Pilone vs Pioneer Cables: write the spec before you compare brands

PILONE CABLES TECHNICAL TEAM

Write the six fields down first: construction, conductor class, cross-section, cores, voltage rating, metres. Then ask for prices.

Most brand arguments in this trade are really one of those six fields quietly changing between two quotes — a two-core against a three-core, a class 5 flexible against a class 2, a short coil against a measured length. We hold no test data on Pioneer Cables' product and will not rank a competitor on nothing. What we can give you is the specification line that makes any two suppliers comparable, this one included.

The six fields that make a cable order

A cable order is six fields, not a brand name. Written out, one line reads: 4 mm² 3 core standard cable, IEC 60228 class 2 (7/0.85), 450/750 V PVC, 92 metres. Any two suppliers quoting that line are quoting the same cable, and the gap between their figures is then a real gap. Change one field and the two numbers stop being comparable.

The fields a supplier needs before a quote means anything. Conductor class and stranding per IEC 60228; insulation voltage rating per IEC 60227 — 450/750 V for fixed wiring cable, 300/500 V for light flexible cords. Current capacity per BS 7671 reference method C, clipped direct, 30°C ambient, PVC.
FieldWhat you writeWhat it decides
ConstructionStandard, flexible, armoured, solar DCWhere the cable is allowed to run, and whether it can bend
Conductor classClass 2 or class 5The stranding, and the maximum resistance the standard allows
Cross-section4 mm² (trade code 7/.036)The current capacity, and most of the price
Cores2, 3 or 4Whether the earth is inside the sheath — and the rating: 4 mm² is 36 A on two loaded cores, 32 A on three
Voltage rating450/750 VFixed wiring against a light appliance cord at 300/500 V
MetresThe measured run, both endsThe quote. Coil lengths differ between makers, so ask per metre

The field left blank most often is the second one, and it is the one that changes what you are holding.

Class 2 or class 5: what the class does and does not change

Class 2 is the rigid stranded conductor for fixed wiring — seven thicker strands, 7/0.67 at 2.5 mm². Class 5 is the flexible conductor, many fine strands, 50/0.25 at the same nominal size. Both are copper and both are IEC 60228; they are built for different jobs, not to different quality grades.

Stranding and maximum conductor resistance at 20°C per IEC 60228, plain annealed copper. Class 2 is the fixed-wiring conductor, class 5 the fine-stranded flexible one, whose limit the standard sets slightly higher at the same nominal size. Current capacity is read from the cross-section, so it is the same for both classes: BS 7671 reference method C, clipped direct, 30°C ambient, PVC, two loaded conductors. Derate for conduit, grouping and higher ambient temperature.
SizeClass 2 strandsClass 2 maxClass 5 strandsClass 5 maxCapacity, 2 cores
1.5 mm²7/0.5312.1 Ω/km30/0.2513.3 Ω/km19.5 A
2.5 mm²7/0.677.41 Ω/km50/0.257.98 Ω/km27 A
4 mm²7/0.854.61 Ω/km56/0.304.95 Ω/km36 A
6 mm²7/1.043.08 Ω/km84/0.303.30 Ω/km46 A
10 mm²7/1.351.83 Ω/km80/0.401.91 Ω/km63 A
16 mm²7/1.701.15 Ω/km126/0.401.21 Ω/km85 A

Read the last column across: the class does not move the amps. What it moves is the resistance ceiling — 7.98 ÷ 7.41 = 1.08 at 2.5 mm², so the standard allows a class 5 conductor about 8% more resistance than a class 2 of the same size. Compare standard cable against standard and flexible cable against flexible, or the two lines are not the same product.

Standard ya flexible — order mein kya likhein?

Deewar ke andar aur conduit mein jo wiring hamesha lagi rehti hai, uske liye standard cable likhein — class 2. Jahan cable mudta hai, jaise machine ka tail ya appliance ka cord, wahan flexible cable — class 5. Zameen ke andar ya jahan cable ko chot lag sakti hai, wahan armoured cable, aur solar ke DC side par solar DC cable, jo 90°C ke liye bana hota hai.

Why the core count is not a detail

The same 4 mm² copper is rated 36 A with two loaded conductors and 32 A with three, because three loaded cores share the heat. On a 20 A circuit that is 36 − 20 = 16 A of margin as a two-core and 32 − 20 = 12 A as a three-core, before any derating for conduit, grouping or summer ambient. The third core also carries the earth inside the sheath, which is usually why it is there.

So a quote that comes back a core short is not a better price, it is a different cable. Decide the core count from the circuit, then hold every supplier to it. Where the size itself is the open question, the arithmetic is in the 2.5mm vs 4mm cable guide; where the spec matches and the figures still differ, see why two quotes for the same cable differ.

A specification is not a design. Every current figure on this page is BS 7671 reference method C, clipped direct, 30°C ambient, PVC insulated copper, and must be derated for conduit, grouping and higher ambient temperature. Fix the size with a licensed electrician, or start with the cable size calculator, before you send the line to any supplier.

What we will and will not say about Pioneer Cables

We publish no measurement of Pioneer Cables' product, because we have not measured it, and no purity figure at all, ours included, because a buyer cannot verify one. What we publish is the specification our own cable is drawn and sold against: IEC 60228 conductor classes and their resistance limits, 450/750 V PVC insulation for fixed wiring, and the installation assumptions behind every current figure on this site. All of it can be checked on a sample — weigh it with the conductor mass test, or put a meter on it with the resistance test.

The rest is the route. Pilone draws its own cable in Lahore and quotes the day's factory rate straight to the buyer — roots in the copper trade going back to 1992, the cable line running since about 2020, Punjab in 1–2 days and the rest of Pakistan in 2–4. The wider set of questions to put to any supplier, ours included, is on how to choose a cable company in Pakistan.

Frequently asked

Pilone vs Pioneer Cables — which one should I buy?
Write the specification first, then ask both. We hold no test data on Pioneer Cables' product and will not rank a competitor on nothing. Once construction, conductor class, cross-section, cores, voltage rating and metres are fixed, the two quotes describe the same cable and you can judge them on the figure and the delivery. Where Pilone differs is the route: we draw the cable in Lahore and sell at the day's copper rate.
Standard cable ya flexible cable — ghar ki wiring ke liye kaun sa lein?
Deewar ke andar aur conduit mein jo wiring permanent lagti hai, uske liye standard cable lein — IEC 60228 class 2, saat moti strands. Flexible cable class 5 hai, bohat bareek strands se bana, aur woh wahan chahiye jahan cable mudta hai: machine ka tail ya appliance ka cord. Current dono ka ek jaisa hai — 2.5 mm² dono soorat mein 27 A.
What do class 2 and class 5 mean on a cable?
They are conductor classes under IEC 60228. Class 2 is the rigid stranded conductor for fixed wiring — seven thicker strands, 7/0.67 at 2.5 mm². Class 5 is the flexible conductor built from many fine strands, 50/0.25 at the same nominal size. The standard allows class 5 slightly more resistance: 7.98 Ω/km against 7.41 at 2.5 mm², which is about 8% more.
Does the conductor class change how many amps a cable carries?
No. Current capacity is read from the cross-section, so 2.5 mm² is 27 A and 4 mm² is 36 A on two loaded cores whether the conductor is class 2 or class 5 — BS 7671 reference method C, clipped direct, 30°C ambient, PVC. What the class changes is how the cable bends and the maximum resistance the standard allows.
How many metres of cable should I order?
Measure the route the cable takes, not the distance across the room: down the wall, along the chase, up to the point, plus about a metre of slack at each end. Add the runs together per size and per core count. Then ask for the rate per metre, because coil lengths are not the same between makers and a per-coil figure cannot be compared until you know its length.
What should a cable order line actually say?
Six fields in one line: construction, conductor class, cross-section, cores, voltage rating, metres. For example — 4 mm² 3 core standard cable, IEC 60228 class 2 (7/0.85), 450/750 V PVC, 92 metres. Send that identical line to every supplier. If a quote comes back against a different line, two cores instead of three or one coil instead of 92 metres, it is not a competing price.

Send us the line, not the brand

Construction, class, size, cores, voltage rating and metres — one message gets today's factory rate from Lahore against that exact spec, per metre and per coil.