Skip to content
Factory-direct from Lahore · Nationwide delivery in 2–4 days +92 319 4262451 WhatsApp

Cable for construction sites

PILONE CABLES TECHNICAL TEAM

On a site the cable moves. That makes the conductor's construction as much of a decision as its size: class 5 flexible copper for anything that gets recoiled and re-routed, class 2 standard cable for the parts that stay put.

The two are not the same conductor at the same nominal size. Class 5 is built from many fine strands so it survives handling, and it carries up to about 7 percent more resistance than class 2 of the same mm² — 25 mm² is 0.727 Ω/km as class 2 against 0.78 Ω/km as class 5, though the penalty varies by size and disappears at 50 mm². That difference is small on a short tail and it is real on a 90-metre temporary run at the edge of a voltage-drop budget. Both tables are below.

What a site actually does to a cable

A construction load is unlike a building load in three ways. It is intermittent, so the connected total badly overstates the demand. It is mobile, so the cable is re-routed every few weeks as the work moves up the structure. And it is short-lived but reused, so the same coil is expected to serve the next job. Almost nothing that fails on a site fails because the conductor was too thin.

The runs on an ordinary site, what wears them out, and which conductor construction suits each. Class 2 is stranded copper for fixed wiring; class 5 is fine-stranded flexible copper. Conductor classes per IEC 60228. Temporary installations still need proper protection, earthing and RCD arrangements — have a licensed electrician set up and inspect the site supply.
Run on the siteDutyWhat actually kills itConstruction
Supply to the main site boardWhole site, weeks or months in one placeVehicles and trench crossingsFixed class 2, armoured where exposed
Site board to sub-boards up the structureMoves up a floor at a timeRe-termination and rough haulingClass 5 flexible, cut long
Mixer, vibrator, bar bender, cutterPlugged in and dragged dailyAbrasion on rebar and rubbleClass 5 flexible, sheathed
Welding setHeavy, intermittent drawBeing run while still on the drumClass 5, fully unwound in use
Site cabins, offices, security lightingSteady, fixed for the job's durationStanding water at joints and boxesFixed class 2, elevated route
Tower crane or hoist supplyHeavy motor starts, constant vibrationTerminations working looseFixed class 2, properly clamped
Two site habits do more damage than undersizing. Running a cable while it is still coiled on the drum traps its own heat, so the middle of the coil cooks long before the breaker notices — run the full length out before putting load on it, and see why a cable overheats. And a joint made with tape in the open is a site's most common fault path. Temporary supplies still need real protection, earthing and RCD arrangements, set up and inspected by a licensed electrician.

Class 2 or class 5: the same size is not the same conductor

A 25 mm² cable has 25 mm² of copper in it whichever class it is, but the copper is arranged differently and the measured resistance is not identical. Class 2 uses a few thick strands and sits still. Class 5 uses many fine ones so it can be coiled and uncoiled without work-hardening — which is exactly what a site cable does — and pays a small penalty in resistance for it.

Conductor resistance at 20°C and typical strand construction per IEC 60228, class 2 (stranded, fixed wiring) against class 5 (fine-stranded, flexible). The difference column is (class 5 − class 2) ÷ class 2, to one decimal place. Current capacity is read against the nominal size and is not changed by the class. Verify sizing with a licensed electrician for your installation.
SizeClass 2 strandsClass 2 resistanceClass 5 strandsClass 5 resistanceDifference
4 mm²7/0.854.61 Ω/km56/0.304.95 Ω/km+7.4%
6 mm²7/1.043.08 Ω/km84/0.303.30 Ω/km+7.1%
10 mm²7/1.351.83 Ω/km80/0.401.91 Ω/km+4.4%
16 mm²7/1.701.15 Ω/km126/0.401.21 Ω/km+5.2%
25 mm²7/2.140.727 Ω/km196/0.400.78 Ω/km+7.3%
35 mm²19/1.530.524 Ω/km276/0.400.554 Ω/km+5.7%
50 mm²19/1.780.387 Ω/km396/0.400.386 Ω/km−0.3%

The last row is worth noticing: at 50 mm² the two classes come out level, and one of them is a hair lower. That is a reminder that this is measured conductor data rather than a rule of thumb, and that the sensible way to use the table is to check the size you are actually buying instead of assuming a fixed penalty. Nothing here changes the current rating — capacity is read against the nominal size, and against the way the cable is installed.

Worked example: 70 A site board, 90 metres out

A temporary supply feeding a site distribution board 90 metres away across the plot, drawing 70 A three-phase at 415 V, run on the surface and lifted over the access road.

Capacity. 25 mm² is 96 A with three loaded conductors at 30°C. Take the ambient and grouping factors for a site run as multiplying to 0.80 — yours come from BS 7671, not from this page — and 96 × 0.80 = 76.8 A, which clears 70 A.

Voltage drop, class 2. The three-phase figure for 25 mm² is 1.5 mV/A/m, so 1.5 × 70 × 90 ÷ 1000 = 9.45 V against a 2.5% budget of 10.4 V on 415 V. It passes, with 0.95 V of margin.

Voltage drop, class 5. Now buy the same size as flexible so the run can be recoiled when the board moves. Conductor resistance goes from 0.727 to 0.78 Ω/km, which is 7.3% more, and the drop scales with it — close enough at these sizes, where reactance is a small part of the total. 9.45 × 1.073 = 10.14 V. Still inside 10.4 V, but the margin has fallen from 0.95 V to 0.26 V.

Answer: 25 mm² will do it today, and 35 mm² is the size to buy. A site board does not stay where it was first put. Add twenty metres when the work moves and the class 5 run is over budget; on 35 mm² the same 90 m is 1.1 × 70 × 90 ÷ 1000 = 6.93 V as class 2, or about 7.33 V as class 5, with room for the move. Buying one size up on a temporary run is not waste — the coil goes to the next job. Check your own numbers in the voltage drop calculator, and the full kW to mm² ladder is on 3-phase cable size.

Cable for site feeds and temporary supplies

The fixed site sizes that leave the Lahore line most often are 25mm 4 core cable and 16mm 4 core cable. Cable is priced off the day's copper rate, so we quote per metre and per coil on WhatsApp rather than publish a figure that goes stale — send the board schedule or a bill of quantities as a photo, with your city: Punjab in 1–2 days, rest of Pakistan in 2–4.

How to order for a site rather than a building

Split the list in two

Mark every run as fixed or mobile before you price anything. The fixed runs go on class 2 standard cable; the runs that will be moved go on class 5 flexible, and the two are ordered differently.

Size the longest run, not the average

The board furthest from the supply sets the size for that circuit, and it is usually the one that gets moved further still. Give us the worst case and the load on it.

Buy in whole lengths

Cable is sold by the coil and coil lengths differ between makers, so ask for the coil length with the rate. On a site, a joint in the middle of a run is a fault waiting for the wet season.

Questions site buyers ask

What size cable for a site distribution board 90 metres from the supply?
At 70 A three-phase, 25 mm² is 96 A with three loaded conductors at 30°C. On an illustrative combined factor of 0.80 that is 76.8 A, which clears 70 A. The three-phase drop is 1.5 × 70 × 90 ÷ 1000 = 9.45 V against a 2.5 percent budget of 10.4 V on 415 V, so it passes with under a volt in hand. On a board that will be moved further out, take 35 mm² instead.
Is flexible cable OK for a construction site, or does it have to be standard?
Flexible is usually the honest choice for anything that gets moved, because class 5 copper is built from many fine strands and survives coiling and re-routing that would work-harden a class 2 conductor. It costs a little in volts: at the same nominal size class 5 runs up to about 7 percent more conductor resistance than class 2, and the penalty varies by size — check the size you are buying. Use fixed class 2 cable for the parts of the site that stay put, such as the incoming supply and the cabins.
Why does a cable overheat when it is used still coiled on the drum?
Because every current rating assumes the cable can lose its heat. A coil is dozens of turns heating each other with no way out, so the middle of the drum gets far hotter than the same cable would lying out straight, and the insulation can be damaged long before the breaker sees anything wrong. Run out the full length before putting load on it. This is the most common avoidable cable failure on a site.
Site par kaunsi cable chalti hai — standard ya flexible?
Dono, magar alag jagah. Jo cable roz hilti hai — mixer, vibrator, bar bender, temporary lighting — us par class 5 flexible chalti hai, kyunke uske baareek strands baar baar lapetne se nahi tootte. Jo cable ek jagah lag kar khari rehti hai — supply se site board tak, cabin ki wiring — us par class 2 standard cable behtar hai. Class 5 mein usi size par takreeban 7 percent tak zyada resistance ho sakti hai, aur yeh har size par mukhtalif hai, is liye lambi run par ek size ooper le lein.

Send the board schedule and the metres

Tell us the board loads, the distances, and which runs will be moved during the job. We come back with sizes, the class that suits each run, and the day's factory rate — a bill of quantities gets a line-item answer.

WhatsApp for a quote