A datasheet is what the maker declares. A test report is what a laboratory measured on a sample. Read the datasheet for the eight lines below, and treat a claim of compliance with a standard as a claim until you see evidence for it.
The lines that matter most are the conductor class, the nominal area, the maximum conductor resistance, the insulation material and its temperature, and the voltage rating. Strand codes such as 7/.029 are a construction, not a size; the size is the nominal mm², and that is defined by resistance.
Layouts differ between makers, but a datasheet for building or power cable should let you answer each of these. A missing line is a question to ask, not necessarily a problem.
| Field | Typical entry | What it tells you |
|---|---|---|
| Conductor material | Plain annealed copper, or aluminium | Copper and aluminium need different sizes for the same job |
| Conductor class | Class 1 solid, class 2 stranded, class 5 or 6 flexible | How flexible the cable is, and which resistance limit applies |
| Nominal cross-section | 2.5 mm² | The size you are buying |
| Maximum conductor resistance at 20 °C | 7.41 Ω/km for 2.5 mm² class 2 | The number that actually defines the nominal size |
| Insulation and sheath material | PVC, XLPE; PVC sheath | Sets the maximum conductor temperature |
| Maximum conductor temperature | 70 °C (PVC), 90 °C (XLPE) | Feeds into current rating, not a room temperature |
| Rated voltage U0/U | 300/500 V, 450/750 V, 0.6/1 kV | The systems the cable is designed for |
| Standard declared | IEC 60227, IEC 60502-1, BS 6004, EN 50618 | The rules the maker says the cable is built to |
Dimensions such as insulation thickness and overall diameter are useful for glands, conduit fill and connectors. Weight per kilometre is useful for transport. Neither tells you the conductor size on its own.
IEC 60228 does not define a 2.5 mm² conductor by measuring its area. It defines it by a maximum resistance per kilometre at 20 °C, and for some classes a minimum number of wires. A conductor that meets the resistance limit is 2.5 mm² for the purposes of the standard; one that does not, is not, whatever the area on the label.
Strand codes used in Pakistan, such as 3/.029 or 7/.029, describe the build: the number of strands and each strand's diameter in inches. You can work out the geometric area from them, but that is a calculation, not the nominal size, and the resistance still has to be checked. The strand code guide converts each common code, and the product pages for 3/.029 and 7/.029 show how the two are described.
| Class | Build | Typical use |
|---|---|---|
| 1 | Solid, one wire | Fixed wiring in small sizes |
| 2 | Stranded, a few thicker wires | Fixed wiring and power cable |
| 5 | Flexible, many fine wires | Flexible cords, panel wiring, solar DC cable |
| 6 | Extra flexible, finer still | Welding and highly flexible leads |
The rating U0/U gives two voltages: U0 between a conductor and earth, U between conductors. House wiring in PVC is commonly 450/750 V; light flexible cords 300/500 V; low-voltage power cable such as IEC 60502-1 types 0.6/1 kV. Solar DC cable to EN 50618 or IEC 62930 is rated for 1.5 kV DC. A rating higher than the system needs is fine; lower is not.
The temperature on a datasheet is the maximum the conductor may reach in normal service: about 70 °C for general PVC and 90 °C for XLPE. It is one input to a current rating, alongside the installation method, ambient temperature and grouping. A datasheet current figure is only valid under the conditions printed next to it. The PVC vs XLPE guide explains what the extra rating buys.
Three different documents get called "the certificate". They carry very different weight.
| Document | Who produces it | What it shows | Questions to ask |
|---|---|---|---|
| Datasheet or catalogue | The maker | What the maker declares | Which standard? Which sizes does it cover? |
| Routine test record | The maker, on production | Checks run on each length, for example conductor resistance or a voltage test | Which tests, on which batch? |
| Type test report | A laboratory, on a sample | The full set of tests a standard requires, done once on a cable design | Which lab? Is it accredited (ISO/IEC 17025) for those tests? Which size and design, and when? |
| Product certification | A certification body | Ongoing surveillance of production against a standard | Is the certificate current, and does it name this product? |
A test report covers the sample that was tested. It does not cover a different size, a later design change, or a coil it was never connected to. Check the report names the cable you are buying.
The extract below is invented for teaching. It is not a Pilone datasheet or test result and does not describe any real cable. It shows how to read the lines against each other.
| Line on the sheet | Entry | How to read it |
|---|---|---|
| Construction | Cu / PVC / PVC, 3 core | Copper conductor, PVC insulation and sheath |
| Conductor | 2.5 mm², class 2, 7 wires | Stranded fixed-wiring conductor |
| Max resistance at 20 °C | 7.41 Ω/km | Matches the IEC 60228 class 2 limit for 2.5 mm² |
| Rated voltage | 450/750 V | Suitable for 230/400 V building wiring |
| Max conductor temperature | 70 °C | Consistent with general-purpose PVC |
| Current rating | "24 A" | Meaningless without the installation method and ambient temperature beside it: ask for them |
| Standard | "Conforms to IEC" | Too vague: ask which standard and part, and for the evidence |
Send the size, cores and metres you need. We reply with the specification Pilone declares for that cable alongside the quotation, so you can read one against the other.