Ask for the conductor resistance, not the copper purity. 2.5 mm² class 2 must not exceed 7.41 Ω/km; 4 mm² must not exceed 4.61.
Purity percentages are the standard currency of cable marketing in Pakistan and none of them can be checked by a buyer — we have seen no independent purity assay published here, and we publish none ourselves. IEC 60228 does not work in purity at all. It sets a maximum resistance for each size and each conductor class, and resistance is a number you can put a meter on in the shop. That is the honest ground for comparing Magna Cables, us, or anyone else.
Resistance is the property the whole cable depends on. It sets how much of your supply voltage the run loses and how much heat the conductor makes carrying its load, which is why the standard defines it and defines nothing about purity. A conductor that meets its resistance limit has enough well-drawn copper in it, whatever a marketing page says about the metal.
| Size | Class 2 max | Class 5 max | Class 2 per 100 m |
|---|---|---|---|
| 1.5 mm² | 12.1 Ω/km | 13.3 Ω/km | 1.21 Ω |
| 2.5 mm² | 7.41 Ω/km | 7.98 Ω/km | 0.741 Ω |
| 4 mm² | 4.61 Ω/km | 4.95 Ω/km | 0.461 Ω |
| 6 mm² | 3.08 Ω/km | 3.30 Ω/km | 0.308 Ω |
| 10 mm² | 1.83 Ω/km | 1.91 Ω/km | 0.183 Ω |
| 16 mm² | 1.15 Ω/km | 1.21 Ω/km | 0.115 Ω |
Take a 100 m coil of 2.5 mm² two-core. Short the two conductors together at the far end, then measure across the pair at the near end. You are reading the loop, so the figure to expect is 2 × 0.741 = 1.48 Ω. On 4 mm² over the same length the loop is 2 × 0.461 = 0.92 Ω.
Three honest cautions. Short your own probes together first and subtract that reading, because at these values the meter's leads are a large share of the answer. The limits are defined at 20°C, so measure a coil that has been out of the sun, and treat a hot coil's higher reading as heat rather than bad copper. And a hand-held meter resolving hundredths of an ohm is at the edge of its accuracy — the test catches a conductor that is badly undersized, not a 3% shortfall. For the check that is decisive with a kitchen scale instead, use the conductor mass test; for what the metal itself is, see checking the conductor, not the label.
We publish the resistance limits our conductors are drawn to, the stranding for each class, and the installation assumptions behind every current figure on this site, so all of it can be measured against us. We publish no test on Magna Cables' product, because we have not run one, and no purity figure at all, ours included, because a buyer cannot verify one. Pilone draws its cable in Lahore and sells at the day's copper rate — roots in the copper trade since 1992, the cable line running since about 2020, Punjab in 1–2 days and the rest of Pakistan in 2–4. The wider set of questions to put to any supplier is on how to choose a cable company in Pakistan.