HP, 16 A5 HP, 26 A
1.5 mm²3/.0292963 m34 m23 m14 m
2.5 mm²7/.02918102 m56 m38 m23 m
4 mm²7/.03611167 m91 m63 m38 m
6 mm²7/.0447.3251 m137 m94 m58 m
10 mm²7/.0524.4417 m227 m156 m96 m
16 mm²7/.0642.8655 m357 m245 m151 m

Read the 2.5 mm² row against its 27 A rating and the point lands: the cable runs out of volts at 56 m on a 2 HP pump while still carrying less than half the current it is rated for. Past about 50 m, heat stops being the question. Most published pump charts show you the answer without the budget they used, so you cannot check them. This one shows both.

Best wire for submersible pump work: two cables, one job

A tubewell circuit is two purchases, and confusing them is how boreholes get pulled twice in a year. The length that hangs in the water is a drop cable: it needs insulation built to sit permanently submerged, and the maker has to say so on the drum. The length from the wellhead junction to the starter panel, and from the panel back to the distribution board, is ordinary dry-side cable.

Our catalogue is PVC and XLPE copper flexible cable, standard cable, aluminium and solar DC. There is no submersible-rated drop cable in it. Buy the wet length from a maker who states an immersion rating, and check that rating yourself before it goes down the hole. What we draw is the copper for the dry side of the same job, at the day's factory rate.

The sizing does not split, though. Voltage drop accumulates over the whole route, wet metres and dry metres together, so size both parts to the same total length. If the drop cable is 4 mm², the surface run should not be thinner.

Never joint or splice cable inside the well — run one continuous length from the motor to the wellhead. Fit dry-run protection and an overload relay sized to the motor, earth the pump body and the delivery pipe, and confirm the drop cable's immersion rating with its maker. Current capacities here assume method C at 30°C; derate for conduit, burial and grouping. Have a licensed electrician confirm the size and the protection for your installation, or start with the cable size calculator.

Work out the length first, then the size

Almost every wrong pump cable starts as a wrong length. The depth of the bore is only the first of three runs, and the pump shop usually asks for that one alone.

1. Total the route

Bore depth 150 ft, wellhead to the panel 50 ft, panel to the board 20 ft. That is 220 ft. In metres: 220 × 0.3048 = 67 m.

2. Take the current from the plate

A 2 HP single-phase pump is assumed at 11 A here. Read your own plate: the full-load current is printed on it, and it is the only figure specific to your motor.

3. Read the row, then check it

2 HP at 67 m falls between the 50 and 75 m columns, so take the longer one: 4 mm². Then prove it with the formula.

The check on 2.5 mm² first, because that is what gets sold for a 2 HP pump: 18 × 11 × 67 ÷ 1000 = 13.3 V, which is 6.0% of 220 V and over the budget. Step up to 4 mm²: 11 × 11 × 67 ÷ 1000 = 8.1 V, which is 3.7%. That passes, with room. Stretch the same pump to an 80 m total and 2.5 mm² loses 18 × 11 × 80 ÷ 1000 = 15.8 V, a 7.2% drop, while 4 mm² loses 9.7 V and holds at 4.4%.

Buy to the measured route plus a working allowance at each end, not to the bore depth. Check your own figures in the voltage drop calculator before you order the coil.

1 HP water pump wire size in mm, and the strand code at the counter

Ask for a size in mm² in a Pakistani shop and you get answered in strand codes. The codes are imperial — 7/.036 is seven strands of 0.036 inch — so the area they compute to does not land exactly on the metric size they are sold as. Both names are on the same drum, and this is the translation.

Trade strand code to metric size, with the two numbers that decide a pump run. Actual area is the imperial code multiplied out; sold-as is the IEC 60228 nominal size it is supplied against. Current capacity is two loaded conductors, BS 7671 reference method C, 30°C, copper, PVC. Verify sizing with a licensed electrician for your installation.
Trade codeActual areaSold asCurrent capacityVoltage dropLongest run, 1 HP
3/.0291.29 mm²1.5 mm²19.5 A29 mV/A/m63 m
7/.0293.0 mm²2.5–3 mm²27 A18 mV/A/m102 m
7/.0364.6 mm²4 mm²36 A11 mV/A/m167 m
7/.0446.9 mm²6–7 mm²46 A7.3 mV/A/m251 m
7/.0529.6 mm²10 mm²63 A4.4 mV/A/m417 m
7/.06414.5 mm²16 mm²85 A2.8 mV/A/m655 m

So for a 1 HP borehole pump the shop answer is 3/.029 on a short run and 7/.029 once the total route passes 63 m. One warning about imported charts: American tables give AWG, and the millimetre figure quoted beside an AWG number is usually the conductor diameter, not its area. Number 14 AWG is 1.6 mm across and 2.08 mm² in area. Read one as the other and a pump circuit ends up a size and a half light.

When the supply is already down to 200 V

Rural feeders in Punjab and Sindh often sit well under 220 V through the afternoon, and not one of the pump charts that rank for this search starts from that. It matters twice over. The motor's power draw does not fall with the voltage, so the current rises to make it up, and the percentage budget itself shrinks because it is a percentage of a smaller number.

Take the 2 HP pump on an 80 m run again, with the wellhead seeing 200 V. Current becomes 11 × 220 ÷ 200 = 12.1 A. The 5% budget becomes 10 V, not 11. On 4 mm²: 11 × 12.1 × 80 ÷ 1000 = 10.6 V, which is 5.3% and now outside the budget. Step to 6 mm²: 7.3 × 12.1 × 80 ÷ 1000 = 7.1 V, or 3.5%. If your supply sags, go one size up from the chart and measure the voltage at the panel while the pump is running, not while it is off.

Starting current, the breaker and the starter

Every figure above is a running figure. A direct-on-line motor draws several times its full-load current for the first second or two, and that transient is what stalls a pump at the end of a long cable: the drop that is 4% at running current is a multiple of that at start, so the motor is asked to break away on a badly reduced voltage. It heats, it hums, it trips the overload, and eventually the winding goes. A cable that is correct on the running sums has already dealt with most of this; a cable chosen without any length in the calculation has not.

Protection for a single-phase 220 V pump circuit, at the assumed full-load currents used in the chart above. The MCB must sit above the running current and below the cable's capacity, and the overload relay is set from the nameplate, not from this table. Type C curve rides the starting surge. Verify with a licensed electrician for your installation.
PumpAssumed FLCMCBSmallest cable that clears the MCB
0.5 HP3.5 A10 A type C1.5 mm² (19.5 A)
1 HP6 A16 A type C1.5 mm² (19.5 A)
1.5 HP8.5 A16 A type C1.5 mm² (19.5 A)
2 HP11 A20 A type C2.5 mm² (27 A)
3 HP16 A25 A type C2.5 mm² (27 A)
5 HP26 A40 A type C6 mm² (46 A)

Take whichever is larger, this size or the one the run length asks for. On any tubewell past 50 m the run length wins every time.

1 HP water pump ke liye kitne mm ka wire chahiye?

Yeh sirf HP se tay nahi hota — lambai bhi dekhni parti hai. 1 HP pump 220 volt par takreeban 6 amp leta hai. Kul lambai 63 meter tak ho to 1.5 mm² (3/.029) kaafi hai, 102 meter tak 2.5 mm² (7/.029), aur 167 meter tak 4 mm² (7/.036). Kul lambai ka matlab hai boring ki gehrai, phir wellhead se panel tak, phir panel se meter tak — teenon jama karke.

Boring ke andar wala hissa alag cheez hai: uske liye submersible drop cable chahiye jiska paani mein rehne ka rating drum par likha ho. Hum woh nahi banate. Panel aur board wali dry side ka copper hum khud Lahore mein banate hain, aur usi din ke rate par milta hai.

The cable for the dry side of the job

Coil of four-core flexible copper cable with a black PVC outer sheath, of the type used between a tubewell starter panel and the distribution board
4MM² · 4 CORE · 300/500 V · CU CLASS 5

4mm 4 Core Flexible Cable

Class 5 stranded copper, PVC insulated and sheathed, 300/500 V, drawn on the Pilone line in Lahore. Rated 32 A on three loaded conductors and 11 mV/A/m — the wellhead-to-panel and panel-to-board run on a three-phase tubewell. For a single-phase pump the same run takes three cores.

Factory-direct price
Contact for quote
Message us for today’s rate
WhatsApp for today's rate

Copper cable is priced off the day's copper rate, so we quote per metre and per coil on WhatsApp. Send the HP, the total metres and your city.

Same size, other constructions: 4mm 3 core flexible cable for a single-phase surface run, 4mm 3 core standard cable for a fixed run in conduit. Longer routes step up to 6mm 4 core cable and 10mm 4 core cable; the rates are on 1 HP and 2 HP motor cable price.

Frequently asked

1 HP water pump ke liye kitne mm ka wire chahiye?
Lambai par depend karta hai. 1 HP pump 220 volt par takreeban 6 amp leta hai: 63 meter tak 1.5 mm² (3/.029), 102 meter tak 2.5 mm² (7/.029), 167 meter tak 4 mm² (7/.036). Lambai kul milaa kar naapein — boring ki gehrai, wellhead se panel, aur panel se board tak.
What size cable for a 1 HP submersible pump at 100 feet?
100 ft of bore is 30 m, but that is not the run. Add the wellhead-to-panel and panel-to-board lengths first. If the total comes to 50 m or less, 1.5 mm² holds the drop inside 5% at 6 A. Between 63 and 102 m total, take 2.5 mm².
Does the cable size change with the depth of the borehole?
Yes, and depth is usually the largest single part of the run. Volts lost = mV/A/m × amps × metres ÷ 1000, so doubling the depth doubles the loss on the same size. A 1 HP pump that is comfortable on 1.5 mm² at 50 m needs 2.5 mm² by 100 m and 4 mm² by 150 m.
What is the best wire for a submersible pump?
The right size for your run in the right construction — there is no brand answer, and anyone selling you one is not looking at your metres. Below the water it must be a drop cable with a stated immersion rating. Above ground it is ordinary copper, sized off the total route as in the chart above.
3 core or 4 core cable for a submersible pump?
Count the conductors the motor actually needs. A three-phase pump takes three phases plus earth, so 4 core. A single-phase pump takes live, neutral and earth, so 3 core — unless it has a separate start winding brought out, in which case the maker specifies the fourth core. The size does not change with the core count; the run length sets that.
Can I use ordinary flexible cable inside the borehole?
No. Ordinary PVC flexible cable is built for a dry protected run. The length inside the well sits in water permanently and needs insulation rated for immersion, stated by its maker. Use ordinary copper only for the dry part of the circuit, from the wellhead junction to the panel and the board.
Flat cable or round cable for a borewell?
Flat drop cable sits closer to the rising main and passes more easily through a tight bore and the clamps; round cable is bulkier but simpler to handle in long lengths. Electrically they are the same at the same conductor size — the choice is clearance in the bore, not current. Size it off the run either way.
How much voltage drop is acceptable for a pump motor?
This page works to 5% of the supply, which is 11 V on 220 V, and treats 3% as the comfortable target on a run you can afford to upsize. Beyond 5% the motor starts hard, runs hot and loses torque exactly when the head is highest. Measure at the panel with the pump running, not standing.
How do I work out the total cable length I need to buy?
Add three runs: the depth the pump hangs at, the wellhead to the starter panel, and the panel back to the distribution board. Convert feet to metres by multiplying by 0.3048. Then add a working allowance at each termination. 150 ft plus 50 ft plus 20 ft is 220 ft, which is 67 m.
Why does my motor run hot, trip or burn out on a long run?
Usually undersized cable. Low voltage at the motor terminals makes it draw more current for the same work, which heats the winding and trips the overload. Check the size against the total run first, then the supply voltage at the panel while the pump is running. See voltage drop problems and wire size too small.

Send the HP, the depth and the total run

We draw the copper in Lahore and sell it at the day's rate — no dealer margin. Give us the horsepower, the bore depth and the surface run with your city, and one message comes back with the size and the number: Punjab in 1–2 days, rest of Pakistan in 2–4.

WhatsApp the pump details